Job sheet · Project

Installation of a LIFEBREATH RNC 155 air exchanger in Repentigny

A LIFEBREATH RNC 155 air exchanger in perfect condition, but the owners were no longer using it. The faulty component was not the unit—it was the wall control. The recirculation mode is explained, along with the humidity setting that should be adjusted in winter.

By AirGreen Climatisation & Chauffage Admin13 min read
City
Region
Equipment
Brand
Challenges
Published
–chapters, to open one by one
13 minto read the whole story
–type of installation
2026year published
At a glance

The job on one screen

The full story

The article, chapter by chapter

We brought the ventilation of a Repentigny home back to life by changing just one component: the wall control

On the hallway wall of this Repentigny home, the outline of the old control is still visible: a rectangle of whitewashed plaster and two abandoned screw holes. The old housing was wider, taller, and above all much more opaque. A humidity dial graduated from 20 to 80, a three-position switch, and no indication of what was actually happening.

The homeowners told us plainly: they never touched it. The dial had remained in the same position since they bought the house, eight years earlier.

Their air exchanger, a LIFEBREATH RNC 155, was nevertheless in perfect working order. Clean core, quiet motors, healthy ductwork. The system's only faulty component was the interface. We therefore replaced the wall control with a model featuring indicator lights, reprogrammed the modes, adjusted the humidity setpoint, and rebalanced the system.

The result, three weeks later: no more condensation on the basement windows, and the temperature difference between the basement and the main floor cut in half. Without touching the unit.


What the old control prevented

An older-generation wall control does only one thing: it starts the unit at one speed, with a fixed humidity threshold. It provides no information and offers no modes.

The installed control offers, on a single plate:

  • A continuous low-speed mode (LO) — the unit ventilates continuously at a low airflow rate.
  • Partial-cycle modes, identified by percentage, in which the unit ventilates for a fraction of each hour rather than continuously.
  • A 20/40 mode, alternating 20 minutes of ventilation and 40 minutes of recirculation.
  • A recirculation mode identified by its own indicator light.
  • Humidity-based control, accessible via the droplet-shaped button.
  • A settings menu beneath the gear button.
  • Green indicator lights that continuously show the active mode and current speed.

This last point is what changes everything in real-world use. A control that displays its status is a control the occupants understand—and therefore use. In the photo taken after commissioning, three indicator lights are on: continuous low speed, medium speed, and the 20/40 cycle active. One glance is all it takes.


Recirculation mode, finally explained

It is the least understood function of all the air exchangers sold in Quebec, and yet one of the most useful in January.

What it is

In recirculation mode, the appliance does not introduce outdoor air. It circulates the air already in the house: it draws air from certain areas and redistributes it to others through its own network of ducts.

In other words, it works like an air circulator for the entire house, with no energy penalty from reheating cold air.

When we use it

In very cold weather. When outdoor air drops below –20 °C, it contains almost no water vapor. Ventilating continuously dries out the house very quickly. Alternating ventilation and recirculation maintains sufficient air exchange while slowing the drying process. That is exactly the logic behind 20/40 mode: 20 minutes of fresh air, 40 minutes of indoor air circulation.

To even out temperatures between floors. In this house in Repentigny, the difference between the finished basement and the bedroom floor reached several degrees in winter. By moving the warm air accumulated upstairs downward, recirculation reduces this difference without consuming more heating energy.

During periods of poor outdoor air quality. A smoke event, agricultural spraying in nearby areas, or roadwork close by: recirculation allows you to continue circulating and filtering indoor air without introducing outdoor air for a few hours.

What recirculation does not do

This needs to be made clear, because the confusion is common and can lead to improper use:

  • It does not bring in any fresh air. CO₂ and volatile organic compounds continue to accumulate while it operates.
  • It does not replace ventilation. An appliance left in continuous recirculation throughout the cold season is equivalent to not ventilating at all.
  • It does not dry out the house. If indoor humidity is too high, only ventilation with outdoor air will lower it in winter.

That is why we never program recirculation alone as the default mode. It is used alternately or occasionally.


Humidity-based control: the setting that must change with the season

The droplet-shaped button provides access to the humidity setting. When indoor relative humidity exceeds the target, the unit automatically increases its airflow until it drops below the threshold.

The most common mistake in Quebec: setting the target once and never touching it again. A 40% setting works in October and becomes a source of condensation in January because the temperature of interior surfaces—glazing, frames, and corners of exterior walls—drops as the outdoor temperature falls.

Here is the chart we leave with our customers and review with them during commissioning:

Outdoor temperature Indoor relative humidity setting
0°C and above up to 40 %
–1°C to –10°C approximately 35 %
–11°C to –20°C approximately 30 %
–21°C to –30°C approximately 25 %
below –30°C approximately 20 %

The rule of thumb that sums it all up: if condensation appears along the bottom of the windows in the morning, the setting is too high for the current weather. Lower it by 5% and monitor for two or three days.

We also recommend that homeowners adjust the setting two or three times per winter rather than continuously—at the first deep freeze, in the heart of January, and during the spring thaw. Three adjustments per year, each taking less than a minute.


