Commercial heat pump or natural gas: what each one delivers in the cold
Side by side
Heat pump or natural gas: what each one delivers when the cold sets in
A gas appliance delivers the same output at 8 °C as at −20 °C. A heat pump delivers less as the outdoor air gets colder, but it draws several kWh of heat from each kWh of electricity. Here are the published figures, point by point, for a 5-ton central heat pump we sell, and what they change for the backup heat of a commercial space.
What the heat pump delivers at each published temperature
Pick a temperature. The teal bar shows the heat pump’s output; the orange bar, a gas appliance’s, which does not depend on the outdoor air.
How to read these figures
- Output: the NEEP-certified maximum capacity at each temperature, as a % of the 8.3 °C value. The yellow line marks the rated capacity, where published.
- Squares: each square is 0.25 kWh of heat delivered for 1 kWh of energy bought. For the heat pump it is the COP measured at that temperature; for gas it is the federal minimum AFUE, measured over a typical season. The two are not measured under the same conditions.
- Between two points: we estimate nothing between published temperatures. Only measured points are shown.
How much heat is missing, and at what temperature?
Enter your space’s heat need in deep cold and the number of units. The chart compares, at each published temperature, the heat required with what the heat pumps can deliver. The gap is the backup’s job.
How this is calculated
- Need at each temperature: it falls in a straight line between −20 °C and 18 °C, where the space no longer needs heat. This is an AirGreen simplification for the illustration; the real calculation accounts for insulation, fresh air and internal gains.
- Capacity: the NEEP-certified maximum capacity of the BOSCH IDS Premium Connected 5-ton (record 423131, AHRI certificate 214771733), at 8.3, −8.3, −15 and −20 °C only.
- Below −20 °C: the BOSCH installation manual says the unit stops and calls on the electric backup. The whole need then goes to the backup.
AirGreen method, November 17, 2026. This is not a load calculation: it does not replace the site visit.
Where the winter months fall against the measured points
The 1991–2020 normals for the Montréal–Trudeau station, on the same scale as the temperatures published by NEEP. In January, the mean (−9.2 °C) falls between two measured points; we do not invent a value between them.
| November, mean | 2.3 °C |
| December, mean | −5.0 °C |
| January, mean | −9.2 °C |
| January, mean daily minimum | −13.5 °C |
| February, mean | −8.0 °C |
| March, mean | −2.0 °C |
A monthly mean hides colder nights. The building’s design temperature, used to size the backup, is set by the designer under the Building Code.
Six questions that point the way before any quote
The choice depends on the building before it depends on the appliance. Here is what we look at on site.
What is the heat need in deep cold?
Everything starts there: a heat-loss calculation sets the output needed at the building’s design temperature.
Are there ducts already?
A central heat pump and a gas furnace both use a duct network. Without ducts, other systems come into play.
Does the space have a gas service?
An existing gas furnace can stay in place as backup for a heat pump added to the same ducts.
Does the electrical panel have capacity?
Heat pumps and electric backup add to the power drawn; on a business rate, power is billed too.
Do you also want cooling?
The heat pump cools in summer with the same unit. A gas appliance does not cool: it needs a coil and an outdoor unit.
What backup below −20 °C?
The BOSCH manual calls for electric backup when the unit stops. An existing gas furnace can also play that role.
Heat pump and natural gas, line by line
No line is highlighted: each space weighs these lines its own way.
