GE ZONELINEHow PTAC costs compare with other commercial HVAC systems: what heat costs, room by room
In short, for managers
A commercial project with AirGreen
- 1On-site assessmentAn AirGreen advisor visits your building.
- 2QuoteClear and detailed.
- 3Planning with youWe set the dates together.
- 4Work and follow-upRBQ 5645-9605-01 (15.8, 15.10, 16).
The same heat, three prices: PTAC, wall heat pump or baseboards
In a hotel, a rental building or an office, each room has its own unit. What changes from one system to the next is how much electricity it takes to deliver the same heat, and that depends on how cold it is outside. The figures below come from the manufacturers' documents and the AHRI certificate; two units sold by AirGreen serve as examples.
GE ZONELINE
FUJITSU AIRSTAGE ORION XLTH12,000 BTU
ASUH12KZAS · AOUH12KZAH1 · AHRI 214888802See the product page1 kWh of electricity = 1 kWh of heat
All heat from resistance, at any temperatureWhat 100 kWh of heat costs in the room
Pick an outdoor temperature: each unit needs only "100 ÷ COP" kWh of electricity to deliver 100 kWh of heat. The COP comes from each manufacturer's document or the AHRI certificate, at the temperature shown; nothing is estimated between two temperatures.
Dark square: 1 kWh of electricity. Coloured squares: the heat delivered in return, one square per 0.25 kWh. Bar: the electricity needed for 100 kWh of heat.
How this amount is calculated
Electricity = 100 kWh of heat ÷ COP. Cost = electricity × Hydro-Québec Rate D price in force on April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average) × 1.14975 (GST and QST). Access charges are not counted. A business is often billed under another Hydro-Québec rate: the kWh column does not change, only the price does.
GE PTAC: COP 3.6 at 8.3 °C (47 °F) per the GE sheet, AHRI 310/380 test. Below −3.9 °C (25 °F), the sheet says the heat pump stops; heat then comes from the electric element, whose power and heat output the sheet publishes: 4,800 W for 16,300 BTU/h, i.e. 16,300 ÷ (4,800 × 3.412) = 0.995, rounded to 1.0. Wall heat pump: AHRI-certified COPs published by NEEP (record 392122), at rated or maximum capacity as you choose; at −26.1 °C, only the COP at maximum capacity is published.
AirGreen method v1.1 (prices), November 18, 2026. An estimate is for comparing units under the same conditions. The real bill depends on the building, insulation, settings and use; this amount is not a promise.
The handover: where the PTAC hands over to its heater
A heat pump PTAC carries two heat sources in one box. GE publishes its heat pump's limit at −3.9 °C; colder than that, the electric element chosen at order time does the heating. The wall heat pump publishes its certified maximum capacity down to −26.1 °C. Pick the PTAC element to see its heat on the same scale.
Purchase price, upkeep, service life: what this page does not put a number on, and why
You often read that a PTAC costs less to buy and maintain than a central system, a VRF or a wall heat pump. No document we consulted shows this, and a project's price depends on the building. Here instead is what weighs on the bill for each type, to check in your quote.
One unit per room, in the wall
A sleeve goes through the outside wall: GE requires an opening of at least 16 1/4 × 42 1/4 in. Each unit has its own circuit: 15, 20 or 30 A depending on the element chosen (GE sheet). Heating in extreme cold goes through that element.
An indoor head, an outdoor unit
A refrigerant line connects the head to the outdoor unit; some outdoor units serve several rooms (multi-zone). Performance is certified per combination, on the AHRI certificate.
One unit, a duct network
Heat travels through ducts to each room. The cost depends mostly on the network to build or reuse, which no unit sheet puts a number on.
A refrigerant network, many units
One or more outdoor units feed many indoor units. Piping and connected-capacity limits come from each manufacturer's design manual; the project is calculated case by case.
On each product page and in the written quote that follows the assessment visit.
The "What 100 kWh of heat costs" block above: it is the only part of the cost the documents let us compare figure by figure.
Each unit's manual describes the expected upkeep (filters, cleaning). No document we consulted publishes an upkeep cost comparable from one system to the next.
None of the documents we consulted publishes one. So this page does not state one.
