Project

Installation of a Fujitsu Aquila XLTH dual-zone heat pump in Terrebonne

In Terrebonne, AirGreen installs a Fujitsu Aquila XLTH R32 dual-zone heat pump on a sturdy wall bracket, above the snow and landscaping, with protected lines and clear access.

By AirGreen Climatisation & Chauffage Admin16 min read
Installation of a Fujitsu Aquila XLTH dual-zone heat pump in Terrebonne
Installation of a Fujitsu Aquila XLTH dual-zone heat pump in Terrebonne
Generic diagram: wall-mounted heat pump, indoor and outdoor units

In summer, the outdoor unit rejects the house's heat outside.

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. Mounted level on a wall plate, high enough for the air to reach the whole room, with enough space around it to slide the filters out easily.

  2. The refrigerant lines, the communication cable and the drain go through the wall in a single opening, sealed against water, cold air and insects.

  3. Two insulated copper pipes connect the two units. Outside, a line cover can protect them from sun, knocks and weather.

  4. A shut-off switch near the outdoor unit isolates it safely for service. It must stay accessible at all times.

  5. The compressor and the fan. In heating mode it captures heat from the outdoor air, even in winter, and moves it inside.

  6. On the ground or on the wall, it keeps the unit above accumulated snow. The unit stays clear and defrost water can drain away.

  7. The fan needs to blow freely. Storage, a fence or a wall too close, and efficiency drops while noise goes up.

An outdoor wall-mounted installation that frees up ground space without sacrificing stability

For this Fujitsu Aquila XLTH dual-zone heat pump installation in Terrebonne, our AirGreen team had to work with a narrow side space, a brick wall, a concrete foundation, and well-established landscaping. Plants at the base of the wall limited the ground-level options, while the passage had to remain accessible.

The chosen solution was to install the Fujitsu AIRSTAGE outdoor unit on a metal wall bracket secured to the foundation. This configuration keeps the heat pump above ground level, protects the landscaping, and clears the space around the house.

The photograph shows an especially clean installation: the unit is mounted high enough to remain clear of the snow, the braced supports provide good rigidity, and pads are placed under the unit's feet to limit vibration transmission. The marking R32 as well as the rating A2L are visible on the front panel.

This system serves two indoor zones from a single outdoor unit. The homeowner therefore benefits from heating and cooling adapted to two distinct areas, without having to install two separate compressors around the property.

Why a dual-zone system was the right choice in Terrebonne

A dual-zone heat pump allows two indoor units to be connected to a single outdoor unit. Each zone can be controlled independently with regard to temperature, fan speed, and several comfort settings.

This configuration is advantageous in a home where heating and cooling needs vary from one space to another. A room with extensive glazing can accumulate a great deal of heat in summer, while a north-facing bedroom remains cooler. A basement may also require a different strategy from the ground floor.

A dual-zone system is particularly suitable for the following layouts:

  • a ground floor and a basement;
  • an open area and a bedroom;
  • a main house and an extension;
  • one floor and a family room;
  • two areas separated by a hallway;
  • one room exposed to the sun and another with more shade.

The exterior advantage is also important. A single unit occupies the wall, reducing clutter, the number of visible connections, and the space required around the property.

A wall-mounted support installed on the foundation

The heat pump is attached to a metal support anchored to the concrete section of the foundation. This decision is important because the strength of the support depends directly on the quality of the anchoring surface.

The visible brick above is exterior cladding. It should not automatically be considered a structural element capable of supporting the weight and vibrations of an outdoor unit.

By anchoring the support to a suitable load-bearing surface, we obtain a more rigid installation that is better suited to long-term loads.

Why avoid attaching the unit only to the brick

A residential brick wall may consist of cladding separated from the main structure by an air gap. Attaching a heat pump directly to this cladding, without considering the structure behind it, can lead to:

  • insufficient anchoring;
  • cracks in the mortar;
  • increased vibration transmission;
  • progressive settling;
  • damage to the cladding;
  • instability during operating cycles.

The type of anchoring must therefore be chosen according to the actual composition of the wall. In this installation, the concrete section provided a better-suited base for the metal support.

A triangulated structure to withstand weight and vibrations

The support visible in the photo uses a triangulated geometry. The horizontal arms hold the heat pump, while the diagonal braces transfer the load to the wall-mounted uprights.

This shape is commonly used because it limits bending and improves stability.

