GREE UNIX R32 central heat pump. The only GREE 3-ton central system rated 32,600 BTU/h at −8.3 °C. See what that changes on LogisVert, tonnage by tonnage.
4 UNIX R32 systems, from 2 to 5 tons. GREE Canada’s UNIX R32 pairs a GUD outdoor unit with a G air handler. Hydro-Québec pays on the heat certified at −8 °C, and it is at 3 tons that the UNIX R32 stands apart from the other GREE central systems we offer.
- 4UNIX R32 systems on this page
- 2GUD outdoor units
- 2–5tons
- 4amounts confirmed by the Oct. 27, 2026 LogisVert list
Why this 3-ton earns $528 more, and what the other sizes are worth.
To set the amount, Hydro-Québec uses a single figure from the certificate: the ENERGY STAR heat at −8 °C. Pick a tonnage to see the math.
Pick a tonnage.
The list amount follows a simple rule: $120 per 1,000 BTU/h of ENERGY STAR heat at −8 °C, for a cold-climate system. The bars compare the UNIX R32 with the FXU and GUD + E systems of the same tonnage.
Worked out from Hydro-Québec’s list dated Oct. 27, 2026 and the ENERGY STAR records; indicative amounts, capped at the pre-tax cost, to be claimed within nine months of installation.
GREE Canada’s brochure and the certificates, side by side.
Brochure 062025 and the NEEP and ENERGY STAR records cover the same four AHRI numbers. They agree on the heat at 8.3 °C, not always on efficiency. This page shows the certificates.
| UNIX R32 | 2 tons | 3 tons | 4 tons | 5 tons |
|---|---|---|---|---|
| AHRI certificate | 217120759 | 217120760 | 217120761 | 217120762 |
| Heat at 8.3 °C, certificate and brochure | 25,000 | 34,000 | 48,000 | 54,000 |
| SEER2 · certificate | 18 | 18.2 | 19 | 18.2 |
| SEER2 · brochure | 18.0 | 18.0 | 19.0 | 18.5 |
| EER2 · certificate | 12 | 11.2 | 11.7 | 11.2 |
| HSPF2 · certificate | 10 | 10 | 10 | 10 |
| HSPF2 · brochure | 10.0 | 10.0 | 10.0 | 10.5 |
| COP at 8.3 °C · certificate | 3.59 | 3.2 | 3.36 | 3.36 |
| Heat kept at −15 °C · certificate | 96% | 100% | 100% | 100% |
Certificates: NEEP and ENERGY STAR, read Oct. 26, 2026. Brochure: GREE Canada, document 062025. In bold, the certified values that differ from the brochure. For EER2 and COP too, the brochure prints other values: we show only the certificates, which the LogisVert amounts follow.
What GREE Canada prints, what the certificates confirm, and who installs it.
GREE Canada documents the UNIX R32: GUD outdoor unit and G air handler. AirGreen calculates the tonnage, checks the air handler’s room and installs the system.
What GREE brings
- Two outdoor unitsGUD36W2 for the 24,000 and 36,000, GUD60W2 for the 48,000 and 60,000, per GREE Canada.
- A detector on every air handlerEvery GREE Canada indoor unit carries a refrigerant leak detection sensor.
- Valves and terminals outsideService valves and electrical terminals reachable from outside the GUD outdoor unit, for easier field installation, per GREE Canada.
What AirGreen brings
- GREE Elite dealerGREE training completed, priority access to original parts.
- Free estimateWe measure the G air handler’s room, the line-set route and the state of your ducts.
- RBQ 5645-9605-01Licences 15.8, 15.10 and 16. Gas and oil work is done by a licensed partner.
The result: a UNIX R32 at the calculated tonnage, with its certificate’s LogisVert amount, installed by a GREE Elite dealer.
All 4 UNIX R32 systems, right below.
Each product sheet gives the AHRI number (217120759 to 217120762), the GUD outdoor unit and the G air handler. Their LogisVert amounts match the Oct. 27, 2026 list.
Cold, the air handler’s room, sound: the UNIX R32 size by size.
Three tools built from the certificates, GREE Canada’s brochure and GREE’s manual for the G air handlers.
Certified heat, from mild to deep cold.
Pick a size. At −8.3 °C and −15 °C we show the certificates’ ratings, including the −8.3 °C one Hydro-Québec uses; at −30 °C, the maximum capacity NEEP publishes.
Is the G air handler’s room big enough?
