The Greentek space at AirGreen
Sold and installed by AirGreen
Montréal, Laval, Longueuil, South Shore and North Shore.
Installation and replacement
Installing or replacing a Greentek air exchanger
A good model can still end badly: a missing drain, a core nobody can pull out, a fresh-air intake too close to the dryer vent. This page answers one question: will this Greentek model fit where it has to go, and what does the installation take?
To compare the families and pick a model, start with the Greentek page.
Greentek installation checker
Pick a model and describe the spot. The answers come from Greentek’s spec sheets, the HVI directory and the Construction Code; our estimator confirms everything on site.
SOLACE 1.5H
What the installation takes · See the page for the SOLACE 1.5H
- Layout
- Upright, top ports. A good spot for it.
- Ducts
- Your 6 in ducts connect directly.
- Drain
- Plan a drain: in winter an HRV produces condensate.
- Service space
- Keep 14 in clear in front to pull the core (Greentek sheet).
- Weight and size
- 52 lb · 27.88 × 13.38 × 23 in (W × D × H)
- Power
- 120 V, 3 ft cord with three-prong plug.
- Balancing
- Balancing range 90 to 210 cfm, with the STS 2.0 control (Greentek sheet). We measure both airflows at start-up.
- Efficiency vs airflow
- HVI directory, 0 °C, Nov 18, 2026: the harder it runs, the less it recovers and the more it draws.
- Fresh-air intake
- At least 1,800 mm from any exhaust that could contaminate it (Code, art. 9.32.3.13) and at least 460 mm above ground or snow, never in a garage, an attic or under a deck (Greentek).
01Where it goes, by family
With Greentek, the shape of the unit decides almost everything. The SOLACE stands upright with its ports on top: it lives in a basement, against a wall, or in a closet deep enough to pull the core out. The PREMIER lies flat and takes its ducts from the sides; only the small 0.7H keeps its ports on top. The PROFILE is about 10 in deep: Greentek designs it for a dropped ceiling or a small utility closet, which makes it the condo unit. The LCH series hangs from threaded rod or sits on a platform in a commercial space.
One rule covers them all: the unit goes in a heated space. Greentek does not recommend attics or crawlspaces, and its specifications keep the electronics between 0 and 50 °C.
02The fresh-air intake, the distance people forget
The Construction Code (article 9.32.3.13) requires at least 1,800 mm between an air intake and any exhaust that could contaminate it, and the same distance between a moist exhaust, such as a dryer or bathroom vent, and an intake or a vented soffit. The PREMIER 0.7H manual mentions 900 mm from a dryer vent: we apply the Code, which is stricter.
Greentek adds its own rules for the intake hood: at least 460 mm (18 in) above ground or snow, upstream of the exhaust, and never in a garage, an attic, a crawlspace or under a deck. On a back wall where snow piles up, we measure those 460 mm from the usual snowbank, not from the ground.
03The drain: who needs one
An HRV recovers heat without touching humidity: in winter the stale air cools in the core and condenses. It needs a drain. On the PREMIER 0.7H, Greentek provides a 1/2 in spout connected through a trap to a drain or a condensate pump. An ERV moves moisture as well: the SOLACE 1.0E is sold without a drain, and no PROFILE needs one. In a condo with no floor drain, that is often what decides it.
The LCH series does both: the LCH-H units have a full-length drain pan; for the LCH-E units Greentek does not require a drain but recommends one where it stays below −25 °C outside with indoor humidity over 40 % for 24 hours or more.
04Did you know? The setting costs efficiency
The HVI directory tests each unit at several airflows. The lesson is the same every time: the harder you run it, the less heat it recovers and the more power it draws.
| Model | Low airflow | High airflow |
|---|---|---|
| SOLACE 2.0H | 85 cfm: 80 % · 98 W | 195 cfm: 74 % · 192 W |
| SOLACE 2.5H-EC | 85 cfm: 82 % · 34 W | 233 cfm: 72 % · 246 W |
| PREMIER 3.0E-EC | 64 cfm: 77 % · 31 W | 248 cfm: 60 % · 200 W |
| PROFILE 1.2E-D-EC | 51 cfm: 77 % · 23 W | 125 cfm: 64 % · 62 W |
HVI directory, Section III, tests at 0 °C, current as of November 18, 2026.
