Project

Installation of a MIDEA EVOX G3 central heat pump in L’Île-Bizard–Sainte-Geneviève

In L’Île-Bizard–Sainte-Geneviève, AirGreen installs a MIDEA EVOX G3 central heat pump on wall brackets, above a technical area containing another unit, a basement window, and pool equipment.

By AirGreen Climatisation & Chauffage Admin17 min read
Installation of a MIDEA EVOX G3 central heat pump in L’Île-Bizard–Sainte-Geneviève
Installation of a MIDEA EVOX G3 central heat pump in L’Île-Bizard–Sainte-Geneviève
Generic diagram: central heat pump, indoor module and ducts

In summer, the outdoor unit rejects the house's heat outside.

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.

  2. The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.

  3. A shut-off switch near the outdoor unit isolates it safely for service.

  4. Sitting on the indoor module, it moves heat between the house air and the refrigerant.

  5. Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.

  6. Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.

  7. It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.

  8. It runs the heat pump and the backup heat. It must be compatible with the installed system.

A central installation in an already occupied technical area: elevated heat pump, basement window, existing unit, and pool equipment

At L’Île-Bizard–Sainte-Geneviève, we completed an installation of a MIDEA EVOX G3 central heat pump that perfectly illustrates a common reality in renovations: the ideal location on paper does not always exist on the actual building. Here, the outdoor unit had to be integrated into a heavily used side passage, against a brick wall, near a basement window, another existing outdoor unit, and a pool filtration system.

The photo taken after our work immediately shows why this project required precise planning. The MIDEA EVOX G3 was not placed on the ground. We installed it on elevated metal wall brackets, at a higher level than the other equipment located in this part of the property. This positioning allowed us to make smart use of the vertical space without further sacrificing the ground-level passage.

The other important detail concerns the orientation. The MIDEA’s large front fan is directed toward the open space in front of the unit, while the refrigerant and electrical connections are located on the right side, against the wall. We were therefore able to maintain both a good air discharge area and reasonable access to the service components.

For a central heat pump in L’Île-Bizard–Sainte-Geneviève project, the outdoor location must be considered as carefully as the tonnage selection. The machine must operate in July as well as January, when snow, ice, and defrost cycles completely change the conditions around the equipment.

Use the available height rather than cluttering the ground further

The first challenge of this project was the available space.

In the foreground of the photo, another white outdoor unit already occupies a significant portion of the area. On the right, the pool equipment also encroaches on the workspace. Behind the appliances, a basement window must remain accessible. Finally, the paved passage on the left must continue to serve its purpose.

Placing the new MIDEA directly on the ground would have reduced this area even further.

We therefore made use of the available height by securing the heat pump against the building structure on supports designed to bear its weight.

This solution offers several advantages:

  • preserve the ground-level passage;
  • keep the new unit away from the other condenser;
  • better accommodate snow accumulation;
  • create space for defrost water;
  • maintain better accessibility around the different units;
  • avoid occupying the area already used by the pool equipment.

In this specific context, raising the unit was not an aesthetic option. It was part of the project's overall logic.

A heat pump designed to operate down to -30 °C must be installed to survive a real winter

Midea documentation for the EVOX G3 Extreme Heat range states continuous operation down to -30 °C. In its test conditions, the manufacturer also indicates up to 100% heating capacity at around -25 °C, with a COP that can reach approximately 1.9.

This low-temperature performance is only truly useful if the outdoor installation remains functional throughout the winter.

A central heat pump used for heating must deal with two very real factors: snow and defrost water.

When the outdoor coil accumulates frost, the unit periodically runs a defrost cycle. The ice then melts, and the water falls beneath the unit. In cold weather, this water can refreeze.

That is why we never treat the lower clearance as a detail.

The MIDEA visible in this installation is high enough to leave a clear area beneath its cabinet. This provides more clearance when water freezes or snow accumulates around the building.

An elevated installation without compromising the basement window

The window located behind and below the equipment area represented another important constraint.

A heat pump should not unnecessarily block an existing opening when more thoughtful positioning is possible.

We must consider:

access to the window,
cleaning access,
air circulation,
refrigerant lines,
drainage,
and future maintenance of the heat pump.

In this project, using wall brackets made it possible to keep the unit above part of this area rather than fill the entire ground-level space.

This type of decision is important in the residential areas of L’Île-Bizard–Sainte-Geneviève, where existing homes were not necessarily originally designed to accommodate multiple modern outdoor units.

Fitting two outdoor units into the same area

The presence of a second outdoor unit changes a lot.

When two units are located in a relatively compact area, we must prevent the discharge air from one from adversely affecting the intake of the other. We must also leave enough space to access the service panels.

The MIDEA EVOX G3 uses a horizontal front discharge.