| Line | Central heat pumpBOSCH IDS Premium Connected 5-ton | Natural gas applianceforced-air furnace |
|---|---|---|
| How the heat is produced | ||
| Principle | Moves heat from the outdoor air indoors | Burns natural gas in a burner |
| Energy bought | Electricity | Natural gas, plus electricity for the blower |
| Heat per kWh bought (COP or AFUE) | Rated COP of 3.8 at 8.3 °C, 2.5 at −8.3 °C, 2.0 at −15 °C; 1.59 at maximum capacity at −20 °CBOSCH IDS 5-ton, NEEP | AFUE of at least 95%federal minimum, single-phase furnace up to 225,000 Btu/h |
| In deep cold | ||
| Output as it gets colder | Drops: maximum capacity of 58,000 BTU/h at 8.3 °C and 31,800 BTU/h at −20 °C | Constant: the rated output, whatever the outdoor temperature |
| Operating range | Coldest published point: −20 °C; stops below −20 °C per the manual | Does not depend on the outdoor temperature |
| Backup | Electric per BOSCH, or an existing gas furnace | Not required |
| Defrost | Defrost cycles of the outdoor unit | None |
| On site | ||
| Outdoor unit | Yes: clearances and height above the snow to plan | No, except the vent |
| Venting | None | Wall vent or chimney |
| Energy connection | Panel capacity and electricity rate | Connection to the gas network |
| What can be added | ||
| Cooling | The same unit, in reverse mode | Coil and outdoor unit to add |
| Who does the work | AirGreen | Licensed partner |
| Operation | ||
| Maintenance | Filters, coils, clearing around the outdoor unit | Filters, burner, heat exchanger, vent |
| Energy price | Hydro-Québec electricity rates | Énergir natural gas rates |
Sources: NEEP, record 423131 (AHRI 214771733), checked November 17, 2026; BOSCH installation manual BTC 762003301 D, p. 47; Energy Efficiency Regulations, 2016 (SOR/2016-311), s. 259.
What building managers ask us
Does a heat pump still heat at −20 °C?
The BOSCH IDS Premium Connected 5-ton is NEEP-certified at −20 °C with a maximum capacity of 31,800 BTU/h and a COP of 1.59 at that capacity. Its manual says it stops below −20 °C and calls on the electric backup.
Why does output drop as it gets colder?
The heat pump draws its heat from the outdoor air. The colder that air, the less heat there is to extract, and the harder the compressor works to raise it to the needed temperature.
What does COP mean?
The coefficient of performance is the heat delivered divided by the electricity used, at a given temperature. A COP of 2.5 means 2.5 kWh of heat for 1 kWh of electricity, under the test conditions.
Can the gas furnace stay as backup?
Yes, a central heat pump can be added to an existing furnace’s ducts, with the furnace taking over in deep cold. Work on gas or oil appliances, boilers and hydronic systems is entrusted to a licensed partner; AirGreen (RBQ licence 5645-9605-01) handles heat pumps, ventilation, refrigeration and electrical work.
Which one costs less to run?
It depends on the rates in force, the subscription and the COP at each temperature. Our guide on gas and electricity for businesses does that calculation with official rates; this page sticks to the heat delivered.
Who does the work?
Work on gas or oil appliances, boilers and hydronic systems is entrusted to a licensed partner; AirGreen (RBQ licence 5645-9605-01) handles heat pumps, ventilation, refrigeration and electrical work.
Is there financial assistance for businesses?
Hydro-Québec and Énergir each publish programs for their business customers. Their conditions and amounts change: check them on both utilities’ websites before deciding. We do not promise any amount.
We calculate your heat need before we talk about appliances.
Heat loss, ducts, panel, gas service: the estimate visit is free and the quote arrives within 24 hours.
Documents consulted
Data checked November 17, 2026. The capacities and COPs are those certified for a single model, the BOSCH IDS Premium Connected 5-ton, at the published temperatures; we estimate no value between those temperatures. The heat need by temperature is an AirGreen simplification for the illustration, not a load calculation. The AFUE cited is a regulatory minimum, not the efficiency of a specific appliance.
Trademarks and logos belong to their respective owners. This page is not produced, sponsored or approved by NEEP, BOSCH or the Government of Canada.
Does a figure look wrong? Write to us at sales@airgreen.ca.
From reading to your building.
An AirGreen advisor assesses your building on site and gives you a detailed quote.
Commercial requests: sales@airgreen.ca- RBQ licence 5645-9605-01Subclasses 15.8, 15.10 and 16
- $5M liability insuranceOn every job
- 15+ yearsFamily-owned, based in Montréal