An outdoor unit is subjected to several types of loads:

  • its own weight;
  • compressor vibrations;
  • fan movement;
  • variations caused by starting and modulation;
  • wind;
  • snow or ice that may accumulate around it;
  • maintenance work.

A support that is too light may vibrate or deform over time. A properly sized structure keeps the unit level and reduces unwanted movement.

The pads beneath the heat pump’s feet

Pads are visible between the unit’s feet and the support arms. They help isolate some of the mechanical vibrations.

Even when a heat pump is considered quiet, the compressor and fan produce slight movements. If these vibrations are transmitted directly to the bracket and then to the foundation, they can become noticeable indoors.

Vibration management depends on several factors:

  • the rigidity of the bracket;
  • the type of wall;
  • the quality of the anchors;
  • the location in relation to occupied rooms;
  • the leveling of the unit;
  • the pads used;
  • the tightening of the fasteners.

The goal is not to make the unit completely immobile, but to prevent normal vibration from being amplified by the building's structure.

A useful height for Terrebonne winters

The outdoor unit is installed well above the ground. This height protects the unit from several common winter problems.

Reducing the risk of snow obstruction

In Terrebonne and on the North Shore, snow accumulation can quickly reach the lower part of a heat pump installed too close to the ground.

Air passes through the coil located on the sides and rear of the unit. If snow blocks part of this surface, airflow decreases.

Possible consequences include:

  • a reduction in heating capacity;
  • more frequent defrost cycles;
  • increased energy consumption;
  • extended operation;
  • greater ice accumulation;
  • a reduction in indoor comfort.

By installing the unit on a wall bracket, we create clearance that helps the coil remain accessible to air even when snow accumulates near the house.

Allowing defrost water to drain

In heating mode, the outdoor coil may accumulate frost. The heat pump then initiates a defrost cycle to melt this layer.

The water produced must be able to drain beneath the unit. If the machine is installed too close to the ground or a slab, this water may freeze directly against the chassis.

The height of the bracket provides more space for drainage and delays the formation of an ice block beneath the unit.

However, you must plan where this water will flow. It must not create a slippery area in a walkway or accumulate against the foundation.

Protecting the landscaping

Plants are visible directly beneath and near the installation. The wall bracket made it possible to avoid installing a slab or base occupying a large amount of ground space.

This solution reduces the impact on the landscaping, but it still requires certain precautions.

Plants must not grow into the coil or block the side openings. They must remain sufficiently low and far away to preserve airflow.

Seasonal maintenance may be necessary to:

  • trim leaves that are too close;
  • remove debris;
  • prevent stems from touching the fan;
  • maintain access to the service panel;
  • monitor moisture around the foundation.

The plants visible in the photograph are still sufficiently low, but their growth must be controlled over the seasons.

Adequate clearance in front of the fan

The heat pump's large front fan is oriented toward an open space. This arrangement allows the discharged air to disperse without immediately hitting a wall or obstacle.

Insufficient clearance can create recirculation. The discharged air then returns toward the coil, reducing the quality of heat exchange.

Excessive recirculation can cause:

  • a loss of efficiency;
  • reduced capacity;
  • longer cycles;
  • increased noise;
  • less stable operation;
  • increased compressor wear.

The front grille must also remain accessible for inspection and cleaning.

The vertical routing of the lines

The photo shows a vertical line-set cover installed above the unit. This type of finish protects the refrigerant lines and wiring while giving the installation a neat appearance.

In a dual-zone system, the outdoor unit must be connected to two indoor units. Depending on the route selected, the lines may run up the wall before branching off or connecting to the different areas.

The line-set cover protects:

  • the copper pipes;
  • the insulation;
  • the communication cable;
  • electrical conductors;
  • certain connections depending on the configuration.

It also helps limit exposure to ultraviolet rays, rain, and accidental impacts.

The importance of continuous insulation

The refrigerant lines must be properly insulated. A break in the insulation can cause condensation and a loss of efficiency.

Outdoors, the joints must be protected against:

  • water;
  • UV rays;
  • freezing;
  • temperature fluctuations;
  • insects;
  • mechanical damage.

A clean finish is therefore not merely aesthetic. It directly protects the quality of the system.

R32 refrigerant and the A2L classification

The marking R32 is clearly visible on the unit. This refrigerant is used in several new-generation heat pumps.

Its A2L classification means that it has low flammability. When installed according to the prescribed procedures, it can be used safely, but it requires suitable tools and methods.

The installation must take into account:

  • the manufacturer's requirements;
  • the compatible tools;
  • the leak test;
  • the vacuuming;
  • the amount of refrigerant;
  • pipe dimensions;
  • handling practices;
  • of the ventilation of the spaces concerned.

Technicians must understand the characteristics of R32 and not automatically apply the same methods used for an older system using a different refrigerant.

Fujitsu Aquila XLTH combination options

Fujitsu’s H Series documentation presents outdoor units rated at 18,000, 24,000, 36,000, and 45,000 BTU/h. Depending on the model, they can power two to five indoor units.

For an 18,000 BTU/h outdoor unit intended for two zones, Fujitsu permits several indoor-unit combinations, including:

  • 7,000 + 7,000 BTU/h;
  • 7,000 + 9,000 BTU/h;
  • 7,000 + 12,000 BTU/h;
  • 7,000 + 15,000 BTU/h;
  • 9,000 + 9,000 BTU/h;
  • 9,000 + 12,000 BTU/h;
  • 9,000 + 15,000 BTU/h;
  • 12,000 + 12,000 BTU/h.

The tables can confirm whether a combination is permitted, but they do not replace a load calculation. Fujitsu recommends using its Design Simulator software to select H Series AIRSTAGE equipment.

The photographed rating plate is not clear enough to confirm this unit’s exact capacity with certainty. It is therefore best not to infer the number of BTUs solely from its external size.

A dual-zone heat pump designed for personalized comfort

Each zone has its own setting

The two indoor units can be controlled separately. One room can be set to a different temperature from the other, depending on occupancy and the desired comfort level.

This control is useful when:

  • a zone is used only in the evening;
  • a bedroom must remain cooler;
  • a room receives more sunlight;
  • a space is rarely occupied;
  • the two floors respond differently.

Zoning makes it easier to adapt operation to the building’s daily routines.

One important limitation: the mode is shared

A multi-zone system can heat or cool, but it generally cannot do both at the same time.

This means that one zone cannot request heating while the second simultaneously requests cooling.

The settings may differ, but the units must remain compatible with the selected mode.

This characteristic must be considered when the two spaces have very different exposures. Proper zone selection reduces conflict situations.

The connected capacity is not the simultaneous capacity

Fujitsu states that a multi-zone system can accept a connected capacity of up to 130 %, depending on the permitted configurations.

This does not mean that the outdoor unit will automatically provide the full sum of the rated BTUs of all the indoor units when they operate simultaneously.

When both zones require high capacity, the available output is distributed according to the outdoor unit’s limits.

Sizing must therefore take into account:

  • the area of each zone;
  • insulation;
  • windows;
  • sun exposure;
  • air infiltration;
  • the ceiling height;
  • the outdoor temperature;
  • the simultaneous use of the rooms;
  • the actual low-temperature capacity.

Heating down to -26 °C for cold-climate versions

The Aquila series documentation indicates that CTEB versions designed for cold climates can operate in heating mode down to -26 °C.

This feature meets the winter conditions in Terrebonne. However, it is important to distinguish between the minimum operating temperature and the available capacity.

As with any heat pump, heat output may vary as the outdoor temperature decreases.

We must therefore check:

  • low-temperature capacity;
  • the home’s heat losses;
  • the presence of a backup system;
  • the insulation level;
  • the design temperature;
  • the actual needs of both zones.

A heat pump can significantly reduce the use of traditional electric heating, but the choice must be based on technical data and not solely on a displayed minimum temperature.

The technical steps that are not visible in the photo

The quality of an HVAC installation largely depends on steps that are invisible once the work is complete.

Leak testing

Each connection must be checked to confirm that it is not leaking refrigerant.

A small leak may take several months to cause a noticeable loss of performance.

Evacuation

The circuit must be evacuated to remove air and moisture. Insufficient evacuation can contaminate the oil and damage the compressor.

Calculating the additional charge

Depending on the total piping length, a precise amount of refrigerant may need to be added.

This quantity must be calculated according to the model’s instructions.

Testing both zones

We check the operation of each indoor unit, communication with the outdoor unit, heating, cooling, and drainage.

Mistakes to avoid when installing a wall-mounted unit

Attaching the bracket to non-load-bearing siding

The cladding brick must not be considered a sufficient structure without verification.

Installing the unit too low

Snow, plants, and defrost water may block the unit.

Neglecting vibrations

A rigid support without adequate insulation can transmit a humming noise indoors.

