No question matches. Write to sales@airgreen.ca or call 514 316-2973: a technician will answer.
What indoor air quality services do you offer businesses?
Indoor air quality assessment, air purification solutions (purifiers, air cleaners, filtration, UV systems), ventilation system design, installation and maintenance, humidity control, and regular maintenance and checks.
What rules govern ventilation in a Québec business?
The Regulation respecting occupational health and safety (RSST): adequate ventilation (s. 101), minimum fresh-air changes from Schedule III (s. 103), annual inspection (s. 104). The employer must comply with these standards (s. 4).
How often does ventilation need to be inspected?
At least once a year: every mechanical ventilation system must be inspected and adjusted, and filters maintained or replaced as needed (RSST, s. 104). We provide a dated report.
What CO2 level should an office aim for?
Health Canada recommends a long-term exposure limit of 1,000 ppm, averaged over 24 hours. CO2 is mainly an indicator: a high reading points to a lack of fresh air.
What is the minimum humidity in winter?
At least 20% during business hours in an office building or commercial establishment built or opened after December 19, 1979 (s. 119), measured with a psychrometer or hygrometer (s. 120).
And the maximum humidity in summer?
For air-conditioned spaces, ASHRAE 62.1 limits the indoor dew point to 15 °C. Above that, condensation and mould threaten ducts and ceilings.
How much fresh air does my space need?
ASHRAE 62.1 adds a per-person rate and a per-area rate. Example: a 5,000 sq. ft office with 25 people needs 425 CFM of outdoor air. Use the calculator for your own space.
Do ducts need to be cleaned every year?
No. According to the Québec government, duct cleaning isn’t governed by any regulated practice and is only needed when an inspection shows it is.
Does an air purifier replace ventilation?
No. Health Canada separates ventilating, which replaces indoor air with filtered outdoor air, from filtering. A purifier cleans the air in a room, it doesn’t bring in fresh air.
What should we do during a wildfire smoke episode?
Health Canada recommends MERV 13 or higher filters when the system can handle the pressure drop, and a system that can switch to recirculation.
Do you test for mould or asbestos?
That testing is done by an industrial hygienist or an accredited lab. A building constructed before February 15, 1990 must have been inspected for sprayed-on asbestos insulation (RSST, s. 69.3). We then fix the ventilation and humidity.
How much does an assessment cost?
The on-site estimate is free and the quote follows within 24 hours. You see the price of the work before we start.
Which sectors and cities do you serve?
Offices, stores, restaurants, salons, schools and daycares, warehouses, everywhere in Montréal, Laval, Longueuil, the North Shore and the South Shore.