What gets set once on an RNC 155—and never revisited

LIFEBREATH RNC 155 Specifications

Specification Value
Type HRV (heat recovery ventilator), ENERGY STAR certified
Net supply airflow 163 CFM at 0.2 in. w.g. · 146 CFM at 0.3 · 132 CFM at 0.4
Apparent sensible effectiveness (ASE) at 0°C 84 % (at 59 CFM)
Sensible recovery efficiency (SRE) at 0°C 75 % (at 59 CFM)
Core Patented counterflow HEX, removable for cleaning
Power supply 115 V / 60 Hz, 1.4 A
Power consumption 66 W (low speed) / 118 W (high speed)
Defrost Recirculation (damper)
Configuration Horizontal, balancing ports on the door
Dimensions 19 in. H × 33.6 in. W × 14.75 in. D
Weight 71 lb (32.5 kg)
High speeds 3 settings selectable by the installer
Filters Washable, on both air streams
Suspension Adjustable straps and S-hooks, four threaded inserts
Drain fittings 2 × 1/2 in. (12 mm)
Control wiring 3 wires, minimum 20 gauge, maximum 100 ft

Two figures deserve comment.

84% apparent sensible efficiency at 0 °C. This is a high value, supported by the counterflow HEX core, whose geometry circulates the two airflows in opposite directions along their entire length rather than at right angles. Thermal contact is extended, so heat transfer is more complete.

66 W at low speed. On a unit that must run continuously, this is the figure that matters on an annual utility bill—far more than the power at high speed, which is only called upon intermittently.

The three selectable high speeds: the invisible setting

The RNC 155 allows the installer to choose, during commissioning, which of three high speeds the unit will use when it switches to maximum operation. The factory setting is the highest speed.

It is a parameter the owner never sees, that no wall control displays, and that explains why two identical homes equipped with the same unit can behave very differently.

Why we sometimes reduce it:

  • Noise. In a short duct system, maximum speed can generate whistling at the grilles. Lowering it by one setting eliminates the noise without compromising the required airflow.
  • Wintertime drying. A unit that ramps up too high every time the humidity threshold is triggered causes relative humidity to fall below the target.
  • Matching the airflow calculation. If the house requires 130 CFM and the maximum speed delivers 160, we maintain an unnecessary permanent over-supply.

Why we sometimes leave it at maximum: in a long duct system with many elbows, or in a densely occupied home, the reserve is necessary.

At this Repentigny project, we lowered it by one setting. The ductwork was short, the factory maximum speed produced a whistling sound at the main bedroom grille, and the required airflow was still achieved.

Balancing at the door ports

The RNC 155 is equipped with balancing ports directly on the unit door, allowing measurements without dismantling anything or drilling into the ducts.

Our method: measuring at both ports at high speed, reading the pressure-flow relationship, adjusting, taking a second measurement, then recording the values on a sheet left with the owner along with the date and technician identification.

In this house, the unit had never been rebalanced since construction. The measured difference between supply and exhaust exceeded 15%, leaving the house permanently depressurized and explaining some of the condensation observed in the basement.

Recirculation defrost and the two drains

The RNC 155 uses damper-based recirculation defrost. During the anti-frost cycle, a motorized damper closes off the outdoor air intake and circulates indoor air through the core to defrost it. The house is not depressurized during the operation, unlike units that simply shut off the supply fan.

This mechanism has one practical implication: the unit produces condensate and requires connected drains. The RNC 155 has two 1/2 in. connections. We connect them with separate, primed traps, on a continuous slope, with regular supports.

On units returned to service, this is the first thing we check. A clogged drain or a trap that has lost its prime on a unit with recirculation defrost eventually allows water to accumulate in the cabinet.

Mistakes to avoid

  1. Replacing the unit when only the control is outdated. An eight- or ten-year-old air exchanger in good condition deserves an evaluation of its interface and settings first.
  2. Leaving the humidity setpoint fixed all year. This is the primary cause of wintertime condensation on windows.
  3. Using recirculation as the primary mode. It does not bring in fresh air.
  4. Ignoring the installer's high-speed setting. It determines noise, drying, and actual airflow.
  5. Never rebalance. A 15% difference between the two airstreams is invisible and permanent.
  6. Neglecting both drains and their traps on a unit with recirculation defrost.
  7. Install the new control without redoing the wiring. Lifebreath controls operate on three wires, minimum 20-gauge, over a maximum run of 100 ft. Original wiring that is undersized or too long causes erratic behavior that no one associates with the cable.

Maintenance

  • Every three months — wash the filters for both airstreams. They are washable, eliminating a recurring cost, but only if they are actually washed.
  • Every six months — remove and clean the core counterflow, check both drains and their traps, and inspect the defrost damper.
  • Annually — inspection of exterior hoods, verification of the insulation and vapour barrier of the exterior ducts, revalidation of airflow rates at the door ports, and review of the humidity setting with the homeowner.

Compliance and programs

For new homes covered by the Quebec Construction Code, balanced mechanical ventilation is required, and it is a condition of the Novoclimat program. For an existing home like this one, modernizing a control or rebalancing a unit does not fall under a subsidy program — these are maintenance and optimization interventions. They remain among the most cost-effective services we perform, precisely because they cost a fraction of a complete replacement.

We systematically confirm the order of the work with the client when a broader project is being considered, especially when a heat pump or insulation work is planned, because the sequence affects eligibility for current programs.

For your project in Repentigny or elsewhere on the North Shore

At AirGreen, we always start by assessing what can be salvaged. A unit in good condition that is poorly controlled, improperly adjusted, or incorrectly balanced accounts for a significant share of the systems we inspect in Repentigny, Le Gardeur, Charlemagne, L'Assomption, and throughout the North Shore. The solution is often a modern control, documented rebalancing, and twenty minutes of explanations for the occupants.

When replacement is necessary, we say so too, with the numbers to back it up.

We carry out HVAC installations — air exchangers, wall-mounted and central heat pumps, air conditioners, and heating systems — in Repentigny, Montreal, Laval, Longueuil, throughout the North Shore and the South Shore. Licence RBQ # 5645-9605-01.

To have your LIFEBREATH air exchanger settings evaluated or to get a quote, call us at (514) 316-2973 or email sales@airgreen.ca.

The steps

How the job unfolds

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We locate the wall for the two outdoor hoods, the unit's spot, service access and the drain.

  1. The on-site estimateWe locate the wall for the two outdoor hoods, the unit's spot, service access and the drain.
  2. The quoteThe unit, its location and the price, in writing.
  3. The unitHung or set level, with clear access to the filters and the core.
  4. The outdoor hoodsFresh air intake and exhaust, kept apart and sealed.
  5. The ductsThe ones connected to the outside are insulated to prevent condensation inside the house.
  6. The drainConnected with its loop, when the unit needs one.
  7. The wall controlInstalled where you will see it and use it.
  8. BalancingIncoming and outgoing airflows are adjusted so the house is neither pressurized nor depressurized.
  9. The walkthroughSpeeds, filters, core: how to use it through the seasons.
The tour

What we check on a job like this one

Each number is a point we check on site. Switch between summer and winter to watch air and heat move.

Generic diagram: air exchanger, ducts and outdoor hoods

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. It removes stale air and brings in fresh air. The two airflows cross in the core without mixing.

  2. It recovers part of the heat from the outgoing air to temper the incoming air. Depending on the model, it also manages humidity.

  3. An outdoor hood, kept away from the exhaust so the house does not pull back the air it just removed.

  4. Humid, stale air leaves through its own hood, fitted with a damper.

  5. The ducts that connect to the outside are insulated to prevent condensation inside the house.

  6. Stale air is drawn from humid rooms and fresh air is sent to living areas. The airflows are balanced.

  7. It sets the mode and speed. You use it more when the house is humid or full of people.

  8. Depending on the model and the season, the core produces condensation, removed through a drain with its loop.

At your place

Is your home ready?

Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.

0 / 6 checked
Maintenance

Good habits, once the unit is in place

Six simple habits that keep the unit going. Your list stays on this device.

0 / 6 checked
Through the seasons

What to do, season by season

Three habits per season for this unit. They take a few minutes and prevent many calls.

  • Clean the filters and core as the manufacturer specifies.
  • Check the outdoor hoods: nests, debris, dampers.
  • Lower the speed if the outdoor air gets humid.
For your project

The right pages, at the right time

True or false

Four statements: true or false?

It all comes down to details you have just seen.

1. In an air exchanger, fresh air and stale air mix.

2. The two outdoor hoods must be kept apart.

3. An air exchanger can help with condensation on windows.

4. An exchanger never needs maintenance.

Frequently asked questions

What people ask us about this kind of work

9 questions
What does an air exchanger do?
It renews the air in the house and helps keep humidity in the right range: condensation, dry air, odours.
Does fresh air cool the house in winter?
The core recovers part of the heat from the outgoing air to temper the incoming air.
What speed should it run at?
Higher when the house is humid or full of people, lower the rest of the time. The wall control lets you adjust.
Does an exchanger need cleaning?
Yes. Filters and core get dirty. See our cleaning service.
What are the signs of poor ventilation?
Condensation on windows, lingering odours, stuffy air in closed rooms, mould in cold corners.
HRV or ERV: what is the difference?
An HRV (heat recovery ventilator) recovers heat from the outgoing air. An ERV (energy recovery ventilator) also recovers part of the humidity. The right choice depends on the house.
Should it run in winter?
Yes: winter, with the house closed, is often when humidity and odours build up. Adjust the speed to the condensation on the windows.
Does AirGreen hold the required licences?
Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
Is the estimate free?
Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.

Could this job help a neighbour?

Share
Similar projects

More jobs to see, near you

By town, by equipment or by region: browse more than 4,700 published projects.

Each dot: a town where AirGreen has published projects. The glowing dot: this job.

All our projects

Your project

An on-site estimate, the right capacity, the right equipment.

The on-site estimate is free and the quote follows within 24 hours.

  • RBQ licence5645-9605-01 · 15.8, 15.10, 16
  • EstimateOn site, free
  • QuoteWithin 24 hours

Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

Leave a comment