Allowing vegetation to overgrow the coil

Leaves and stems reduce airflow and trap debris.

Blocking the service panel

The unit must remain accessible for maintenance and repairs.

Choosing BTUs based solely on floor area

Glazing, insulation, floor level, and exposure significantly affect requirements.

Choosing two large indoor units without analyzing the outdoor unit’s capacity

Connected capacity does not guarantee equivalent simultaneous output.

Recommended maintenance for this installation

An outdoor wall-mounted heat pump should be inspected periodically.

Maintenance includes, among other things:

  • cleaning the coil;
  • removing leaves and debris;
  • trimming the plants;
  • checking the support;
  • checking the fasteners;
  • inspecting the pads;
  • examining the line-set cover;
  • checking the insulation;
  • cleaning the indoor filters;
  • drain inspection.

During winter, keep the area around the unit clear without striking the coil with a shovel.

Ice should not be removed with a sharp tool or an improvised heat source.

An AirGreen installation adapted to Terrebonne

This Fujitsu Aquila XLTH dual-zone heat pump installation in Terrebonne shows that a wall-mounted support can be an excellent solution when ground space is limited or already landscaped.

The unit is secured to a triangular structure anchored in the foundation. It remains clear of snow, plants, and defrost water. Pads help control vibrations, while the vertical line-set cover protects the connections and improves the finish.

The large front fan has sufficient clearance, and the service panels remain accessible.

At AirGreen, we install dual-zone heat pumps, multi-zone systems, and complete heating and air conditioning solutions in Terrebonne, Montréal, Laval, Longueuil, the North Shore, and the South Shore.

We analyze the wall structure, snow height, vegetation, piping route, the needs of each zone, and electrical capacity before determining the best configuration.

A quality heat pump must be paired with a sturdy support, precise sizing, and complete commissioning. This attention to detail enables the Fujitsu system to provide reliable operation, convenient access for maintenance, and comfort suited to both zones of the building.

The steps

How it goes, from the first call to the end

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.

  1. The on-site estimateWe look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
  2. The quoteModel, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
  3. Getting readyFloors and furniture protected, wall plate position marked level, wall opening located.
  4. The wall openingA single opening, with the slope the drain needs to flow outside.
  5. The outdoor unitSet on a stand raised above the snow, with the clearances the manufacturer requires.
  6. Lines, cable and drainConnected, insulated and protected. The opening is then sealed against water, cold air and insects.
  7. The electrical workA dedicated circuit and an accessible disconnect near the outdoor unit.
  8. Tests and start-upLeak test, vacuum, then start-up and a check of heating and cooling.
  9. The walkthroughRemote, modes, filters: we show you the essentials before we leave.
Your numbers

And at your place?

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Size checkYour baseboards, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Clean the indoor unit's filters.
    • Clear leaves and debris left on the outdoor unit by winter.
    • Test cooling before the first hot days.
    And at your place?

    Which type of equipment for your project?

    Pick what looks like your need.

    Mistakes avoided

    Four mistakes we do not make

    Flip each card to see what we do instead.

    Frequently asked questions

    What people ask us about this kind of work

    12 questions
    Does a wall-mounted heat pump heat in winter?
    Yes, it heats and cools. Its capacity drops in very cold weather; the operating range depends on the model and is listed on its spec sheet.
    Wall-mounted or multi-zone: how do I choose?
    One wall head and one condenser outside: the direct solution for a room or an open area. For two to five rooms, a multi-zone puts one head in each room on a single condenser.
    Where does the outdoor unit go?
    Where it stays above the snow, clear and accessible, away from walkways. We decide it with you during the estimate.
    Are there grants?
    Depending on the model and your situation, assistance programs may apply, including Hydro-Québec's LogisVert. AirGreen checks the model number before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city: location, distances, noise. See permits and by-laws, and we check for your address.
    How cold can it heat?
    It depends on the model. According to Hydro-Québec, newer models work down to a temperature between −15 °C and −25 °C, and some cold-climate models are certified lower. The minimum temperature is on each unit's spec sheet.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Is it noisy?
    The sound level depends on the model and is listed in decibels on each unit's spec sheet. Location matters too: when possible, we avoid putting the outdoor unit under a bedroom window.
    The outdoor unit is covered in ice: is that normal?
    Some frost is: the unit runs defrost cycles. Never hit the ice. If the unit stays iced up or stops heating, call us.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.
    Going further

    Useful pages for what comes next

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    Tell us about your house. We come and see it for free.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment