GREE VRF systems. One outdoor unit, two to seven indoor units, line runs up to 120 m. For a large home or a small commercial space: what GREE’s documents allow, and where they disagree.
10 Mini-GMV listings on 2 outdoor units, the GMV-36WL/B-T(U) and the GMV-48WL/B-T(U). The indoor units branch off one piping network, through Y-branches or branch headers, and the outdoor unit modulates its output to the demand. GREE Comfort, in the United States, has archived these two models; GREE Canada now sells another Mini-GMV. Supply and the Canadian warranty are therefore confirmed at the quote.
- 10listings on this page
- 2outdoor units, 36,000 and 48,000 BTU/h
- 7,500–24,000BTU/h, wall units on our product sheets
- 208/230 Vsingle phase, one circuit per outdoor unit
How many units, how much total capacity? Two GREE documents, two answers.
On a VRF, two rules decide: the number of indoor units, and the sum of their capacity codes compared with the outdoor unit. The 2021 submittal and the 2017 sales guide do not set the same limits: the checker shows both.
Your combination, against both documents
Pick the outdoor unit, then enter the number of indoor units and the sum of their capacity codes. Each line names the GREE document that sets the limit.
Cooling capacity and heating output of the wall units on our product sheets, per the 2017 sales guide’s table. The guide restricts the Ultra Heat GMV5 to the indoor-unit types it lists; these wall units are among them.
Four GREE sources, several discrepancies, and an archived line.
For these two outdoor units, we found documents only at GREE Comfort, in the United States. When two of its documents differ, this page shows both, with their dates.
What gets confirmed at the quote
Supply of these two models and the warranty that applies in Canada, in writing, with the quote. We found no Canadian GREE document for this line.
One outdoor unit for the whole building, a local team to lay it out.
GREE designs the Mini-GMV and its wall units. AirGreen designs the branch network, checks GREE’s limits and installs the system.
What GREE brings
- An inverter compressorRotary, in a cabinet with two axial fans, per the 2021 submittals.
- Five wall-unit sizesFrom 7,500 to 24,000 BTU/h, all on GREE’s list of allowed indoor units.
- A heating range down to −30 °CPer the 2021 submittals, for both outdoor units.
What AirGreen brings
- GREE Elite dealerGREE training completed, priority access to original parts.
- Free estimateWe note the rooms, the distances and the heights, then lay out the piping before quoting.
- 5 GREE VRF installationsEach one has its own article and photos on our installations blog (count as of Oct. 14, 2026).
- RBQ 5645-9605-01Licences 15.8, 15.10 and 16. Gas and oil work is done by a licensed partner.
The result: one GREE unit outside, a wall unit in each room, on piping laid out within GREE’s limits.
The 10 Mini-GMV combinations, sheet by sheet.
Each product sheet is one outdoor unit with a number of wall units. The checker at the top of the page applies GREE’s limits.
One building, one piping network: distances and sound.
The length and height limits of the sales guide, and the outdoor unit’s sound per the submittals.
Your distances, against GREE’s limits
Enter your building’s lengths and heights. The limits come from the 2017 sales guide; the note says where the other documents differ.
One unit for the whole building: how loud outside?
The 2021 submittals give a sound pressure of 56 dB(A) for the 36,000 and 57 dB(A) for the 48,000.
Mini-GMV: circuit, refrigerant, cabinet.
The circuit
208/230 V, 60 Hz, single phase: MCA 37 A, maximum overcurrent protection 50 A, compressor rated load amps 28 A. Same values on the 36,000 and the 48,000.
2021 submittalsThe refrigerant
6.5 kg (229.3 oz) of R410A from the factory in both units. Connections of 5/8 in (gas) and 3/8 in (liquid), on one branched piping network.
2017 sales guide · 2021 submittalsThe cabinet
53 × 35-3/8 × 13-3/8 in (H × W × D), 296.4 lb net, and 3,531 CFM of condenser airflow.
2021 submittalsThe printed ratings
Ducted / non-ducted: SEER 16.5 / 20.5, EER 11.3 / 13 and HSPF 10.3 / 11.7 for the 36,000; SEER 16.5 / 20, EER 9.5 / 12.5 and HSPF 10.2 / 11 for the 48,000. No NEEP or ENERGY STAR record carries them today.
2021 submittalsWhere the documents differ
Outdoor unit below the indoor units: 40 m (131 ft) in the 2017 guide, 134 ft in the 2023 catalogue for the 36,000. The “Distances” tool applies 40 m.
2017 sales guide · 2023 catalogueSix Mini-GMV details, taken from GREE’s documents.
Neither LogisVert nor the federal grant for these two models.
For a LogisVert project, see the GREE central and GREE multi-zone pages instead.
Units, distances, grants: your questions on the GREE VRF.
How many indoor units can one outdoor unit run?
How much total indoor capacity can be connected?
What distances are allowed?
Is there a grant for this VRF?
Does it heat through a cold snap?
Are these two models still offered in Canada?
A large space, many rooms, one unit outside? Let’s talk it through on site, plans in hand.
Free estimate at home. Montréal, Laval, Longueuil, South Shore and North Shore.
- Product sheets on airgreen.ca (metafields), read Oct. 14, 2026
- Hydro-Québec, LogisVert eligible heat pump list (owner, existing home), file proprietaire-habitation-existante-20261027 downloaded Oct. 26, 2026, checked again Oct. 27, 2026 against the next file, proprietaire-habitation-existante-20261028: same amounts for every AHRI number on our product sheets
- Hydro-Québec, LogisVert program, residential participant guide, version 1.10, Sept. 15, 2026, still online Oct. 26, 2026
- Natural Resources Canada, Canada Greener Homes Grant (Québec): program closed, applications until Sept. 30, 2025, read Oct. 26, 2026
- Québec.ca, “Mesure du bruit” (in French), examples of noise sources (updated June 16, 2022), read Oct. 14, 2026
- AirGreen GREE page: Elite status and installations, facts checked Oct. 5, 2026; GREE installation count of Oct. 14, 2026
- GREE Comfort (USA), MultiPRO page, “Archived MultiPRO” section: GMV-36WL/B-T(U) and GMV-48WL/B-T(U) documents, read Oct. 26, 2026
- GREE Comfort, GMV-36WL/B-T(U) submittal, 2021
- GREE Comfort, GMV-48WL/B-T(U) submittal, 2021
- GREE Comfort, GMV5 Ultra Heat Mini sales guide, 2017: allowed units, capacity codes, lengths and heights
- GREE Comfort, catalog GREE_CATALOG_03222023: COP of the GMV-36WL/B-T(U) and GMV-48WL/B-T(U) (file attached to the airgreen.ca product sheets)
- NEEP and ENERGY STAR, search for AHRI numbers 8654208 and 8654211 and both models, Oct. 26, 2026: no record
- GREE Canada, online product catalogue (products.json), read Oct. 26, 2026: Ultra Heat GMV6 Mini
Limits, ratings and sound: the GREE Comfort documents above; Canadian supply and warranty are confirmed at the quote. Checker calculations: AirGreen, from those limits. Page updated Oct. 26, 2026.