That is why we balance the unit at the airflow the house needs, not at full speed.
05Replacing an existing unit
A replacement starts with what is already there: duct size, hood locations, the drain and the outlet. According to Greentek’s sheets, the SOLACE 1.5H, 1.5H-EC, 2.0H and 2.5H-EC have 6 in collars, the SOLACE 1.2H and 1.0E have 5 in collars, and the PREMIER 0.7H has 4 in collars. When your ducts do not match, we fit a reducer and check the airflow at start-up.
For a new house, the Code (article 9.36.3.9, in force since April 17, 2025) requires at least 55 % recovery at −25 °C below 6,000 heating degree-days and 60 % above; a project started before October 17, 2027 may still follow the old 54 % requirement. The texts we read do not say whether a simple replacement in an existing house falls under it: we tell you what applies to your project.
On grants: since October 1, 2026, Rénoclimat no longer funds air exchangers under its new stream; a file evaluated before that date keeps the old rules, $500 for a unit listed in the HVI directory, with the post-work evaluation by March 31, 2027. Hydro-Québec’s LogisVert program does not cover air exchangers.
06Start-up
An unbalanced unit puts the house under positive or negative pressure and ventilates poorly. Before we leave, we measure fresh and exhaust air and set both to the planned airflow. The PREMIER 0.7H manual describes the method: an airflow station and a manometer, on steel duct, at least 300 mm (12 in) from the unit or an elbow, with the furnace blower running and the unit on maximum. For the SOLACE, Greentek has the balancing done through the STS 2.0 control.
Then we show you the filters and how to pull the core: that is the upkeep you will do yourself.
07Installation questions
Can a Greentek air exchanger go in the attic?
No. Greentek requires a heated space and does not recommend attics or crawlspaces.
My condo has no drain near the unit: what are my options?
An ERV that needs no drain: no PROFILE needs one, and the SOLACE 1.0E is sold without a drain. With an HRV, you need a condensate pump or another location.
My ducts are 6 in and the unit has 5 in collars. Is that a problem?
No. We fit a reducer and measure the airflow at start-up. The checker at the top of the page gives each model’s collar size.
How far from the dryer vent must the fresh-air intake be?
At least 1,800 mm, under article 9.32.3.13 of the Construction Code.
How much space does the unit need in front?
Enough to pull the core out. According to Greentek’s sheets: 12 in for the SOLACE 1.2H and 1.0E, 14 in for the 1.5H and 1.5H-EC, 16 in for the 2.0H and 2.5H-EC, 10 in for the PREMIER 0.7H and 22 in for the PREMIER 3.0E-EC.
A free on-site assessment
We assess on site what each room needs, the location, the drain, the duct route and the power supply. Call us at 514 316-2973 or write to sales@airgreen.ca.
To choose the model, see all Greentek air exchangers.
Sources, consulted in November 2026
- Greentek spec sheets for the SOLACE 1.2H, 1.5H, 2.0H, 1.5H-EC, 2.5H-EC and 1.0E, the PREMIER 0.7H and 3.0E-EC, and the LCH series (January 2026 revision), greentek.ca
- PREMIER 0.7H installation manual, item 445792, revision of December 1, 2025, greentek.ca
- CSI specifications for the SOLACE, PREMIER, PROFILE and LCH series, series pages and PROFILE brochure E2198 (March 2025), greentek.ca
- HVI Certified Products Directory, Section III, current as of November 18, 2026, hvi.org
- Québec Construction Code, Chapter I (NBC 2020 as amended), articles 9.32.3.13 and 9.36.3.9; Order in Council 437-2025 (Gazette officielle, April 2, 2025); Order in Council 1351-2026
- Rénoclimat program guide in force on October 1, 2026, quebec.ca; LogisVert residential guide, version 1.10 (September 15, 2026), Hydro-Québec