Job sheet · Project

Installation of a GREE FreeMatch R32 multi-zone wall-mounted heat pump with 4 heads in Calixa-Lavallée (Marguerite-D'Youville RCM, Montérégie)

Four heads, one compressor: we explain why the capacities do not add up. Installation of a GREE FreeMatch R32 GWHD(36)ND6MO in Calixa-Lavallée, with a room-by-room load calculation, measured piping, weighed R32 charge, and the correct AHRI code on file.

By AirGreen Climatisation & Chauffage Admin18 min read
City
Region
Equipment
Brand
Challenges
Published
–chapters, to open one by one
18 minto read the whole story
–type of installation
2026year published
At a glance

The job on one screen

Installation of a GREE FreeMatch R32 multi-zone wall-mounted heat pump with 4 heads in Calixa-Lavallée (Marguerite-D'Youville RCM, Montérégie)
Installation of a GREE FreeMatch R32 multi-zone wall-mounted heat pump with 4 heads in Calixa-Lavallée (Marguerite-D'Youville RCM, Montérégie)
The full story

The article, chapter by chapter

Four heads, one compressor: the thing quotes never explain

A 4-head multi-zone system is easy to sell. Four rooms, four remote controls, four temperatures. This is how most quotes present it, and this is what the client understands.

The physical reality is different, and it deserves to be explained before the work rather than during the first winter: the four heads share a single compressor, a single refrigeration circuit, and a single reversing valve. This constraint determines the sizing, the system's behaviour under simultaneous demand, whether or not one room can be heated while another is being cooled, and even the subsidy code the client may be able to use.

Here is how we approached this installation in Calixa-Lavallée, and what we explained to the homeowner before drilling the first wall.

Calixa-Lavallée: 500 residents, no duct network, no natural gas

Calixa-Lavallée is the smallest municipality in the Marguerite-D'Youville RCM, in Montérégie, between Verchères and Contrecoeur. About five hundred people, a predominantly agricultural territory, a modest village core, and a name borrowed from the composer of the national anthem.

For an HVAC contractor, this rural profile creates very consistent conditions:

  • No natural gas network. Heating is electric, oil-fired, or wood-burning.
  • Few homes equipped with a duct network. Homes heated with electric baseboards have never had ductwork, and installing it afterward often costs more than the equipment itself.
  • Very different needs from one room to another. A country home with a large south-facing open area, two upstairs bedrooms, and an office added in a former sunroom cannot be heated with a single setpoint.
  • Distances. The condenser is not always installed three metres from the living room.

This is the natural setting for multi-zone systems. Not because they are trendy, but because the central solution would require ductwork that does not exist.

Selected equipment: GREE FreeMatch R32, GWHD(36)ND6MO condenser

We selected the GWHD(36)ND6MO condenser, which supports 2 to 4 indoor units. This is the exact configuration for the project: four heads, with no room for any future additions. This point was discussed with the client because it is not insignificant.

Installed condenser specification sheet
Parameter Value
Outdoor model GWHD(36)ND6MO
Number of connectable indoor units 2 to 4
Power supply 208/230 V
Nominal cooling capacity 36,000 BTU/h (10,550 W)
Cooling capacity range 8,870–40,900 BTU/h (2,600–12,000 W)
Nominal heating capacity 36,000 BTU/h (10,550 W)
Heating capacity range 8,870–51,180 BTU/h (2,600–15,000 W)
Power input (cooling / heating) 3,000 W / 2,960 W
SEER2 21
HSPF2 10
EER2 12
EER / COP 3.52 W/W / 3.56 W/W
MCA / MOCP 30 A / 45 A
AHRI codes (ductless / ducted / mixed) 214931589 / 214931595 / 214931599
Certification ENERGY STAR
Outdoor airflow 3,413 CFM
Sound pressure (high speed) 63 dB(A)
Compressor: power input / RLA 3,514 W / 19.6 A
Refrigerant / factory charge R32 / 2,700 g (95.3 oz)
Dimensions (W × H × D) 1,020 × 826 × 427 mm (40-1/8 × 32-1/2 × 17-5/16 in)
Net weight 78.5 kg (173.1 lb)
Cooling range -30 °C to 48 °C
Heating range -30 °C to 24 °C
Pre-charged length 40 m (131 ft)
Maximum total length 80 m (262 ft)
Additional charge 20 g/m (0.2 oz/ft)
Maximum elevation difference 25 m (82 ft)
Liquid line / gas line 1/4 in / 3/8 in