R-32 is an A2L refrigerant: GREE’s manual for the G air handlers sets a minimum room area by charge. Enter the area and the size.
Outdoors, GREE Canada lists 62 dB(A) for the 60,000 UNIX R32.
Outdoor sound pressure per GREE Canada: 60, 61, 62 and 62 dB(A), where GREE Comfort and Dettson print 63 for their 60,000. No measuring distance is published.
GREE Canada’s figures for your electrician and installer.
Electrical
Rated system input: 3.2, 4.6, 6.4 and 6.7 kW in cooling (14.6, 22.0, 30.0 and 31.0 A); 4.2, 5.6, 6.8 and 7.0 kW in heating (19.2, 25.6, 32.0 and 32.0 A), 24,000 to 60,000. Outdoor circuit: MCA 27.7 A and MOP 30 A (24,000 and 36,000), 39.9 A and 45 A (48,000 and 60,000). Air handler: 4.7 to 7.7 A, MOP 15 A; an optional auxiliary heater changes both values.
GREE Canada 062025Line set
Standard length 7.5 m, 30 m at most, 15 m of rise; suction 3/4 in, liquid 3/8 in. GREE Canada prints no charge per metre; Dettson gives 30 g/m (GUD36W2) and 20 g/m (GUD60W2) for the same outdoor units.
GREE Canada 062025 · Dettson X61067CFootprints
Air handlers from 460 × 1105 × 540 mm (61.5 kg) to 630 × 1320 × 540 mm (90.5 kg). Outdoor units: 990 × 960 × 370 mm (85.0 kg) and 900 × 1260 × 340 mm (109.5 kg).
GREE Canada 062025Air handlers sold with an electric heating element are on the GREE electric furnaces page.
Four facts about the UNIX R32, from GREE Canada and ENERGY STAR. Flip the cards.
Before counting on the amount: the program conditions.
The amounts on the Oct. 27, 2026 list are worked out above: $2,472, $3,912, $4,740 and $5,400, indicative until Hydro-Québec answers. Exclusions for a central system: the GREE central heat pumps page.
What people ask us about the UNIX R32.
Why does the 3-ton UNIX R32 get more LogisVert than the FXU and GUD + E 3-tons?
Are the brochure’s SEER2 and HSPF2 the certified values?
How does the UNIX R32 handle a Montréal winter?
Can I keep my thermostat?
What warranty does GREE Canada give for the UNIX R32?
Can I keep my furnace and pair the UNIX R32 with it?
The UNIX R32 tonnage you need, and the amount that comes with it: we do the math at your home.
Free estimate at home. Montréal, Laval, Longueuil, South Shore and North Shore.
- Product sheets on airgreen.ca (metafields), read Oct. 14, 2026
- NEEP cold-climate heat pump list, records by AHRI number, read Oct. 14 and 15, 2026 and checked again Oct. 26 and 27, 2026
- ENERGY STAR, “Certified Air-Source Heat Pumps” (data.energystar.gov, dataset w7cv-9xjt, updated Oct. 25, 2026, read Oct. 26 and 27, 2026)
- Hydro-Québec, LogisVert eligible heat pump list (owner, existing home), file proprietaire-habitation-existante-20261027 downloaded Oct. 26, 2026, checked again Oct. 27, 2026 against the next file, proprietaire-habitation-existante-20261028: same amounts for every AHRI number on our product sheets
- Hydro-Québec, LogisVert program, residential participant guide, version 1.10, Sept. 15, 2026, still online Oct. 26, 2026
- National Building Code of Canada 2020, Appendix C, Table C-2 (Montréal, City Hall)
- Québec.ca, “Mesure du bruit” (in French), examples of noise sources (updated June 16, 2022), read Oct. 14, 2026
- GREE Canada, “UNIX R32 central system” brochure, document No. 062025, English and French versions
- GREE Canada, UNIX R32 product page, read Oct. 26, 2026 (no warranty term published)
- GREE manual for the GUD…AH2/G-D(U) air handlers, document X40273A (file posted by Dettson), read Oct. 26, 2026
- Dettson, Flexx R32 sheet, document X61067C (charge per metre of the GUD36W2 and GUD60W2)
Capacities and amounts: indicative, to be confirmed in the quote. Tool calculations: AirGreen, from the published values above. Page updated Oct. 27, 2026; NEEP records, ENERGY STAR and the LogisVert list checked again that day.