Installation of a 5-ton GREE UNIX R32 central heat pump in Marieville, in the Rouville RCM
Six feet between two concrete walls: in Marieville, the site geometry mattered more than the SEER2. Installation of a 5-ton GREE UNIX R32 central heat pump — air recirculation, sound amplification, permanent shade, and a freestanding support with adjustable feet.

Take a tour of the installation
Each number is a point we check on site. Switch between summer and winter to watch air and heat move.
In summer, the outdoor unit rejects the house's heat outside.
Generic illustration of this type of installation, not a survey of this job site. Tap a number.
It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.
The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.
A shut-off switch near the outdoor unit isolates it safely for service.
Sitting on the indoor module, it moves heat between the house air and the refrigerant.
Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.
Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.
It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.
It runs the heat pump and the backup heat. It must be compatible with the installed system.
A six-foot corridor between two concrete walls: what site geometry imposes on a central heat pump
In the photo from this Marieville project, in the Rouville RCM, the unit is installed in a narrow passage between two concrete block walls. The ground is a slab, the walls are stained and moss-covered, and direct sunlight clearly never reaches this spot.
This is the type of location that most quotes cover in a single line: “installation of the outdoor unit at the back of the yard.” Yet, on a site like this, the site's geometry has a greater effect on actual performance than three-tenths of a SEER 2 point.
Two phenomena are triggered as soon as a central heat pump is placed between two closely spaced hard surfaces: air recirculation and sound amplification. We address them before anchoring the support, not after the neighbor's first call.
Air recirculation: the efficiency that disappears without a trace
What happens
The outdoor unit in the UNIX R32 series discharges air through its front, via its two fans. In an open yard, this air moves away and dissipates. In a six-foot corridor, it hits the wall opposite and returns toward the unit.
The consequences are not the same depending on the season:
- In cooling mode, the unit expels hot air. If it draws that air back in, the temperature seen by the outdoor coil rises, condensing pressure increases, capacity drops, and consumption rises. The unit operates, but as if it were 40 °C outside when it is actually 28 °C.
- In heating mode, the opposite happens: the unit expels cold air and draws it back in. The coil sees air that is colder than the actual ambient air, frost buildup accelerates, and defrost cycles multiply just when the home needs heat the most.
In both cases, nothing breaks. There is no error code or unusual noise. The customer simply realizes, two years later, that their bill has not decreased as much as promised.
What we do
- Orient the discharge along the corridor's most open axis, never perpendicular to the nearest wall.
- Measure the manufacturer's clearances with a tape measure, giving priority to the front clearance.
- Raise the unit. In a confined corridor, air stagnates near the ground. A unit mounted higher up operates in a better-renewed layer of air.
- Check what closes off the corridor at both ends. A tarp, temporary shelter, or shed added later turns a ventilated passageway into a closed box.
The noise: 62 dB(A), but measured where
The outdoor unit's technical specifications state a sound pressure level of 62 dB(A). This value is established under standardized conditions, at a given distance, without a nearby reflective surface.
Place the same unit between two parallel concrete walls, and the perceived result changes. Each hard surface reflects sound energy rather than absorbing it, and the reflections add up. The difference amounts to a few decibels—around three to six depending on the configuration—which translates into a clearly perceptible difference to the ear.
What we check at a site like Marieville:
- The distance from nearby openings, particularly bedroom windows, on either side of the corridor.
- Structure-borne transmission. The unit rests on a freestanding support with adjustable feet and controlled tightening: a chassis rigidly bolted to a slab that touches a shared wall transmits compressor vibrations into the neighboring building.
- Municipal noise regulations. They vary from one municipality to another in Montérégie, and they apply at night, when the heat pump is also operating.
One reassuring point about this unit: DC Inverter technology with a two-stage, twin-cylinder compressor allows it to operate at reduced speed for most of the year. A modulating unit remains much quieter than a fixed-speed unit that starts and stops all night.
Permanent shade: an advantage in summer, a constraint in winter
The corridor receives no direct sunlight. This is visible on the walls, where moss has taken hold.
In summer, it is a real advantage. A condenser operating in the shade sees cooler ambient air than a unit exposed to full southern sun on a concrete slab. Cooling efficiency is therefore improved, provided recirculation is controlled.
In winter, this is a constraint. A location that never sees the sun does not dry out. Defrost water — and a 5-ton heat pump produces plenty of it — does not evaporate or melt between cycles. It accumulates as ice beneath the unit.
This is the main reason for the freestanding support with adjustable feet visible in the photo, rather than installing it directly on the slab. The unit is well above the area where ice accumulates, water can fall freely, and the underside remains accessible. The adjustable feet also compensate for the slab's slope and level the unit perfectly — a requirement for defrost water to drain where it is supposed to.
The unit and selected configuration
GREE UNIX R32, 5 tons, with cased coil
The building already had an air handler and a ductwork system in good condition. We therefore chose the cased coil configuration, which retains the existing blower and adds the heat pump coil to the plenum.
- Indoor unit: GCAC60H/NhA — Outdoor unit: GUD60W2/NhE-D(U)
- AHRI code : 216765694
- Cooling capacity : 52,000 BTU/h (15 600 – 57 200)
- Heating capacity : 53,000 BTU/h (16 200 – 59 400)
- SEER 2: 15.2 — EER 2: 9.5 — HSPF 2: 8.5 — COP at 8 °C: 3.10
- Airflow: 1,200 cfm
- Dehumidification capacity: 8.15 L/h, or approximately 17 pints per hour
- Condensate drain: 3/4 in
- Operating temperatures: heating from -30 °C to 24 °C; cooling from -15 °C to 54 °C
- R32 refrigerant, 4.6 kg charge — lines: 3/4 in suction, 3/8 in liquid
- Piping: standard length 24.6 ft, maximum 98.4 ft, maximum elevation 49.2 ft
- Electrical: 208-230 V / 60 Hz / single-phase — outdoor MCA 39.9 A, MOP 45 A
- Coil: 24 1/2 x 28 1/2 x 21 1/4 in, 110 lb — Outdoor unit: 35 25/64 x 49 19/32 x 13 25/64 in, 241.4 lb
- Integrated refrigerant leak detector, compatible with 24 VAC thermostat and RS485
- Ultra Heat: 100% heating capacity at -20 °C, stable operation at -30 °C
The most interesting figure on the specification sheet: 15,600 BTU
On a unit with a nominal capacity of 52,000 BTU/h, the 15,600 BTU/h modulation floor is what truly distinguishes this configuration.
That is less than one-third of the nominal capacity. In practical terms, the unit can run continuously at very low output on mild days in May and September—exactly the periods when a fixed-speed system would simply start and stop without ever dehumidifying.
In a shaded corridor where moisture does not dissipate naturally, the ability to run for long periods at low output matters more than peak efficiency.
Condensate, not to be underestimated
A coil added to an existing unit creates water production where there had never been any: up to 17 pints per hour at peak, discharged through a 3/4-inch drain.
Our requirements: a properly sized and primed trap at commissioning, a safety pan with a float switch when the coil is above a finished space, and accessible cleanout plugs, shown to the customer. This is the most common cause of water damage after adding a coil.
A2L refrigerant
R32 is classified as A2L, mildly flammable. All GREE Canada indoor units—from cased coils to air handler cabinets—are equipped with a refrigerant leak detector. We verify its position and test the shutdown logic during commissioning.
Mistakes to avoid on a confined site
- Treat a corridor like an open yard. The manufacturer's clearances are a minimum, not a target.
- Point the discharge toward the nearest wall because it is more convenient for the piping.
- Place the unit directly on the slab in a location that never dries out.
- Ignore nearby windows and municipal noise regulations.
- Close off the corridor afterward with a shelter, tarp, or shed. What was ventilated will no longer be.
- Forget about service access. A technician must be able to open the side panel and maneuver a cylinder through this passage in February.
Rebates
The Chauffez vert program ended on March 31, 2026. Hydro-Québec's LogisVert program remains the reference assistance program for a central heat pump: eligibility is based on the exact indoor/outdoor combination installed and its AHRI code — here, 216765694 —, on a contractor holding an RBQ licence and registered with the program, and on an application submitted within the prescribed period following invoicing. We validate the combination before signing, never afterward.
Maintenance in a narrow passage
Two points are added to the annual HVAC maintenance on a site like this: clearing the corridor, which has a strong tendency to fill with stored materials over the seasons, and inspecting the coil, which collects dust and leaves trapped between the two walls. Everything else — pressures, superheat, subcooling, airflow, tightening, indoor filters, and the condition of the support — remains part of the usual program.
Why homeowners in the Rouville RCM call us
At AirGreen, we install central heat pumps, wall-mounted heat pumps, mini split systems, air conditioners, and air exchangers in Montreal, Laval, Longueuil, on the North Shore, on the South Shore, and in the municipalities of the Richelieu Valley — Marieville, Richelieu, Chambly, Rougemont, Sainte-Angèle-de-Monnoir, and Saint-Mathias-sur-Richelieu.
A difficult location does not make an installation impossible. It makes preliminary work essential: measuring clearances, directing the discharge, choosing the right support, and warning the customer about what they must not add around their unit in the years to come.
If you need to install a central heat pump in a narrow yard, a shared driveway, or a service shaft, call us. We travel to your location, take measurements, calculate the load, and provide you with a clear proposal including actual performance ratings, the AHRI code, and eligibility for rebates already validated.
AirGreen — Air Conditioning & Heating. RBQ 5645-9605-01. (514) 316-2973
The big day, step by step
The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.
We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
The equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
Access protected, old unit disconnected and removed when it is being replaced.
Electric furnace or air handler, with its coil, connected to the supply and return ducts.
On a level base, raised above the snow, with free space all around.
Insulated, they enter through a sealed opening and run to the indoor coil.
Dedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
Leak test, vacuum, start-up, airflow check and a test of both modes.
Filter, thermostat, backup heat in extreme cold: what to know before winter.
- The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
- The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
- Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
- The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
- The outdoor unitOn a level base, raised above the snow, with free space all around.
- The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
- Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
- Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
- The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
What would it look like at your place?
Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.
Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.
Four mistakes we do not make
Flip each card to see what we do instead.
Your own project, step by step
What to do, season by season
Three habits per season for this unit. They take a few minutes and prevent many calls.
- Check the indoor module's filter.
- Clear winter debris from the outdoor unit.
- Test cooling before the heat arrives.
- Check the filter more often in peak season.
- Keep registers and returns clear.
- Watch condensate drainage near the coil.
- Change or clean the filter.
- Test heating and backup heat before the cold.
- Book periodic maintenance.
- Clear snow around the outdoor unit.
- Store nothing in front of the indoor module.
- Note any unusual noise or smell and call us.
Is your home ready?
Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.
Four statements: true or false?
It all comes down to details you have just seen.
1. A central heat pump uses the house's ducts.
It connects to the existing ducts to heat and cool everywhere.
2. In extreme cold, electric backup heat can take over.
The indoor module (furnace or air handler) works with the heat pump and takes over in extreme cold.
3. The filter only gets changed when the unit breaks down.
A dirty filter cuts airflow. It gets checked regularly.
4. You can reuse the old unit's size without checking.
The house may have changed: insulation, windows, added rooms. Capacity is confirmed on site.
0 / 4 right answers
What people ask us about this kind of work
Can I keep my current ducts?
What happens in extreme cold?
Furnace, air handler, ducted: what is the difference?
Are there grants?
Do I need a permit?
How much can I save?
How is the LogisVert assistance calculated?
Will my current thermostat work?
Central or wall units: which one?
Does AirGreen hold the required licences?
Is the estimate free?
No question matches. Write to us: we answer.
More jobs to see, near you
By town, by equipment or by region: browse more than 4,700 published projects.
Each dot: a town where AirGreen has published projects. The glowing dot: this job.
Every house has its constraints. We see them before we install.
The on-site estimate is free and the quote follows within 24 hours.
Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).