According to Midea, the outdoor unit combines a horizontal-discharge fan with a vertical heat exchanger. The manufacturer states that this configuration promotes more uniform airflow across the heat exchanger's surface and improved heat-transfer efficiency as the temperature decreases.

On this installation, this geometry is particularly useful: the air is discharged directly toward the open area in front of the machine rather than toward the brick wall.

The presence of a pool system also changes how the job site is organized

On the right side of the photo, a pool filtration system with piping and hoses can be clearly seen.

This equipment occupies an area that must also remain accessible.

We therefore avoid treating the heat pump as if it were the property's only technical equipment. A good installation must take into account everything that is already there.

On this job, we had to preserve enough space to:

  • work on the heat pump;
  • work on the other outdoor unit;
  • access the pool system;
  • move along the building;
  • reach the electrical connections;
  • keep the basement window functional.

This coordination becomes particularly important when several contractors may work in the same area over the years.

Refrigerant lines protected and grouped against the wall

The photograph also shows the routing of the refrigerant lines.

The pipes exit from the right side of the heat pump and then enter a vertical duct installed on the façade. The insulated lines are therefore not simply left hanging against the building.

This protection serves several purposes.

It limits the insulation's exposure to UV rays, protects the lines from physical damage, improves the support of the run and gives it a much neater finish.

Installing a central heat pump sometimes involves several metres of refrigerant line. How this line is protected can therefore have a significant impact on the installation's durability.

The service valves must remain accessible

The photo also shows a good view of the right side of the MIDEA unit, where the refrigerant connections are located.

This area must remain accessible because it may be needed for:

  • diagnostics;
  • pressure testing;
  • refrigerant circuit service;
  • certain repairs;
  • checking the connections;
  • long-term maintenance.

When we position a heat pump against a wall or near other equipment, we must think about the person who will return to work on the machine ten years from now, not just the team installing it today.

M-Powevi technology and maintaining low-temperature heating

The EVOX G3 uses the M-Powevi compressor technology described by Midea.

According to the manufacturer, when operating in extreme cold, the machine can inject vapor at an intermediate temperature to increase the amount of compressed refrigerant and support heat production.

Midea also mentions a test on a three-ton system in which the system reaches up to 118% of its rated heating capacity at around -25 °C, with a COP of 1.92 under the stated conditions.

We never automatically apply this figure to every installed unit.

It depends on the model, capacity, and precise test conditions. Nevertheless, it clearly shows that the EVOX G3 platform was developed with cold-weather heating as a major objective.

From the outdoor unit to the ductwork: why an EVOX G3 must be considered as a complete central system

Capacities ranging from approximately 18,000 to 54,000 BTU/h

The term MIDEA EVOX G3 refers to a complete product line.

The documentation shows cooling capacities ranging from approximately 18,000 to 54,000 BTU/h, with efficiencies reaching up to 19 SEER2, 12.5 EER2, and 10.8 HSPF2 depending on the configuration.

The Extreme Heat series presented by Midea includes, among others:

  • 18,000 BTU: MAUSE-H18B-2A + MO1HE-H18B-2A
  • 24,000 BTU: MAUSE-H24B-2A + MO1HE-H24B-2A
  • 30,000 BTU: MAUSE-H30B-2A + MO1HE-H30B-2A
  • 36,000 BTU: MAUSE-H36B-2A + MO1HE-H36B-2A
  • 48,000 BTU: MAUSE-H48B-2A + MO1HE-H48B-2A
  • 54,000 BTU: MAUSE-H60B-2A + MO1HE-H60B-2A.

The rating plate of the photographed unit is located on its side, but its text does not allow us to confirm the exact capacity of this installation with sufficient certainty.

We therefore do not assign it a tonnage based on a visual estimate.

Efficiency depends on the exact indoor-outdoor pairing

The Midea table shows, among other things, the following performance figures for the Extreme Heat combinations described:

  • 18,000 BTU: 19 SEER2, 12.5 EER2, 10.1 HSPF2
  • 24,000 BTU: 18.6 SEER2, 12 EER2, 10 HSPF2
  • 30,000 BTU: 17.2 SEER2, 12 EER2, 10.8 HSPF2
  • 36,000 BTU: 17.7 SEER2, 12 EER2, 10.0 HSPF2
  • 48,000 BTU: 17.5 SEER2, 12 EER2, 9.5 HSPF2
  • 54,000 BTU: 17.5 SEER2, 12 EER2, 9.5 HSPF2.

This shows why the word “EVOX” on a quote is not enough.

We want to know the exact outdoor model, indoor model, and their certified combination.

The right tonnage is not necessarily the largest

For a home in L’Île-Bizard–Sainte-Geneviève, we size the heat pump according to the actual building.

