Installation of a GREE FreeMatch R32 2-head heat pump in Saint-Charles-sur-Richelieu (La Vallée-du-Richelieu RCM)
GREE FreeMatch R32 2-head wall-mounted heat pump, 36,000 BTU/h, installed in Saint-Charles-sur-Richelieu—the subsidy that prohibits increasing the rent, and the electrical reason why a single unit cannot serve two apartments in a multiplex.
- City
- Region
- Equipment
- Brand
- Challenges
- Published
The job on one screen

The article, chapter by chapter
The program subsidizes the owner and prohibits the owner from increasing the rent as a result
On October 23 and 24, 1837, five to six thousand people, according to the sources, gathered in Saint-Charles-sur-Richelieu for the Assembly of the Six Counties—Richelieu, Rouville, Saint-Hyacinthe, Chambly, Verchères, and L'Acadie, the latter admitted that same day. Wolfred Nelson presided; Louis-Joseph Papineau, Denis-Benjamin Viger, Édouard-Étienne Rodier, and Thomas Storrow Brown spoke there. A column topped with a Phrygian cap was erected, bearing the inscription “To Papineau, his grateful compatriots, 1837.”
A village in the Richelieu Valley where people gathered to discuss who decides what. It is a somewhat easy transition, and we accept it, because the installation we carried out there raises exactly that question in a much more prosaic form: when a heat pump is installed in a rental dwelling, who decides, who pays, who maintains it, and who benefits?
This is a subject on which a great deal of outdated information circulates. We will therefore be precise about our sources and explicit about what we will not say.
What was installed
| Item | Data |
|---|---|
| Outdoor unit | GREE FreeMatch R32 GWHD(42)ND6MO |
| Rated capacity | 12,310 W — 42,000 BTU/h in cooling · 44,300 BTU/h in heating |
| Heads | 18,000 + 18,000 = 36,000 BTU/h, or 86% of rated capacity in cooling, 81% in heating |
| Modulation range | 2,600 to 13,000 W in cooling (8,870 to 44,300 BTU/h) · 2,600 to 16,000 W in heating (8,870 to 54,590) |
| Ratings | SEER2 21 · HSPF2 10 · EER2 12 · EER 3.81 · COP 3.90 |
| AHRI reference | 214931590 |
| Heating range | −30 °C to 24 °C |
| Factory charge | 2,700 g of R32 |
| Piping | 14 m + 19 m = 33 m developed length, well below the 50 m factory charge → no R32 added |
| Electrical | MCA 30 A · MOCP 45 A |
| Cabinet | 1,020 × 826 × 427 mm, 79 kg, 3,413 cfm, 63 dB(A) |
Values taken from the specification sheet X610068B from the manufacturer, read directly.
Why the 42,000 rather than the 36,000, and the argument has nothing to do with piping length
Two 18,000 BTU/h heads would fit on the lower chassis. Here is the reason for the choice, and it can be read directly in the manufacturer's table:
The modulation minimum for the 36,000 and the 42,000 is identical—2,600 W, or 8,870 BTU/h. Exactly the same figure for both models, in both cooling and heating.
In other words: moving up one capacity level costs nothing at the bottom of the range. The low-load behavior—the factor that determines comfort in May and September, as well as cycle frequency—is the same for both units. What you gain at the top end is a higher maximum capacity (54,590 BTU/h in heating versus 51,180), a 50 m pre-charge instead of 40, a maximum total length of 100 m instead of 80, and up to five indoor units instead of four.
This is reasoning we had never published before, and it deserves to be known: between two neighboring capacities, the question is not only “is it too large?” but “does the minimum modulation level change?” Here, it does not.
The two heads operating alone are located approximately 103% above this minimum, and the total of 36,000 remains well below the adjusted maximum. One point of transparency that we make systematically: the 18 + 18 configuration has already been used elsewhere in our series for other outdoor units; what is new is combining it with this capacity.
What the program actually says—and prohibits
Let’s get to the heart of the matter. The facts below are taken directly from the Hydro-Québec LogisVert program participation guides. We cite them as program conditions, which is what they are, not as legal rules.
1. A tenant alone cannot receive assistance for a heat pump
Under the general residential guide, a tenant acting on their own behalf is eligible for only two appliances: an induction range and a heat pump dryer. A heat pump is not included.
The consequence is significant, and it surprises many people: in a rented dwelling, the heat pump application is the owner’s responsibility. A tenant who wants to have a unit installed cannot submit the application alone.
2. The multi-unit housing incentive exists only when the tenant pays for their electricity
The residential guide reserves the multi-unit housing incentive for owners of an eligible dwelling “where each tenant is responsible for their electricity bill”, subject to three cumulative conditions: the building must have been built in 1995 or earlier, have a main electric heating system, and be equipped with one electric meter per dwelling.
Take a second to look at the diagram. The increased assistance does not apply where heating is included in the rent. This is not an oversight; it is a decision. Where the tenant pays for electricity, a heat pump reduces their bill. Where heating is included, the savings would go to the landlord, and the program stops providing the increase.
3. The prohibition—and this is the line that almost no one cites
In the guide intended for tenants and landlord-renters, the list of the landlord’s commitments ends with this one, word for word:
“Do not use the installation of a unit as justification for increasing the rent.”
And in the general residential guide, the rule is worded differently but points in the same direction: the landlord must comply with the rent-setting rules of the Administrative Housing Tribunal and cannot include, when calculating a rent increase, equipment or improvements that have been subsidized under the program.
The portion paid for by the program cannot be recovered through the rent. It is clear, it is written, and it changes the calculation for a landlord who thought they could do both.
4. The maintenance responsibilities are also set out in writing
The same guide divides the tasks unambiguously. The landlord agrees to carry out periodic maintenance and pay the costs, to coordinate access to the dwelling with the tenant, to inform the tenant of visits, to not prohibit the use of the unit or block access to it, and to acknowledge that the installed unit belongs to them. The tenant, for their part, is responsible for regularly cleaning the filter.
This last point deserves emphasis: it is exactly the division of responsibilities we recommend anyway, and seeing it written in a program document avoids many conversations. We add just one operational detail: the filter demonstration is given to the tenant present on the day the unit is commissioned, and the sheet stays in the dwelling—not in the landlord’s binder. Tenants change; the unit stays.
What we will not say, and why
Many online texts will tell you that a heat pump constitutes a “major improvement” within the meaning of the Civil Code, along with the notices and deadlines that this entails.
We will not make that claim. The Civil Code does not define the expression, and the qualification is decided on a case-by-case basis by the Administrative Housing Tribunal. A heat pump that replaces the heating system is not in the same situation as a unit added to air-condition a room. We cite documents; we do not make decisions, and that question should be addressed to the TAL or a lawyer, not an HVAC contractor.
Two useful reference points nonetheless, and they are verifiable:
- The regulation on rent-setting criteria has changed its number and its content. The former reference R-8.1, r. 2 was repealed in 2020; the text now appears under T-15.01, r. 2. It was also substantially rewritten effective January 1, 2026, with the new method applying to modification notices given on or after that date. Any web page that cites the old number has not been revised in at least five years—a simple and remarkably effective freshness test.
- Access for maintenance is not optional. The tenant cannot refuse access for work, provided notice is given and the work takes place within a time period set by law. We will not go into the details here—it is something to verify with the TAL—but remember that an annual maintenance contract in a rented unit is enforceable, and it is better to include it in the lease than discuss it in July.
Only one thing prevents a multi-split from serving two units, and it is not capacity
This is the question we receive from almost every duplex owner, and the answer always surprises them:
“My unit supports five indoor units. Can I put two upstairs and two downstairs, and buy only one outdoor unit?”
In terms of capacity, nothing prevents it. Electrically, everything does.
The indoor units are not powered by the room
It is stated plainly in the manufacturer's documentation, and it is probably the least understood feature of this type of system: the indoor units are powered by the outdoor unit.
A wall-mounted indoor unit does not have its own circuit. It is not connected to the panel of the unit where it is located. It receives its power and signals through an interconnection cable that runs back to the outdoor unit, which is supplied by a single circuit—here, MCA 30 A, MOCP 45 A for the entire system, including both indoor units.
The consequence, in one sentence
All the energy consumed by all the indoor units passes through a single meter: the one supplying the outdoor unit.
In a duplex with separate meters, a multi-split serving two units therefore makes a single occupant pay for the heating and air conditioning of two. This is not a billing detail: it is a design problem that cannot be fixed afterward, because the only possible solution is to separate the systems, which means buying another outdoor unit.
And this directly conflicts with what we have just read: the program’s multi-unit-building incentive requires one electrical meter per dwelling and a tenant responsible for their own bill. A system shared between two dwellings cannot meet this condition, regardless of its efficiency.
The rule we apply
One system per dwelling. One outdoor unit, one circuit, one meter, and one occupant paying for what they consume. The additional ports on a large chassis are for adding zones within the same dwelling—not for crossing the separation between housing units.
Two corollaries we systematically verify:
- The interconnection cable and the pair of pipes belonging to the same head must terminate at the same numbered port. Crossing them causes the wrong expansion valve to be controlled, and the symptoms look like a defective unit: one room never reaches its setpoint while another exceeds it, one head freezes, or one head stops without displaying an error code. Our Hinchinbrooke page published the verification method; this is the fault we most often correct on other contractors’ multi-zone installations.
- Before drilling, we know which panel supplies the power—and, in a rental building, which meter that panel is connected to.
The difference from our other pages about the valley
Our Beloeil page raised an occupancy question: who is in the room, and who can speak on their behalf. The Mont-Saint-Hilaire page raised a surface question: what the unit is installed on, and what that surface does with water. This one raises a meter question: who pays for what the unit consumes, and is that actually the person benefiting from it?
Three neighboring municipalities, three questions that are not alike. That is, ultimately, why we write these pages one by one instead of using a template.
At AirGreen, we install, maintain, and document HVAC systems in Saint-Charles-sur-Richelieu, Saint-Marc-sur-Richelieu, Beloeil, Mont-Saint-Hilaire, Otterburn Park, and throughout the Richelieu Valley, as well as in Montreal, Laval, Longueuil, on the North Shore, and on the South Shore. If your project involves a rental unit or a multi-unit building, mention it during the first visit: the meter issue is resolved on a plan, never on a wall that has already been drilled.
The job tools
Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.
Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.
How the job unfolds
The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.
We look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
Model, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
Floors and furniture protected, wall plate position marked level, wall opening located.
A single opening, with the slope the drain needs to flow outside.
Set on a stand raised above the snow, with the clearances the manufacturer requires.
Connected, insulated and protected. The opening is then sealed against water, cold air and insects.
A dedicated circuit and an accessible disconnect near the outdoor unit.
Leak test, vacuum, then start-up and a check of heating and cooling.
Remote, modes, filters: we show you the essentials before we leave.
- The on-site estimateWe look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
- The quoteModel, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
- Getting readyFloors and furniture protected, wall plate position marked level, wall opening located.
- The wall openingA single opening, with the slope the drain needs to flow outside.
- The outdoor unitSet on a stand raised above the snow, with the clearances the manufacturer requires.
- Lines, cable and drainConnected, insulated and protected. The opening is then sealed against water, cold air and insects.
- The electrical workA dedicated circuit and an accessible disconnect near the outdoor unit.
- Tests and start-upLeak test, vacuum, then start-up and a check of heating and cooling.
- The walkthroughRemote, modes, filters: we show you the essentials before we leave.
What we check on a job like this one
Each number is a point we check on site. Switch between summer and winter to watch air and heat move.
In summer, the outdoor unit rejects the house's heat outside.
Generic illustration of this type of installation, not a survey of this job site. Tap a number.
Mounted level on a wall plate, high enough for the air to reach the whole room, with enough space around it to slide the filters out easily.
The refrigerant lines, the communication cable and the drain go through the wall in a single opening, sealed against water, cold air and insects.
Two insulated copper pipes connect the two units. Outside, a line cover can protect them from sun, knocks and weather.
A shut-off switch near the outdoor unit isolates it safely for service. It must stay accessible at all times.
The compressor and the fan. In heating mode it captures heat from the outdoor air, even in winter, and moves it inside.
On the ground or on the wall, it keeps the unit above accumulated snow. The unit stays clear and defrost water can drain away.
The fan needs to blow freely. Storage, a fence or a wall too close, and efficiency drops while noise goes up.
Is your home ready?
Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.
Good habits, once the unit is in place
Six simple habits that keep the unit going. Your list stays on this device.
What to do, season by season
Three habits per season for this unit. They take a few minutes and prevent many calls.
- Clean the indoor unit's filters.
- Clear leaves and debris left on the outdoor unit by winter.
- Test cooling before the first hot days.
- Clean the filters more often when the unit runs a lot.
- Keep plants away from the outdoor unit.
- Check that no water drips from the indoor unit.
- Rake the leaves around the outdoor unit.
- Test heating before the first cold days.
- Book periodic maintenance before winter.
- Keep snow away from the stand and the front of the unit.
- Let the unit defrost: it is normal.
- Never hit the ice on the fins; call us if the unit stays iced up.
The right pages, at the right time
Four statements: true or false?
It all comes down to details you have just seen.
1. In heating mode, the outdoor unit can produce water.
During defrost cycles. That water must drain away without forming ice.
2. You pick the capacity with a simple square-footage rule.
Windows, insulation, orientation and how the room is used all count. Capacity is chosen on site.
3. A multi-zone connects several indoor heads to a single condenser.
One head per room, all on the same condenser. Each room keeps its own temperature.
4. The disconnect can sit behind the patio furniture.
It must stay accessible: it is what shuts the unit off for service.
0 / 4 right answers
What people ask us about this kind of work
Does a wall-mounted heat pump heat in winter?
Wall-mounted or multi-zone: how do I choose?
Where does the outdoor unit go?
Are there grants?
Do I need a permit?
How cold can it heat?
How much can I save?
How is the LogisVert assistance calculated?
Is it noisy?
The outdoor unit is covered in ice: is that normal?
Does AirGreen hold the required licences?
Is the estimate free?
No question matches. Write to us: we answer.
More jobs to see, near you
By town, by equipment or by region: browse more than 4,700 published projects.
Each dot: a town where AirGreen has published projects. The glowing dot: this job.
An on-site estimate, the right capacity, the right equipment.
The on-site estimate is free and the quote follows within 24 hours.
Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).