The rule no one explains: head capacities do not add up

This is the core of sizing a multi-zone system, and this is where customer satisfaction and the contractor's reputation are determined.

The combination ratio

On a 4-head system, the sum of the indoor units' nominal capacities almost always exceeds the condenser's capacity. Four heads rated at 9,000, 9,000, 12,000, and 12,000 BTU/h total 42,000 nominal BTU/h on a condenser certified at 36,000 BTU/h, or approximately 117 %.

This is not a design error: it is the design. It relies on load diversity—the four rooms never reach their peak at the same time. A north-facing bedroom reaches its maximum demand at five in the morning in January; the south-facing living room reaches its own at three in the afternoon in July. The condenser modulates between 8,870 and 40,900 BTU/h in cooling and between 8,870 and 51,180 BTU/h in heating to follow the actual total, not the theoretical total.

This limitation must be clearly explained to the customer: at maximum simultaneous demand, each head receives less than its nominal capacity. On the coldest morning of the year, with four heads calling for heat, the distribution is proportional, and no room receives its full heating output. A combination ratio chosen without calculating the load for each room produces exactly this situation, and the customer concludes—in error—that the unit is defective.

The modulation floor: the trap of an undersized head

The other end of the range is just as important and much less well known. The condenser does not go below 8,870 BTU/h. That is its floor, regardless of the number of heads operating.

Direct consequence: if a single 9,000 BTU/h head operates alone one evening in October, the system is already at its minimum. It cannot modulate any lower. It reaches the setpoint, stops, and restarts—this is short cycling, with the resulting discomfort, compressor wear, and actual efficiency below the displayed SEER2.

We derive two design rules from this:

  1. Never connect a single small head to a large condenser hoping to add more later. The system will operate poorly throughout the interim period.
  2. Group zones that call for the same mode. Two upstairs bedrooms facing the same direction behave as a single load and keep the compressor above its minimum operating level.
One mode at a time: heating OR cooling

This is the most misunderstood feature of all multi-zone systems of this type. The four heads share a single refrigeration circuit with one reversing valve. The unit can therefore heat all four rooms or cool all four rooms. It cannot do both at the same time.

In practice, the first head to call determines the mode; a head requesting the opposite mode goes into standby or fan-only operation. In Calixa-Lavallée, as everywhere in Quebec, the critical period is the shoulder season: late April and early October, when a south-facing room with large windows overheats while a north-facing bedroom remains cool.

We discussed this with the client before signing, and this is the kind of conversation that distinguishes a properly designed HVAC installation from equipment sold by tonnage. Possible strategies:

  • Group zones by orientation and use, so contradictory demands are rare.
  • Accept the constraint with full awareness, which is the case in the vast majority of homes.
  • Physically separate a room with very different thermal behavior—a computer-equipped office or a glass-enclosed sunroom—on an independent system when the budget and intended use justify it.

One useful detail here: the cooling range extends down to an outdoor temperature of -30 °C. This is not a typo. A room with high internal heat gains—a home office, a home server room, or a room next to a wood stove—can be cooled in the middle of winter, which most systems refuse to do below 0 °C.

A single electrical circuit for the entire system

One feature of the FreeMatch R32 concretely changes the cost of the work: the indoor units are powered by the outdoor unit. There is no dedicated circuit or outlet to install in each room.

The electrical summary is therefore:

  • One circuit to the condenser, sized according to MCA 30 A and protected according to MOCP 45 A.
  • One interconnection cable to each indoor unit, routed with the refrigerant piping and condensate drain in the same conduit.