We consider, in particular:

  • heat loss;
  • insulation;
  • heated floor area;
  • windows;
  • airtightness;
  • ceiling height;
  • existing ductwork;
  • return-air paths;
  • required airflow;
  • available electrical capacity;
  • auxiliary heating.

An oversized system can create its own operating problems. Conversely, insufficient capacity can unnecessarily increase reliance on auxiliary heating.

Sizing therefore remains an essential step.

Computational Constant Airflow 2.0: an important feature when retaining existing ductwork

In a central heat pump, the ductwork can become the system’s limiting factor.

Midea equips the EVOX G3 with Computational Constant Airflow 2.0 technology. The documentation indicates that the indoor fan can adjust its output based on the resistance encountered in the ductwork. Midea presents examples of up to approximately 1.2 in. of water column static pressure and mentions up to 60 airflow adjustment levels.

This capability can be useful in an existing home where the ductwork is not new.

Factors such as a denser filter, certain elbows, duct length, or limited return air can increase resistance.

But an important distinction must be kept in mind: an adaptable fan does not replace good ductwork.

If the system is improperly sized, we must identify and correct the problem whenever possible.

The M-Coil and symmetrical fan of the indoor module

The EVOX G3 documentation also presents an M-Coil combined with a symmetrical fan.

In the comparison shown by Midea, this architecture is intended to achieve more even air distribution through the evaporator. The manufacturer presents an approximately 2% difference in airflow between the heat exchanger sections and less than 0.02 in. of water column pressure loss in the example shown.

The homeowner never sees this part when looking at the outdoor unit in the yard.

Yet it influences the operation of the entire system.

A modular indoor unit for difficult basements and mechanical rooms

The EVOX G3 uses a Block N Lock architecture that allows different orientations of the indoor unit.

Midea offers up to six configurations, including vertical, horizontal, and low-boy installations.

This design becomes particularly interesting in renovations.

In several homes in the West Island and L’Île-Bizard–Sainte-Geneviève, the mechanical room may have long contained a water heater, piping, storage, or other equipment.

Being able to configure the indoor unit more easily gives us greater flexibility to integrate the system without unnecessarily rebuilding the entire room.

A width designed to facilitate certain furnace replacements

Midea lists indoor unit widths of approximately 14.5 to 21.5 inches, depending on capacity.

The documentation also indicates compatibility with 115 V and 208/230 V indoor power supplies in the applicable configurations.

This facilitates certain modernization projects involving an older furnace.

But before discussing a direct replacement, we always check:

the plenum,
the ducts,
the returns,
the electrical supply,
the protections,
and the auxiliary heating configuration.

Auxiliary heating: up to 25 kW depending on the configuration

Midea's documentation provides for auxiliary heating kits rated at 10 kW, 15 kW, and 25 kW, with staged control.

The largest component is not automatically the best.

We must find a balance between the home's heat loss, the heat pump's low-temperature performance, and the capacity of the electrical panel.

485 communication or 24 V control

The EVOX G3 lineup also provides different control methods.

Midea indicates compatibility with 485 communication as well as 24 V controls, with automatic identification of the control mode in certain configurations and the option to use third-party thermostats.

This flexibility can be useful when replacing an existing system.

The manufacturer also describes its communicating thermostat and the SmartHome app, with scheduling, consumption monitoring, diagnostics, and remote update features.

Filtration up to MERV 13

The brochure presents a module that can accommodate 1-, 2-, or 4-inch filters, including MERV 13 in the configuration described.

A higher-performance filter media can trap more dust, pollen, and particles.

However, its impact on static pressure must always be considered.

We therefore do not choose a filter simply because its MERV rating is higher. We first want to ensure that the system maintains the required airflow.

R-454B: a new refrigerant that also changes service practices

The EVOX lineup presented by Midea uses R-454B.

The documentation identifies it as an A2L refrigerant with a GWP of 466.

For the homeowner, this difference is barely noticeable in everyday use.

For our refrigeration technicians, it means that the equipment, practices, and service procedures must be adapted to this new generation.

LogisVert Rebate: why we do not announce an amount without the exact combination

Midea indicates that its featured range exceeds the ENERGY STAR Most Efficient specifications mentioned in its documentation.

However, this alone does not confirm the amount of financial assistance available in Quebec for this specific project.

To determine eligibility for a central heat pump in L’Île-Bizard–Sainte-Geneviève, we always verify:

  • the outdoor model;
  • the indoor model;
  • the certified combination;
  • the AHRI number;
  • the capacity;
  • the program rules applicable at the time of installation.

Best practice is to start with the exact model numbers, not only the EVOX G3 commercial name.

The mistakes this project helps illustrate

Adding a new unit without considering the equipment already in place

The presence of the other condenser and pool equipment had to be incorporated into our plan from the outset.

Installing the new heat pump directly on the ground

This would have reduced clearance and provided less room for snow and defrosting.

