
Indoor LIV36HP230V1R32AH · outdoor LIV36HP230V1R32AO · AHRI 214779348
See the product pageRoof exhaust, evaporative cooler, wall heat pumps by zone, variable refrigerant flow system, rooftop heat pump with ducts: none of them is the right answer for every warehouse. This guide puts side by side what each one does to the air, what it asks of the building and what Montréal's summer design conditions say, so you can decide for your own.
A warehouse is not billed at the residential rate: depending on its demand, it falls under Hydro-Québec's Rate G or another business rate, with a demand charge above 50 kW that depends on what the whole building draws, lighting and machinery included. A dollar amount for a single unit would therefore be misleading. Instead, we show how much electricity each certified example draws while it cools, at 35 °C outside.
Ventilation and evaporative cooling: the power of an exhaust fan or an evaporative cooler depends on the model (fan motors, water pump). It is printed on the nameplate and the manufacturer's sheet for the unit you choose; we do not estimate it here. These two solutions do not do the same job as a heat pump, as the next section shows, and their kilowatts are not directly comparable.
Natural Resources Canada's summer design conditions for Montréal-Trudeau are 29.7 °C dry bulb and 23.4 °C wet bulb. Pick a station or set the air yourself: ventilation blows in outdoor air, the evaporative cooler brings it closer to its wet-bulb temperature by adding water, the heat pump cools it and removes water from it.
AirGreen calculation, at sea level, accurate to about one point of relative humidity. It is meant to compare principles, not to size a unit.
The earlier article on this blog presented these five approaches. We keep them, in the same order, with what can be checked for each; the field tests and job-site results it quoted have been removed, since no document supports them.
This table compares operating principles, not models. It ranks nothing: the right column depends on what you want to achieve in your warehouse.
| What matters | 1. Roof exhaust | 2. Evaporative cooler | 3. Wall heat pumps | 4. Variable refrigerant flow (VRF) | 5. Rooftop heat pump with ducts |
|---|---|---|---|---|---|
| Supply air compared with outdoor air | At outdoor air temperature | Cooler, down to the outdoor wet-bulb temperature at best | Cooler than outdoor air | Cooler than outdoor air | Cooler than outdoor air |
| Humidity of the supply air | Same as outdoor air | Rises: the evaporated water goes into the air | Falls: condensed water is drained | Falls: condensed water is drained | Falls: condensed water is drained |
| Winter heating | Does not heat | Does not heat | Also heats (heat pump) | Also heats, depending on the system | Also heats (heat pump) |
| Zoning | The whole ventilated volume | One zone blown in front of the unit | One zone per indoor unit | Several indoor units on one outdoor unit | The zones the ducts reach |
| Open loading-dock doors | Works with an outdoor air supply | Needs an outdoor air supply to remove the humidity | Cool air is lost through open doors | Cool air is lost through open doors | Cool air is lost through open doors |
| Refrigerant | No refrigerant | No refrigerant | Yes, R-32 or R-454B on recent models | Yes, depending on the system | Yes, R-32 for the example on this page |
| Water use | No water | Continuous make-up water, and bleed-off per the manufacturer | No water; condensate is drained | No water; condensate is drained | No water; condensate is drained |
| Certified performance | Per the fan manufacturer | Per the cooler manufacturer | SEER2, EER2 and HSPF2, AHRI certificate | By size: SEER2 and HSPF2, or IEER and COP | SEER2, EER2 and HSPF2, AHRI certificate |
| What the building needs | Roof openings and air inlets | Water supply, drain and power | An outside wall or a stand for each outdoor unit | Refrigerant piping between units, per the design manual | A roof that can carry the unit, ducts and grilles |
Sources: principles from chapter 41 of the ASHRAE Handbook (evaporative cooling); AHRI certificates and NEEP listings for the heat pumps. "Depending on the system": each VRF manufacturer publishes its own design limits.
To give real orders of magnitude, here are two heat pumps sold by AirGreen, of the same brand: a wall unit for a targeted zone (solution 3) and a packaged rooftop unit that feeds ducts (solution 5). They do not have the same capacity; they illustrate two ways of doing things, not a head-to-head.

Indoor LIV36HP230V1R32AH · outdoor LIV36HP230V1R32AO · AHRI 214779348
See the product page
GK-H05TC/NhA-D(U) · AHRI 215866831
See the product page| Certified value | GREE LIVO R32 36,000 | GREE Rooftop R32 5 tons |
|---|---|---|
| Cooling · 35 °C outdoors | ||
| Rated capacity at 35 °C | 33,600 BTU/h | 56,000 BTU/h |
| Capacity min. / rated / max. at 35 °C | 7,850 / 33,600 / 37,000 BTU/h | 18,600 / 56,000 / 57,200 BTU/h |
| Electrical power drawn at 35 °C | 2.80 kWthat is, 0.83 kW per 10,000 BTU/h (AirGreen calculation) | 5.00 kWthat is, 0.89 kW per 10,000 BTU/h (AirGreen calculation) |
| SEER2 | 21 | 18 |
| EER2 | 12 | 11.2 |
| Heating · both also heat in winter | ||
| HSPF2 region IV / region V | 8.5 / 7.5 | 8.3 / 6.5 |
| Capacity min. / rated / max. at 8.3 °C | 10,000 / 34,000 / 34,100 BTU/h | 13,700 / 57,000 / 58,200 BTU/h |
| Coldest certified point | ||
| Max. capacity at −15 °C (5 °F) | 24,600 BTU/h | 51,600 BTU/h |
| Coldest point published by NEEP | 21,000 BTU/h max. at −25 °C (−13 °F) | 28,500 BTU/h max. at −30 °C (−22 °F) |
| Listing | ||
| Certified configuration | Ductless wall unit, one zone | Packaged rooftop unit with ducts |
| Refrigerant | R-32, GWP 675 (IPCC AR4), class A2L | R-32, GWP 675 (IPCC AR4), class A2L |
| AHRI certificate · NEEP listing | 214779348 · 393213 | 215866831 · 505248 |
| ENERGY STAR, per NEEP | Yes, and cold climate | Yes, and cold climate |
All values: NEEP listings 393213 and 505248, consulted on November 17, 2026. Cooling is certified at 35 °C outdoors (condition A of the AHRI 210/240 standard). On NEEP, the GREE Rooftop R32 shows a higher rated capacity at −15 °C (51,000 BTU/h) than at −8.3 °C (34,000 BTU/h); the page shows the values as published. The two units are not the same size, so the table marks nothing "higher".
Not necessarily. If staff work mainly in packing, receiving or built-in offices, cooling those zones takes far less capacity than the whole volume under the roof. Wall heat pumps (one zone per unit) and VRF systems (several indoor units) lend themselves to that zoning; a rooftop heat pump serves the zones its ducts reach.
It cools the air, but humidifies it. Chapter 41 of the ASHRAE Handbook states that direct evaporative cooling is not suitable for indoor comfort when the outdoor wet-bulb temperature is above about 21 °C (70 °F), and that it remains satisfactory for relief cooling in industrial settings. Montréal-Trudeau's summer design wet-bulb temperature is 23.4 °C. Use the "July air" section to see the effect for the day's humidity.
They remove the heat that builds up under the roof and replace it with outdoor air. They cannot go below the outdoor air temperature: at 30 °C outside, the air coming in is at 30 °C. It is often a useful first step, not an equivalent of air conditioning.
A business pays for electricity under a business rate (Rate G for small power, others above), with a demand charge above 50 kW based on what the whole building draws. The cost of one unit therefore depends on what runs at the same time. We show the certified power drawn at 35 °C; your bill and your rate let you convert it to dollars.
Variable refrigerant flow: one outdoor unit feeds several indoor units by varying the amount of refrigerant sent to each. Piping lengths, the number of indoor units and the connected capacity are set by each manufacturer's design manual. Depending on size, performance is certified in SEER2 and HSPF2 or in IEER and COP.
Yes, they are heat pumps. Their certified heating points are in the table: 24,600 BTU/h max. at −15 °C for the GREE LIVO R32 36,000 and 51,600 BTU/h max. for the GREE Rooftop R32 5 tons, according to NEEP. Exhaust ventilation and evaporative cooling do not heat.
Programs change and depend on the building and the unit; we promise none and give no amount. Hydro-Québec's LogisVert program is aimed at homes; Hydro-Québec presents its business offers on its website.
The two heat pumps used as examples are on AirGreen's website. For a commercial building, call or write to us with your plans, the floor area and how the zones are used.
Data verified on November 17, 2026. Certified values come from the NEEP listings cited; climate conditions from Natural Resources Canada; the principles of evaporative cooling from ASHRAE. The calculations in the "July air" section are AirGreen estimates with their method shown. This guide presents facts; it does not rank the solutions and does not replace a study of the building.
GREE is a trademark of its owner. The mark and images are used to identify the products only. AirGreen is a dealer; this page is not produced, sponsored or approved by the manufacturer. Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong to you? Write to us.
This article was published on May 18, 2025 and rewritten on November 17, 2026 using AirGreen's comparison method.
An AirGreen advisor assesses your building on site and gives you a detailed quote.
Commercial requests: sales@airgreen.ca