In an older house in Calixa-Lavallée—with lath-and-plaster walls, no vertical service cavities, and an electrical panel often already heavily loaded by baseboard heating—this design avoids four electrical penetrations and four panel circuits. It is a technical argument, but also a building-preservation argument.

The piping: where the real cost of a four-indoor-unit system lies

The condenser is factory-charged for 40 metres of total piping, across all circuits. The maximum total length is 80 metres, with a maximum elevation difference of 25 metres. Beyond the 40 metres included in the factory charge, 20 grams of R32 per additional metre must be added.

On a four-indoor-unit system, this calculation is not merely theoretical. Let us take a realistic layout for a two-storey country house:

Indoor unit Piping length
Living room (ground floor) 12 m
Primary bedroom (upstairs) 16 m
Second bedroom (upstairs) 9 m
Office (rear addition) 21 m
Total 58 m

The total of 58 m remains below the 80 m limit but exceeds the 40 m factory charge by 18 m. The additional charge is therefore 18 × 20 g = 360 g, bringing the system charge to approximately 3,060 g of R32.

Three consequences that we document systematically:

  1. The additional charge must be weighed, not estimated from pressure readings. An electronic scale, a written record, and a signature.
  2. The actual length of each branch must be measured, not inferred from a plan. Routing around joists and columns can easily add two or three metres per branch.
  3. The total charge, not that of a single indoor unit, governs the A2L requirements. We will get to that.

R32, A2L classification, and minimum room area: what changes with a multi-zone system

R32 is classified as A2L, mildly flammable, and the FreeMatch range comes standard with a refrigerant leak detection sensor. So far, there is nothing different from a standard wall-mounted air conditioner.

The difference is in the numbers. A 9,000 BTU/h single-zone mini-split contains a few hundred grams. This system contains more than three kilograms, and all that refrigerant circulates through a single circuit. If a leak occurs at one indoor unit, it is not the fraction assigned to that unit that can be released there: it is the circuit's full charge.

This distinction governs the minimum room area required by the applicable standard for each head. A small 8 m² bedroom poses no problem on a single-split system; on a high-load multi-zone system, it requires an explicit check against the installation manual's table and sometimes choosing a different location for the head or a different type of indoor unit.

We perform this calculation during the design stage, not at the time of installation. An entirely installed system whose head is located in a room that is too small cannot be corrected with a screwdriver.

The wall-mounted head: what the photo shows and what it implies

The visible wall-mounted unit is a GREE head installed high on a light-coloured wall in a finished room.

The display shows 74: a settings issue, not a malfunction

The digital display shows 74, meaning a setpoint in degrees Fahrenheit—approximately 23.3 °C. Units leave the factory with the imperial display, and many Quebec customers spend weeks reading a value that means nothing to them.

The switch to degrees Celsius is made using the remote control. We set it systematically during commissioning and show the customer how to do it, because an occupant who does not understand the display on their unit eventually adjusts it by trial and error—that is, incorrectly.

In the same conversation, we explain the remote control's remote sensor function, often called I Feel: the setpoint is then measured at the height of the remote control rather than at the head, two metres below the ceiling. In a room with a high ceiling, the difference between the two readings can easily reach two degrees.

Ceiling clearance and wall position

The head is installed near the ceiling, as it should be, but the clearance above the casing is not merely an aesthetic detail: it determines the return-air intake. A head pressed beneath molding or wedged under a poorly assessed cathedral ceiling recirculates its own discharged air and loses a measurable portion of its capacity.

We apply three positioning criteria, in this order:

  1. The return-air clearance above and on the sides, as specified in the manual.
  2. The path of the air jet, which must not sweep across a nearby side wall or blow directly onto a seated person.
  3. The condensate drain outlet with a continuous slope, which very often determines which side of the wall the head can be installed on.
Wall marks: a real, predictable, and avoidable problem

Marks can be seen on the wall beneath the head. This phenomenon is known and has nothing to do with a leak: the air jet carries suspended dust along the surface, and the deposits settle in the turbulence zones beneath and beside the unit.

