Head to head · Central heat pumps

FUJITSU AIRSTAGE CENTAURI XLTH or GREE FLEXX ULTRA, 4 tons: thirty Montréal winters against both certificates

12 min
Head to head · Central heat pump · 4 tons

FUJITSU AIRSTAGE CENTAURI XLTH and GREE FLEXX ULTRA: two 48,000 BTU/h central systems against thirty Montréal winters

The previous version of this article promised to say which of the two brands was “ideal for Montréal’s climate”. Montréal’s climate, though, can be measured. We set the coldest temperature of each year at Montréal-Trudeau airport, from 1994 to 2023, next to what the two certificates publish at those temperatures. Two 4-ton R-32 central heat pumps sold by AirGreen; neither is ranked ahead of the other, and every figure carries its source.

Rated heating capacity at 8.3 °C 51,000 and 48,000 BTU/h Refrigerant R-32 for both Coldest certified point −26.1 °C and −30 °C ENERGY STAR, cold climate: yes for both
FUJITSU AIRSTAGE CENTAURI XLTH outdoor units, AirGreen product card
FUJITSU AIRSTAGE · CENTAURI XLTH

CENTAURI XLTH R-32 · 4 tons

AOUH48KUAH1 + AMUH48KUAS · AHRI 217895718

Heating stated down to −26 °C

View the product page
GREE FLEXX ULTRA R32 outdoor units, AirGreen product card
GREE · FLEXX ULTRA

FLEXX ULTRA R-32 · 4 tons

FXU48HP230V1R32AO + FXU48HP230V1R32AH · AHRI 215213331

Heating stated down to −30 °C

View the product page

airgreen.ca product cards, for identification: they show the line, not just the 4-ton model, which the Installation section draws to scale.

Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 48,000 BTU/h house in Montréal, at Hydro-Québec’s Rate D, taxes included, calculated with the HSPF2 region V and SEER2 seasonal ratings of each AHRI certificate. With HSPF2 region V ratings of 8.4 and 7.8, the winter gap comes almost entirely from that number; in summer, both certificates show the same SEER2, 19. Electric baseboards serve as the reference, calculated the same way as on our other comparisons.

How this amount is calculated
  1. Heat needed over the winter. A house whose heat loss reaches 48,000 BTU/h (0 kW) at −23.1 °C, Montréal’s design temperature: 0 kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = 0 kWh of heat for heating 24 hours a day, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours per day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: a simplification that ignores the recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the backup heat used when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity per kWh of heat.
  3. Electricity for cooling. 48,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s cooling calculator, with the SEER2 seasonal rating from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day: a maximum, since a variable-speed unit slows down once the room is at temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ above; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.

AirGreen method v1.1, November 9, 2026. An estimate is for comparing equipment under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.

Thirty winters at Montréal-Trudeau

The coldest night of each year, 1994 to 2023, against both certificates

Each line is a year; its dot marks the lowest temperature recorded that year at Montréal-Trudeau airport. Three lines cross the chart: Montréal’s design temperature, and each heat pump’s last certified point. Pick a year to see what each certificate publishes at its coldest temperature.

Thirty annual lows

An annual low often lasts a few hours, at night. It doesn’t describe the whole winter: the heating season is measured with degree-days and HSPF2, used in the Cost section. Temperatures are published rounded to the degree.

2023
−23.1 °C, Montréal design temperature (NRCan)−26.1 °C, last FUJITSU AIRSTAGE certified point−30 °C, last GREE certified point

Annual lows: Current Results, “Montreal – Lowest Temperature for Each Year”, compiled from Environment and Climate Change Canada historical climate data (Montréal-Trudeau station since 1984), reviewed November 17, 2026. System values: NEEP listings 306745 and 392094. Nothing is calculated between two published temperatures.

Deep cold

Colder than −15 °C: where each certificate stops

At −15 °C (5 °F), both certificates publish a maximum capacity at the same temperature: 51,000 BTU/h for the FUJITSU AIRSTAGE and 48,000 for the GREE. The FUJITSU AIRSTAGE’s last certified point is at −26.1 °C (−15 °F), with the same maximum capacity, 51,000 BTU/h; the GREE’s is at −30 °C (−22 °F), with 26,200 BTU/h. In between, GREE adds its own table, shown as diamonds on the chart: maximum output every 5 °F, outside the AHRI protocol.

The diamonds come from GREE_FLEXX_ULTRA_EXTENDED RATINGS_08272024, FXU48 column, 70 °F return air, which GREE itself describes as values outside AHRI test conditions. At −15 °C it shows 45,000 BTU/h, the certificate 48,000; at −30 °C, 26,200, the same value as the certificate. In its submittal 48KUAH1M, FUJITSU AIRSTAGE writes that heating capacity exceeds 100% at 5 °F and 75% at −15 °F, without stating what those percentages are based on: this page sticks to the certified values.

Spec sheet

Both spec sheets, row by row

FeatureFUJITSU AIRSTAGE CENTAURI XLTHGREE FLEXX ULTRA
Certificate
Certificate combinationAOUH48KUAH1 + AMUH48KUASFXU48HP230V1R32AO + FXU48HP230V1R32AH
AHRI certificate · NEEP record217895718 · 306745215213331 · 392094
SEER21919
EER211.211.7
HSPF2 region IV10.210
HSPF2 region V8.47.8
ENERGY STAR, cold climateYes And “Most Efficient”; ENERGY STAR database, certified April 27, 2026Yes ENERGY STAR database, certified September 16, 2026
Heating (min. / rated / max., NEEP)
Heating capacity at 8.3 °C (47 °F)16,000 / 51,000 / 55,000 BTU/h15,800 / 48,000 / 48,400 BTU/h
Heating capacity at −8.3 °C (17 °F)10,700 / 34,000 / 52,100 BTU/h9,800 / 39,500 / 41,500 BTU/h
Heating capacity at −15 °C (5 °F)8,600 / 51,000 / 51,000 BTU/h18,600 / 48,000 / 48,000 BTU/h
COP at −15 °C (min. / rated / max.)3.5 / 1.96 / 1.962 / 2 / 2
Stated heating range−26 to 24 °C −15 to 75 °F; no low-temperature shutoff, capacity not tested below −15 °F (submittal 48KUAH1M)−30 to 24 °C −22 to 75 °F per the GREE brochure, FXU48 column
Cooling
Cooling capacity at 35 °C (min. / rated / max.)15,400 / 45,500 / 50,000 BTU/h13,600 / 48,000 / 48,000 BTU/h
Stated cooling range−21 to 50 °C −5 to 122 °F−15 to 54 °C 5 to 129 °F
Dehumidification4.70 L/h 9.9 pints per hour, submittal 48KUAH1MNot published by the manufacturer
The equipment
CompressorInverter Submittal 48KUAH1MG20 twin-cylinder inverter “2-Stage Inverter”, GREE brochure
Indoor fan, airflowPublished value: 1,600 CFM AMUH48KUAS indoor unit, submittal 48KUAH1MPublished value: 1,200 CFM GREE brochure
Base pan heaterYes Built in, submittal 48KUAH1MNot published by the manufacturer
Electric backup heatOptional kits Submittal 48KUAH1M6, 9 or 12 kW optional GREE brochure
Installation
Outdoor unit, W × D × H and weight38 3/16 × 14 9/16 × 55 13/16 in., 225 lb35 7/16 × 13 3/8 × 49 5/8 in., 241.4 lb
Indoor unit, W × D × H and weight21 × 21 × 48 in., 137 lb24 13/16 × 21 1/4 × 52 in., 199.5 lb
Liquid – gas diameters3/8 – 5/8 in.3/8 – 3/4 in.
Line set length17 to 246 ft10 to 98 ft
Pre-charged length98 ft25 ft
Maximum height difference98 ft49 ft
RefrigerantR-32, 8 lb 6 oz, A2L class, GWP 675R-32, 162.3 oz, A2L class, GWP 675
Electrical protectionMax. breaker 45 A MCA 37.5 AMOCP 45 A MCA 39.9 A

Capacities, COPs and seasonal ratings come from NEEP listings 306745 and 392094 (November 17, 2026). Everything else comes from two documents: FUJITSU AIRSTAGE submittal 48KUAH1M, version 20260123A, and the GREE FLEXX ULTRA brochure, FXU48 column.

Sound

Noise, as each manufacturer publishes it

Outdoor unit

FUJITSU AIRSTAGE publishes one value in cooling and one in heating, measured in an anechoic chamber; GREE, a single value.

Indoor unit

FUJITSU AIRSTAGE publishes one value per fan speed; GREE, a single one.

dB

How to read these numbers. dB(A) measures a noise level; the lower the number, the quieter. Each dot is a value published by the manufacturer. A modulating 4-ton unit spends most of the year below its maximum output.

Why this is not a ranking. The two manufacturers don’t describe their measurements the same way (different method, not comparable), and the noise you hear also depends on where the unit sits and the walls around it.

Measurements taken by each manufacturer with its own method: read them separately, not as a ranking.

Installation

Two tall cabinets, two very different line set limits

At 4 tons, both outdoor units are tall: 55 13/16 in. for the FUJITSU AIRSTAGE, 49 5/8 in. for the GREE. The sharpest difference is elsewhere: FUJITSU AIRSTAGE allows up to 246 ft of line set, 98 ft of it precharged, and GREE up to 98 ft for this model. Both outlines are drawn at the same scale, from each manufacturer’s dimensions.

FUJITSU AIRSTAGE · AOUH48KUAH1

GREE · FXU48HP230V1R32AO

Top view, against the wall

Thick line: the wall. The free space required around each unit is listed in its installation manual and is checked on site.

