Réparation d’une thermopompe centrale Goodman à Lachine
Reading time: 3'

Repair of a Goodman central heat pump in Lachine

Central system down before the warm season

As spring approached, the first warm weather in Lachine revealed a problem for one of our clients: their Goodman central heat pump refused to start. At AirGreen , we know that a breakdown of this type can quickly compromise the comfort of a home, especially when the HVAC system provides both heating and air conditioning. Our team responded quickly to diagnose and repair the system.

System Description

The client owns a Goodman central heat pump , installed about eight years ago in a typical house in the residential neighborhood of Lachine. This model, powered by R-410A refrigerant , is connected to an indoor electric furnace , ensuring year-round comfort. The outdoor unit, mounted on a raised galvanized steel base, is well protected from the elements, but exposed to dust and temperature variations typical of the Montreal climate.

Symptoms observed

The customer reported to us that:

  • The indoor fan was running, but the air blown out remained lukewarm.

  • The outdoor unit would no longer turn on, even when the requested temperature was much lower than the room temperature.

  • No compressor noise was audible, but the circuit breaker tripped after each start attempt.

This type of symptom indicated either a short circuit in the compressor or a faulty control board .

Diagnosis carried out by our HVAC team

Our certified technicians undertook a complete check of the electrical and refrigeration circuit :

  1. Voltage control at the input of the outdoor unit: compliant with 240 V.

  2. Start capacitor inspection : worn over 70%, which prevented the compressor from starting the cycle properly.

  3. High pressure switch check : no blockage detected.

  4. Compressor start current analysis : too high, confirming capacitor failure.

Repair and recommissioning

Once the diagnosis is confirmed, we have:

  • Replaced the faulty capacitor with a genuine Goodman part.

  • Cleaned the condenser coil using a biodegradable product to optimize heat exchange.

  • Checked the R-410A refrigerant level , which was found to be stable.

  • Tested the compressor and outdoor fan over several operating cycles.

Result: The system resumed normal and silent operation upon first restart. The air coming out of the interior grilles reached 13°C , proof that the heat pump was operating optimally.

Preventive advice given to the client

After the repair, we explained to the owner the importance of annual preventative maintenance . Our recommendations included:

  • Have the condenser coils cleaned every spring to prevent overheating.

  • Check circuit breakers regularly and make sure they do not trip unnecessarily.

  • Replace interior filters every three months to maintain efficient air circulation.

  • Schedule a complete system inspection in the fall before the heating season.

These simple actions can extend the lifespan of a central heat pump and reduce energy consumption by up to 15% per year.

AirGreen expertise: reliability and proximity

This intervention in Lachine demonstrates the added value of AirGreen's HVAC repair service . We combine rapid diagnostics , genuine parts , and local expertise to ensure lasting repairs. Our technicians are trained on all major brands, including Goodman, Lennox, Trane, Midea, Bosch, and Comfortmaker .

We work every week in the residential and commercial sectors of Montreal, Laval, Longueuil, the South Shore and the North Shore , always ensuring total transparency on costs and progress of the work.

Final result: restored comfort and optimized performance

After our visit, the client immediately noticed restored comfort throughout the house . The outdoor unit, cleaned and tested, is operating at full efficiency, and the electricity bill will be significantly more stable during the warm season.