The aggravating factors are identifiable: a dirty filter, a head installed too close to a perpendicular wall, louvers fixed in a downward position, and above all, a lack of regular HVAC maintenance. Cleaning the filters every four to eight weeks during the operating season resolves most of the problem. We leave this instruction in writing and show the customer how to remove the filters before leaving the job site.

The most costly design mistakes on a four-head multi-zone system

We are regularly called in as a second option for multi-zone systems installed elsewhere, in Montreal, Laval, Longueuil, on the North Shore, and on the South Shore. The same mistakes keep recurring, and almost all of them are made before the first hole is drilled.

  • No room-by-room load calculation. The heads are selected based on floor area, which consistently results in oversized bedrooms and undersized open areas.
  • An excessive combination ratio, promising the customer performance the condenser cannot deliver under simultaneous demand.
  • A single small head on a large condenser, with short cycling guaranteed outside peak season.
  • The single-mode constraint never explained, resulting in a service call in October and a customer convinced they were misled.
  • The total piping length not added up. On a four-head system, it is easy to exceed the 40 m of pre-charged piping without realizing it, resulting in a system that is undercharged by several hundred grams.
  • The additional charge estimated from pressure readings rather than weighed.
  • The minimum room area not verified for the head installed in the smallest bedroom.
  • The condensate drain installed with a reverse slope, or connected to a pump when a gravity drain was possible—each added pump is another failure point, multiplied by four.
  • Unsealed wall penetrations on the interior side, allowing outdoor air to pass behind the drywall and causing condensation in winter.
  • The condenser installed on the ground without clearance for defrosting, which matters twice as much on a multi-zone system operating for more hours per season.

Rebates: three AHRI codes for a single condenser

This system has an administrative peculiarity that deserves the full attention of owners and contractors.

The GWHD(36)ND6MO condenser has three distinct AHRI reference codes, depending on the type of indoor units connected to it:

Indoor unit configuration AHRI code
Non-ducted (wall-mounted units, cassettes, consoles) 214931589
Ducted (ducted units) 214931595
Mixed (ducted and non-ducted) 214931599

In other words, adding a single ducted unit to a set of three wall-mounted heads changes the system from code 214931589 to code 214931599. The condenser is physically the same. The subsidy application is not.

We have seen applications denied or delayed for this very reason: a file prepared with the “non-ducted” code even though the installed system included a ducted unit. We therefore provide the code corresponding to the configuration actually installed, along with the list of indoor units.

Systems with this level of efficiency—SEER2 21, HSPF2 10, and ENERGY STAR certification—are generally eligible for financial assistance programs offered in Quebec, subject to the criteria in effect when the application is submitted. These criteria change faster than brochures do, so we recommend verifying them before signing the contract rather than after the work is completed.

What the customer received at the end of the project

  • The complete list of indoor units, with their capacity and location.
  • The AHRI code corresponding to the configuration actually installed.
  • The measured length of each branch, the total, and the additional charge weighed in grams.
  • Commissioning readings for each head: incoming and outgoing air temperatures, current draw, and pressures.
  • Confirmation that the minimum room size requirement was verified for each of the four heads.
  • The display switched to degrees Celsius and a demonstration of the remote sensor function.
  • Instructions for cleaning the filters and the recommended HVAC maintenance schedule.

AirGreen in Calixa-Lavallée and Greater Montreal

Multi-zone systems account for an increasing share of our work, particularly in the rural municipalities of Montérégie where ductwork does not exist and natural gas is unavailable. We serve Calixa-Lavallée and the entire MRC de Marguerite-D'Youville, as well as Montréal, Laval, Longueuil, the North Shore, and the South Shore.

If you are considering a wall-mounted heat pump, a two-, three-, or four-head system, a central heat pump, or replacing an existing unit, our team performs a room-by-room load calculation before recommending a model. With a multi-zone system, this calculation—not the total tonnage—determines whether the system will deliver on its promises in January.

Your numbers

The job tools

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Size checkYour baseboards, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    The steps

    How the job unfolds

    The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

    Step 1 of 9The on-site estimate

    We look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.

    1. The on-site estimateWe look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
    2. The quoteModel, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
    3. Getting readyFloors and furniture protected, wall plate position marked level, wall opening located.
    4. The wall openingA single opening, with the slope the drain needs to flow outside.
    5. The outdoor unitSet on a stand raised above the snow, with the clearances the manufacturer requires.
    6. Lines, cable and drainConnected, insulated and protected. The opening is then sealed against water, cold air and insects.
    7. The electrical workA dedicated circuit and an accessible disconnect near the outdoor unit.
    8. Tests and start-upLeak test, vacuum, then start-up and a check of heating and cooling.
    9. The walkthroughRemote, modes, filters: we show you the essentials before we leave.
    The tour

    What we check on a job like this one

    Each number is a point we check on site. Switch between summer and winter to watch air and heat move.

    Generic diagram: wall-mounted heat pump, indoor and outdoor units

    In summer, the outdoor unit rejects the house's heat outside.

    Generic illustration of this type of installation, not a survey of this job site. Tap a number.

    1. Mounted level on a wall plate, high enough for the air to reach the whole room, with enough space around it to slide the filters out easily.

    2. The refrigerant lines, the communication cable and the drain go through the wall in a single opening, sealed against water, cold air and insects.

    3. Two insulated copper pipes connect the two units. Outside, a line cover can protect them from sun, knocks and weather.

    4. A shut-off switch near the outdoor unit isolates it safely for service. It must stay accessible at all times.

    5. The compressor and the fan. In heating mode it captures heat from the outdoor air, even in winter, and moves it inside.

    6. On the ground or on the wall, it keeps the unit above accumulated snow. The unit stays clear and defrost water can drain away.

    7. The fan needs to blow freely. Storage, a fence or a wall too close, and efficiency drops while noise goes up.

    At your place

    Is your home ready?

    Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.

    0 / 6 checked
    Maintenance

    Good habits, once the unit is in place

    Six simple habits that keep the unit going. Your list stays on this device.

    0 / 6 checked
    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Clean the indoor unit's filters.
    • Clear leaves and debris left on the outdoor unit by winter.
    • Test cooling before the first hot days.
    For your project

    The right pages, at the right time

    True or false

    Four statements: true or false?

    It all comes down to details you have just seen.

    1. In heating mode, the outdoor unit can produce water.

    2. You pick the capacity with a simple square-footage rule.

    3. A multi-zone connects several indoor heads to a single condenser.

    4. The disconnect can sit behind the patio furniture.

    Frequently asked questions

    What people ask us about this kind of work

    12 questions
    Does a wall-mounted heat pump heat in winter?
    Yes, it heats and cools. Its capacity drops in very cold weather; the operating range depends on the model and is listed on its spec sheet.
    Wall-mounted or multi-zone: how do I choose?
    One wall head and one condenser outside: the direct solution for a room or an open area. For two to five rooms, a multi-zone puts one head in each room on a single condenser.
    Where does the outdoor unit go?
    Where it stays above the snow, clear and accessible, away from walkways. We decide it with you during the estimate.
    Are there grants?
    Depending on the model and your situation, assistance programs may apply, including Hydro-Québec's LogisVert. AirGreen checks the model number before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city: location, distances, noise. See permits and by-laws, and we check for your address.
    How cold can it heat?
    It depends on the model. According to Hydro-Québec, newer models work down to a temperature between −15 °C and −25 °C, and some cold-climate models are certified lower. The minimum temperature is on each unit's spec sheet.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Is it noisy?
    The sound level depends on the model and is listed in decibels on each unit's spec sheet. Location matters too: when possible, we avoid putting the outdoor unit under a bedroom window.
    The outdoor unit is covered in ice: is that normal?
    Some frost is: the unit runs defrost cycles. Never hit the ice. If the unit stays iced up or stops heating, call us.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    An on-site estimate, the right capacity, the right equipment.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment