The list · Commercial HVAC

Cooling a warehouse in Montréal: 5 HVAC solutions compared, from ventilation to the rooftop heat pump

9 min
Comparison · Guide · Warehouse

Cooling a warehouse: five ways to do it, and what each one does to July air

Roof exhaust, evaporative cooler, wall heat pumps by zone, variable refrigerant flow system, rooftop heat pump with ducts: none of them is the right answer for every warehouse. This guide puts side by side what each one does to the air, what it asks of the building and what Montréal's summer design conditions say, so you can decide for your own.

July, Montréal-Trudeau: 29.7 °C dry bulb · 23.4 °C wet bulb5 types of systems2 NEEP-certified examples
officedock12345diagram, not to scale

Operating cost

What electricity costs: the power drawn, not a dollar amount

A warehouse is not billed at the residential rate: depending on its demand, it falls under Hydro-Québec's Rate G or another business rate, with a demand charge above 50 kW that depends on what the whole building draws, lighting and machinery included. A dollar amount for a single unit would therefore be misleading. Instead, we show how much electricity each certified example draws while it cools, at 35 °C outside.

Ventilation and evaporative cooling: the power of an exhaust fan or an evaporative cooler depends on the model (fan motors, water pump). It is printed on the nameplate and the manufacturer's sheet for the unit you choose; we do not estimate it here. These two solutions do not do the same job as a heat pump, as the next section shows, and their kilowatts are not directly comparable.

Signature · July air

A July afternoon: what each solution does to the outdoor air

Natural Resources Canada's summer design conditions for Montréal-Trudeau are 29.7 °C dry bulb and 23.4 °C wet bulb. Pick a station or set the air yourself: ventilation blows in outdoor air, the evaporative cooler brings it closer to its wet-bulb temperature by adding water, the heat pump cools it and removes water from it.

How these values are calculated
  1. Outdoor air humidity: saturation vapour pressure from the Magnus-Tetens formula, then the psychrometric relation e = es(Twb) − 0.000662 × 101.325 kPa × (Tdb − Twb). Relative humidity = e ÷ es(Tdb).
  2. Evaporative cooler (direct): leaving temperature = Tdb − effectiveness × (Tdb − Twb), the definition of saturation effectiveness in chapter 41 of the ASHRAE Handbook (HVAC Systems and Equipment, 2016). The process is adiabatic: the wet-bulb temperature does not change, the relative humidity rises.
  3. Ventilation: the supply air is the outdoor air, with no change in temperature.
  4. Heat pump: no leaving temperature is calculated here; it depends on the unit and its airflow. The page gives the certified capacity at 35 °C of the two examples.

AirGreen calculation, at sea level, accurate to about one point of relative humidity. It is meant to compare principles, not to size a unit.

The five solutions

What each one does, what it asks of the building

The earlier article on this blog presented these five approaches. We keep them, in the same order, with what can be checked for each; the field tests and job-site results it quoted have been removed, since no document supports them.

Side by side

The five types of systems, row by row

This table compares operating principles, not models. It ranks nothing: the right column depends on what you want to achieve in your warehouse.

What matters1. Roof exhaust2. Evaporative cooler3. Wall heat pumps4. Variable refrigerant flow (VRF)5. Rooftop heat pump with ducts
Supply air compared with outdoor airAt outdoor air temperatureCooler, down to the outdoor wet-bulb temperature at bestCooler than outdoor airCooler than outdoor airCooler than outdoor air
Humidity of the supply airSame as outdoor airRises: the evaporated water goes into the airFalls: condensed water is drainedFalls: condensed water is drainedFalls: condensed water is drained
Winter heatingDoes not heatDoes not heatAlso heats (heat pump)Also heats, depending on the systemAlso heats (heat pump)
ZoningThe whole ventilated volumeOne zone blown in front of the unitOne zone per indoor unitSeveral indoor units on one outdoor unitThe zones the ducts reach
Open loading-dock doorsWorks with an outdoor air supplyNeeds an outdoor air supply to remove the humidityCool air is lost through open doorsCool air is lost through open doorsCool air is lost through open doors
RefrigerantNo refrigerantNo refrigerantYes, R-32 or R-454B on recent modelsYes, depending on the systemYes, R-32 for the example on this page
Water useNo waterContinuous make-up water, and bleed-off per the manufacturerNo water; condensate is drainedNo water; condensate is drainedNo water; condensate is drained
Certified performancePer the fan manufacturerPer the cooler manufacturerSEER2, EER2 and HSPF2, AHRI certificateBy size: SEER2 and HSPF2, or IEER and COPSEER2, EER2 and HSPF2, AHRI certificate
What the building needsRoof openings and air inletsWater supply, drain and powerAn outside wall or a stand for each outdoor unitRefrigerant piping between units, per the design manualA roof that can carry the unit, ducts and grilles

Sources: principles from chapter 41 of the ASHRAE Handbook (evaporative cooling); AHRI certificates and NEEP listings for the heat pumps. "Depending on the system": each VRF manufacturer publishes its own design limits.

Two certified examples

A 36,000 BTU wall unit and a 5-ton rooftop heat pump, figure by figure

To give real orders of magnitude, here are two heat pumps sold by AirGreen, of the same brand: a wall unit for a targeted zone (solution 3) and a packaged rooftop unit that feeds ducts (solution 5). They do not have the same capacity; they illustrate two ways of doing things, not a head-to-head.

Example · solution 3
AirGreen product card for the GREE LIVO R32 36,000 BTU wall heat pump
GREE LIVO R32 36,000 wall unit

Indoor LIV36HP230V1R32AH · outdoor LIV36HP230V1R32AO · AHRI 214779348

See the product page
Example · solution 5
AirGreen product card for the GREE Rooftop R32 5-ton packaged heat pump
GREE Rooftop R32 5 tons packaged rooftop unit

GK-H05TC/NhA-D(U) · AHRI 215866831

See the product page
Certified valueGREE LIVO R32 36,000GREE Rooftop R32 5 tons
Cooling · 35 °C outdoors
Rated capacity at 35 °C33,600 BTU/h56,000 BTU/h
Capacity min. / rated / max. at 35 °C7,850 / 33,600 / 37,000 BTU/h18,600 / 56,000 / 57,200 BTU/h
Electrical power drawn at 35 °C2.80 kWthat is, 0.83 kW per 10,000 BTU/h (AirGreen calculation)5.00 kWthat is, 0.89 kW per 10,000 BTU/h (AirGreen calculation)
SEER22118
EER21211.2
Heating · both also heat in winter
HSPF2 region IV / region V8.5 / 7.58.3 / 6.5
Capacity min. / rated / max. at 8.3 °C10,000 / 34,000 / 34,100 BTU/h13,700 / 57,000 / 58,200 BTU/h
Coldest certified point
Max. capacity at −15 °C (5 °F)24,600 BTU/h51,600 BTU/h
Coldest point published by NEEP21,000 BTU/h max. at −25 °C (−13 °F)28,500 BTU/h max. at −30 °C (−22 °F)
Listing
Certified configurationDuctless wall unit, one zonePackaged rooftop unit with ducts
RefrigerantR-32, GWP 675 (IPCC AR4), class A2LR-32, GWP 675 (IPCC AR4), class A2L
AHRI certificate · NEEP listing214779348 · 393213215866831 · 505248
ENERGY STAR, per NEEPYes, and cold climateYes, and cold climate

All values: NEEP listings 393213 and 505248, consulted on November 17, 2026. Cooling is certified at 35 °C outdoors (condition A of the AHRI 210/240 standard). On NEEP, the GREE Rooftop R32 shows a higher rated capacity at −15 °C (51,000 BTU/h) than at −8.3 °C (34,000 BTU/h); the page shows the values as published. The two units are not the same size, so the table marks nothing "higher".

Questions

What people ask us about cooling a warehouse

Does the whole warehouse need to be cooled?

Not necessarily. If staff work mainly in packing, receiving or built-in offices, cooling those zones takes far less capacity than the whole volume under the roof. Wall heat pumps (one zone per unit) and VRF systems (several indoor units) lend themselves to that zoning; a rooftop heat pump serves the zones its ducts reach.

Does evaporative cooling work in Montréal?

It cools the air, but humidifies it. Chapter 41 of the ASHRAE Handbook states that direct evaporative cooling is not suitable for indoor comfort when the outdoor wet-bulb temperature is above about 21 °C (70 °F), and that it remains satisfactory for relief cooling in industrial settings. Montréal-Trudeau's summer design wet-bulb temperature is 23.4 °C. Use the "July air" section to see the effect for the day's humidity.

Can roof exhaust fans replace air conditioning?

They remove the heat that builds up under the roof and replace it with outdoor air. They cannot go below the outdoor air temperature: at 30 °C outside, the air coming in is at 30 °C. It is often a useful first step, not an equivalent of air conditioning.

Why is there no dollar amount on this page?

A business pays for electricity under a business rate (Rate G for small power, others above), with a demand charge above 50 kW based on what the whole building draws. The cost of one unit therefore depends on what runs at the same time. We show the certified power drawn at 35 °C; your bill and your rate let you convert it to dollars.

What does VRF mean?

Variable refrigerant flow: one outdoor unit feeds several indoor units by varying the amount of refrigerant sent to each. Piping lengths, the number of indoor units and the connected capacity are set by each manufacturer's design manual. Depending on size, performance is certified in SEER2 and HSPF2 or in IEER and COP.

Do the two examples also heat in winter?

Yes, they are heat pumps. Their certified heating points are in the table: 24,600 BTU/h max. at −15 °C for the GREE LIVO R32 36,000 and 51,600 BTU/h max. for the GREE Rooftop R32 5 tons, according to NEEP. Exhaust ventilation and evaporative cooling do not heat.

Is there financial assistance for a warehouse?

Programs change and depend on the building and the unit; we promise none and give no amount. Hydro-Québec's LogisVert program is aimed at homes; Hydro-Québec presents its business offers on its website.

A warehouse to cool?

The two heat pumps used as examples are on AirGreen's website. For a commercial building, call or write to us with your plans, the floor area and how the zones are used.

Sources

Documents consulted

Natural Resources Canada, HOT2000 Climate MapWeather station locations layer: MONTRÉAL INTL, MONTRÉAL-ST-HUBERT, MONTRÉAL MIRABEL INTL (July 2.5% design temperatures). Dataset modified February 15, 2024, consulted November 17, 2026.
ASHRAE Handbook — HVAC Systems and Equipment (2016), chapter 41Evaporative Air-Cooling Equipment: definition of saturation effectiveness, published ranges, limit of about 70 °F wet bulb for comfort. Consulted November 17, 2026.
NEEP, Cold Climate Air Source Heat Pump List, listing 393213GREE LIVO R32 36,000, LIV36HP230V1R32AO / LIV36HP230V1R32AH, AHRI 214779348. Consulted November 17, 2026.
NEEP, listing 505248GREE Rooftop R32 5 tons, GK-H05TC/NhA-D(U), AHRI 215866831. Consulted November 17, 2026.
Hydro-Québec, Electricity Rates effective April 1, 2026Chapter 3, section 1: Rate G (small power) and demand charge above 50 kW. Consulted November 17, 2026; rates change every year.
IPCC, Fourth Assessment Report (AR4)100-year global warming potential of R-32: 675.
You made it to the end.Share it with someone it could help.

Leave a comment