25 ft

FUJITSU AIRSTAGE: 17 to 246 ft, 98 ft precharged, then 0.43 oz per ft (submittal 48KUAH1M). GREE: 10 to 98 ft, 25 ft precharged, then 0.215 oz per ft (brochure, FXU48 column). The actual length is measured on site.

Questions

Questions about these two 4-ton systems and Montréal’s cold

The previous article mentioned the FUJITSU AIRSTAGE KZAH and the GREE Ultra Heat. Where are they?

FUJITSU AIRSTAGE’s KZAH series refers to wall-mounted heat pumps; this page compares central heat pumps, so it takes the CENTAURI XLTH. “Ultra Heat” is a term from the GREE FLEXX ULTRA brochure, the central heat pump compared here. The case studies from Villeray and elsewhere, the prices and the grant amounts were removed: they couldn’t be verified.

Why annual lows rather than an average?

Because that is the question people ask about an operating limit: does Montréal go colder, and how often? A year’s low often lasts only a few hours. The cost of a whole season is calculated with degree-days and HSPF2 region V, as in the Cost section.

Does the FUJITSU AIRSTAGE really keep 51,000 BTU/h at −26 °C?

That is the maximum capacity on its NEEP listing at −15 °F (−26.1 °C), with a COP of 2.31; it is the same as at −15 °C. Below that, FUJITSU AIRSTAGE had no point certified, and its submittal states that capacity is not tested below −15 °F.

And below −30 °C?

Neither has a published value below −30 °C. The only annual low colder than that in these thirty years is 1994’s, −32 °C on January 27. Like any central heat pump, each one connects to backup heat, whose size is chosen during the assessment.

Are the diamonds on the Deep cold chart certified values?

No. They reproduce a table published by GREE, maximum output every 5 °F with 70 °F return air, outside the AHRI protocol. At −26.1 °C, that table gives 32,675 BTU/h for the GREE; that number doesn’t compare with the FUJITSU AIRSTAGE’s certified 51,000 BTU/h at the same temperature, since the two aren’t measured the same way.

In cooling, the FUJITSU AIRSTAGE is certified at 45,500 BTU/h. Is it still a 4-ton system?

It is sold as a 4-ton system, and its AHRI certificate gives 45,500 BTU/h rated capacity at 35 °C, with a 50,000 maximum; the GREE is certified at 48,000. To keep the cost comparable, the Cost section runs the calculation for one and the same 48,000 BTU/h house.

Are these heat pumps eligible for LogisVert?

This page doesn’t say so. The criteria and amounts of Hydro-Québec’s LogisVert program change; eligibility is checked in the official list, with the system’s AHRI number, at the time you apply.

Both are on the AirGreen site.

The free assessment visit calculates your house’s heat loss at −23.1 °C and sizes the backup heat; the written quote follows.

(514) 316-2973Request a quote
Sources

Documents reviewed

NEEP, listing 306745 (FUJITSU AIRSTAGE, AOUH48KUAH1)AHRI 217895718, AIRSTAGE H series · reviewed November 17, 2026
NEEP, listing 392094 (GREE, FXU48HP230V1R32AO)AHRI 215213331, FLEXX High-efficiency series · reviewed November 17, 2026
ENERGY STAR, heat pump databaseCertificates 217895718 and 215213331: cold climate, yes · reviewed November 17, 2026
FUJITSU AIRSTAGE, submittal 48KUAH1MVersion 20260123A · ranges, sound, dimensions, weight, piping, electrical, base pan heater, dehumidification
GREE, FLEXX ULTRA R-32 brochureGREE_FLEXX_ULTRA_R32_032725 · FXU48 column: specifications, ranges, sound, dimensions, piping
GREE, FLEXX ULTRA extended ratingsGREE_FLEXX_ULTRA_EXTENDED RATINGS_08272024 · FXU48, heating, 70 °F return air, maximum output outside AHRI conditions
Current Results, “Montreal – Lowest Temperature for Each Year”Compiled from Environment and Climate Change Canada historical climate data; lows 1994 to 2023 · reviewed November 17, 2026
IPCC, Fourth Assessment Report (AR4)100-year global warming potential: R-32 675
Hydro-Québec, Electricity RatesApril 1, 2026, Rate D, sec. 2.5 · reviewed November 17, 2026
NRCan, HOT2000 climate mapMontréal Intl: 4,167 degree-days (18 °C base), design temperature −23.1 °C
You made it to the end.Share it with someone it could help.
Keep reading

In the same blog

AirGreen Climatisation & Chauffage

From reading to your home.

An AirGreen advisor assesses your situation on site, free of charge, and gives you a quote within 24 hours.

  • RBQ licence 5645-9605-01Subclasses 15.8, 15.10 and 16
  • Free on-site estimateAn advisor assesses your needs
  • Quote within 24 hoursClear and detailed

Leave a comment