The two examples, line by line
| Measure | GE ZONELINE AZHS12 | FUJITSU AIRSTAGE ORION XLTH 12,000 |
|---|---|---|
| Heating at 8.3 °C (47 °F) | ||
| Heating capacity at 8.3 °C | 10,600 BTU/h at 230 V10,500 at 208 V · GE sheet, AHRI 310/380 | 16,000 BTU/h ratedrange 3,500 to 23,600 · NEEP 392122 |
| COP at 8.3 °C | 3.6 at 230 and 208 V | 4.64 rated · 3.07 at max. capacity |
| In extreme cold | ||
| Heat pump lockout | Heat pump down to −3.9 °C (25 °F), then electric element | No automatic lockout stated below −26 °C (brochure FG8153C) |
| Electric element power and breaker | 2.4 · 3.4 · 4.8 kW at 230 V8,100 · 11,600 · 16,300 BTU/h; breaker 15 · 20 · 30 A | No backup element described in the documents consulted |
| Heating capacity at −15 °C | That of the chosen element: 8,100 to 16,300 BTU/h | 16,600 BTU/h max. · COP 2.16NEEP 392122 |
| Cooling — different test methods, not highlighted | ||
| EER2 or EER at 35 °C | EER 11.6 at 230 VAHRI 310/380 · 11.8 at 208 V | EER2 16.0NEEP 392122 · SEER2 30.5 |
| Rated capacity at 35 °C | 12,000 BTU/h at 230 V | 12,000 BTU/h |
| Installation and listings | ||
| Clearance: wall opening | 16 1/4 × 42 1/4 in minimumRAB42MG sleeve 42 × 16 × 13 3/4 in | Passage for the refrigerant line to the outdoor unit |
| RefrigerantGWP per IPCC (AR4); ASHRAE 34 class | R-454B · GWP 466 · A2L | R-32 · GWP 675 · A2L |
| AHRI certificate · NEEP record | Not stated on the GE sheet; PTACs are not in the NEEP list | 214888802 · 392122 |
| ENERGY STAR · cold climate | Not stated on the GE sheet | Yes · yes (NEEP) |
No value is highlighted: the two units are tested under different standards (AHRI 310/380 for the PTAC, AHRI 210/240 for the wall heat pump). The GE sheet carries the note "projected specifications, subject to change".
Questions about the cost of a PTAC
Why doesn't this page give the price of a PTAC or a VRF?
A project's price depends on the building: number of rooms, walls, electrical circuits, existing network. Unit prices are on their product pages and the project price is in the written quote. This page compares what the documents let us compare: the electricity needed for the same heat.
What is a COP?
The coefficient of performance: heat delivered divided by electricity used, under specific test conditions. A COP of 3.6 means 3.6 kWh of heat for 1 kWh of electricity at that temperature. An electric resistance, like a baseboard, has a COP of 1.
Does a PTAC heat in extreme cold?
Yes, through its electric element. The GE sheet says the heat pump runs down to −3.9 °C (25 °F); colder than that, the element chosen at order time (2.4, 3.4 or 4.8 kW at 230 V) produces 8,100, 11,600 or 16,300 BTU/h, at a COP of about 1.
Can the PTAC and wall heat pump COPs be compared directly?
Not quite. The PTAC is tested under AHRI 310/380 and the wall heat pump under AHRI 210/240, published by NEEP. Both give a COP at 8.3 °C, but the test setups differ. This page puts them side by side without highlighting either.
Does my business pay Rate D?
Hydro-Québec Rate D is for residential use; an apartment in a rental building is often billed under it. A business or a hotel is generally billed under a business rate. The number of kWh shown does not change: multiply it by the price on your bill.
Why a wall heat pump as an example?
Because it also serves one room at a time, like a PTAC, and it has an AHRI certificate published by NEEP at several temperatures. The FUJITSU AIRSTAGE ORION XLTH 12,000 BTU is sold by AirGreen; it is an example, not a recommendation.
Rooms to heat and cool, one at a time?
PTAC, wall heat pumps or another system: AirGreen offers both types shown here. The quote follows the assessment visit.
Documents consulted
Data verified November 18, 2026. Values come from the manufacturers' documents and the AHRI certificate published by NEEP; none is estimated between two published temperatures. Amounts are estimates whose method is described above.
GE, ZONELINE, FUJITSU AIRSTAGE and ORION XLTH are trademarks of their respective owners. Logos and images identify the products only. AirGreen is a dealer; this page is not produced, sponsored or approved by the manufacturers. Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong? Write to us at sales@airgreen.ca.