Blocking the basement window

The installation must respect the building’s existing functions as much as possible.

Forgetting about future service work

The connections and service panels must remain accessible after the work is completed.

Neglecting air discharge

A large front fan must not blow directly into an obstacle or into another piece of equipment’s intake.

A central installation that truly adapts to the property

This MIDEA EVOX G3 central heat pump project in L’Île-Bizard–Sainte-Geneviève clearly shows why a professional installation is not limited to the specifications on a technical sheet.

We had to work in an area already occupied by several pieces of equipment. We therefore used wall brackets to free up the ground, kept an open area in front of the fan, organized the connections on the technical side, and protected the lines running up the facade.

The MIDEA EVOX G3 offers an interesting platform for Quebec’s climate: Inverter technology, low-temperature operation, an adaptable indoor module, advanced airflow management, and a new generation of refrigerant.

At AirGreen, our responsibility is then to turn these characteristics into a HVAC installation that is consistent with the actual home.

It is this same approach that we apply to L’Île-Bizard–Sainte-Geneviève, Montréal, Laval, Longueuil, on the North Shore and on the South Shore: analyze the building, anticipate constraints, then install the system so that it remains efficient, accessible, and practical for many years.

In figures
The steps

How it goes, from the first call to the end

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.

  1. The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
  2. The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
  3. Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
  4. The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
  5. The outdoor unitOn a level base, raised above the snow, with free space all around.
  6. The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
  7. Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
  8. Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
  9. The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
The unit

What the unit delivers when it is cold

The range as published on airgreen.ca: pick a size to see its capacity in deep cold.

The range, size by size
SizeHeating at −8 °CHeating at −15 °CColdest certified pointCOP at −15 °CSEERHSPFIndicative LogisVert aid
Midea EVOX G3 · 1.5 tons14,70018,600−30 °C: 11,8002.1219.010.1$1,764
Midea EVOX G3 · 2 tons20,80020,600−30 °C: 12,1002.1418.610.0$2,496
Midea EVOX G3 · 2.5 tons24,00033,200−30 °C: 17,9001.9717.210.8$2,880
Midea EVOX G3 · 3 tons33,00037,400−30 °C: 27,6001.918.010.0$3,960
Midea EVOX G3 · 4 tons39,50048,000−30 °C: 27,2002.017.59.5$4,740
Midea EVOX G3 · 5 tons45,00054,000−30 °C: 37,3001.917.59.5$5,400

Data read live from the airgreen.ca page of each size (NEEP / AHRI certified performance). When the title names the installed size, it is highlighted; otherwise the whole range is shown. The aid shown is today’s, using Hydro-Québec’s rule ($120 per 1,000 BTU/h at −8 °C); amounts quoted in the article date from its publication. Only Hydro-Québec confirms the assistance granted.

Your numbers

And at your place?

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Before / afterThe cost of the same heat

Baseboards and electric furnaces turn 1 kWh of electricity into 1 kWh of heat. A heat pump delivers more: that is its COP. At Hydro-Québec’s rate D (11.142¢/kWh above 40 kWh a day, since 1 April 2026):

Before · baseboards11.142¢/kWh
After · heat pump–

Hydro-Québec: a heat pump can be up to three times more efficient than baseboards for heating in the colder months.

Estimate per kWh of heat, at the chosen temperature, using the certified COP from the product page. Taxes, access charge and backup heat not included.

Size checkYour electric furnace, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Check the indoor module's filter.
    • Clear winter debris from the outdoor unit.
    • Test cooling before the heat arrives.
    And at your place?

    Which type of equipment for your project?

    Pick what looks like your need.

    Mistakes avoided

    Four mistakes we do not make

    Flip each card to see what we do instead.

    Frequently asked questions

    What people ask us about this kind of work

    11 questions
    Can I keep my current ducts?
    Often, yes: the central heat pump connects to the existing ducts. We check their condition and size during the estimate.
    What happens in extreme cold?
    The indoor module (furnace or air handler) works with the central heat pump and takes over in extreme cold.
    Furnace, air handler, ducted: what is the difference?
    The furnace or air handler is the indoor module of the central system. A ducted system hides in the ceiling: all you see are small supply grilles.
    Are there grants?
    Depending on the equipment and your situation, assistance programs may apply. AirGreen checks the exact combination before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city. See permits and by-laws, and we check for your address.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Will my current thermostat work?
    Not always: the thermostat has to run the heat pump and the backup heat. We check compatibility during the estimate.
    Central or wall units: which one?
    If the house has ducts in good shape, a central system heats and cools every room at once. Without ducts, wall units or a multi-zone are often simpler. We compare on site.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.
    Going further

    Useful pages for what comes next

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    Tell us about your house. We come and see it for free.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment