AirGreenGREE
GREE EliteThe GREE space at AirGreen · VRF systemsGREE Elite dealer: GREE training completed, priority access to original parts.
GREE Elite
Archived U.S. line · supply confirmed at the quote
GREE Mini-GMV · VRF · Updated Oct. 27, 2026

GREE VRF systems. One outdoor unit, two to seven indoor units, line runs up to 120 m. For a large home or a small commercial space: what GREE’s documents allow, and where they disagree.

10 Mini-GMV listings on 2 outdoor units, the GMV-36WL/B-T(U) and the GMV-48WL/B-T(U). The indoor units branch off one piping network, through Y-branches or branch headers, and the outdoor unit modulates its output to the demand. GREE Comfort, in the United States, has archived these two models; GREE Canada now sells another Mini-GMV. Supply and the Canadian warranty are therefore confirmed at the quote.

5 · 7Indoor units at most: 5 on the 36,000 and 7 on the 48,000, per GREE’s submittals (2021). The 2017 sales guide allows 6 on the 48,000.
120 mOf real pipe to the farthest indoor unit, and 300 m of liquid line for the whole system, per GREE’s sales guide (2017).
50 mOf height difference with the outdoor unit above the indoor units, 40 m with it below (2017 sales guide): enough to set it on the roof and serve the floors underneath.
  • 10listings on this page
  • 2outdoor units, 36,000 and 48,000 BTU/h
  • 7,500–24,000BTU/h, wall units on our product sheets
  • 208/230 Vsingle phase, one circuit per outdoor unit
AirGreen × GREEGREE Elite dealerOne outdoor unit, one branched piping network120 m to the farthest indoor unit5 GREE VRF installations, with photosMontréal, Laval, Longueuil, South Shore, North Shore
The combination checker

How many units, how much total capacity? Two GREE documents, two answers.

On a VRF, two rules decide: the number of indoor units, and the sum of their capacity codes compared with the outdoor unit. The 2021 submittal and the 2017 sales guide do not set the same limits: the checker shows both.

Your combination, against both documents

Pick the outdoor unit, then enter the number of indoor units and the sum of their capacity codes. Each line names the GREE document that sets the limit.

7,500GMV-N07G/A3A-D(U) · 8,500 BTU/h heating
9,500GMV-N09G/A3A-D(U) · 10,500 BTU/h heating
12,000GMV-N12G/A3A-D(U) · 13,500 BTU/h heating
18,000GMV-N18G/A3A-D(U) · 20,000 BTU/h heating
24,000GMV-N24G/A3A-D(U) · 25,500 BTU/h heating

Cooling capacity and heating output of the wall units on our product sheets, per the 2017 sales guide’s table. The guide restricts the Ultra Heat GMV5 to the indoor-unit types it lists; these wall units are among them.

What the documents say

Four GREE sources, several discrepancies, and an archived line.

For these two outdoor units, we found documents only at GREE Comfort, in the United States. When two of its documents differ, this page shows both, with their dates.

DocumentWhat it saysFor these two models
SubmittalsGREE Comfort, 2021
Main sources
At most 5 indoor units on the 36,000, 7 on the 48,000; units adding up to 50 to 135% of the outdoor unit; heating from −30 to 27 °C; circuits, sound and ratings.
GMV5 Ultra Heat sales guideGREE Comfort, 2017
Differs
At most 6 units on the 48,000 instead of 7, a sum of 50 to 100% instead of 135%, at least two units; every allowed length and height.
GREE Comfort catalogueGREE Comfort, 2023
Efficiency
The COP of both models at 8.3 °C and −15 °C, ducted and non-ducted.
GREE Canada catalogueRead Oct. 26, 2026
Another Mini-GMV
GREE Canada now sells the Ultra Heat GMV6 Mini, not these two model numbers. This page uses no GMV6 figure.
NEEP, ENERGY STAR, Hydro-QuébecChecked Oct. 26, 2026
No record
AHRI numbers 8654208 and 8654211 are on none of the three lists (LogisVert list dated Oct. 27, 2026).

What gets confirmed at the quote

Supply of these two models and the warranty that applies in Canada, in writing, with the quote. We found no Canadian GREE document for this line.

AirGreen × GREE

One outdoor unit for the whole building, a local team to lay it out.

GREE designs the Mini-GMV and its wall units. AirGreen designs the branch network, checks GREE’s limits and installs the system.

GREE

What GREE brings

  • An inverter compressorRotary, in a cabinet with two axial fans, per the 2021 submittals.
  • Five wall-unit sizesFrom 7,500 to 24,000 BTU/h, all on GREE’s list of allowed indoor units.
  • A heating range down to −30 °CPer the 2021 submittals, for both outdoor units.
AirGreen

What AirGreen brings

  • GREE Elite dealerGREE training completed, priority access to original parts.
  • Free estimateWe note the rooms, the distances and the heights, then lay out the piping before quoting.
  • 5 GREE VRF installationsEach one has its own article and photos on our installations blog (count as of Oct. 14, 2026).
  • RBQ 5645-9605-01Licences 15.8, 15.10 and 16. Gas and oil work is done by a licensed partner.

The result: one GREE unit outside, a wall unit in each room, on piping laid out within GREE’s limits.

The GREE shop

The 10 Mini-GMV combinations, sheet by sheet.

Each product sheet is one outdoor unit with a number of wall units. The checker at the top of the page applies GREE’s limits.

GREE
Know before you buy

One building, one piping network: distances and sound.

The length and height limits of the sales guide, and the outdoor unit’s sound per the submittals.

Your distances, against GREE’s limits

Enter your building’s lengths and heights. The limits come from the 2017 sales guide; the note says where the other documents differ.

Technician’s corner

Mini-GMV: circuit, refrigerant, cabinet.

The circuit

208/230 V, 60 Hz, single phase: MCA 37 A, maximum overcurrent protection 50 A, compressor rated load amps 28 A. Same values on the 36,000 and the 48,000.

2021 submittals

The refrigerant

6.5 kg (229.3 oz) of R410A from the factory in both units. Connections of 5/8 in (gas) and 3/8 in (liquid), on one branched piping network.

2017 sales guide · 2021 submittals

The cabinet

53 × 35-3/8 × 13-3/8 in (H × W × D), 296.4 lb net, and 3,531 CFM of condenser airflow.

2021 submittals

The printed ratings

Ducted / non-ducted: SEER 16.5 / 20.5, EER 11.3 / 13 and HSPF 10.3 / 11.7 for the 36,000; SEER 16.5 / 20, EER 9.5 / 12.5 and HSPF 10.2 / 11 for the 48,000. No NEEP or ENERGY STAR record carries them today.

2021 submittals

Where the documents differ

Outdoor unit below the indoor units: 40 m (131 ft) in the 2017 guide, 134 ft in the 2023 catalogue for the 36,000. The “Distances” tool applies 40 m.

2017 sales guide · 2023 catalogue
Did you know?

Six Mini-GMV details, taken from GREE’s documents.

LogisVert · Hydro-Québec

Neither LogisVert nor the federal grant for these two models.

$0LogisVert: guide v1.10 requires a complete ENERGY STAR certified system, outdoor unit and indoor units. These two models are not certified today.LogisVert guide v1.10
8654208 · 8654211The AHRI numbers on our product sheets: not on NEEP or ENERGY STAR, nor on Hydro-Québec’s list of Oct. 27, 2026.NEEP and ENERGY STAR checked Oct. 26, 2026
ClosedCanada Greener Homes Grant: applications ended Sept. 30, 2025.Natural Resources Canada

For a LogisVert project, see the GREE central and GREE multi-zone pages instead.

Questions

Units, distances, grants: your questions on the GREE VRF.

How many indoor units can one outdoor unit run?
From 2 to 5 on the GMV-36WL/B-T(U). On the GMV-48WL/B-T(U), the 2021 submittal allows 7 and the 2017 sales guide gives 6. Both documents are GREE’s: the checker at the top of the page shows both limits.
How much total indoor capacity can be connected?
You add up the units’ capacity codes; for the wall units on our product sheets, the sales guide’s table gives 7,500 to 24,000 BTU/h of cooling. The 2021 submittals allow 50 to 135% of the outdoor unit, the 2017 sales guide 50 to 100%. On the 36,000, our arithmetic gives 18,000 to 48,600 BTU/h per the submittals, or 18,000 to 36,000 per the guide.
What distances are allowed?
Per the 2017 sales guide: 300 m of liquid line in total, 120 m of real pipe (150 equivalent metres) to the farthest unit, 40 equivalent metres past the first branch, 50 m of height difference with the outdoor unit above, 40 m with it below, and 15 m between two indoor units.
Is there a grant for this VRF?
No LogisVert: the guide requires a complete ENERGY STAR certified system, and AHRI numbers 8654208 and 8654211 are not on ENERGY STAR, NEEP or Hydro-Québec’s list of Oct. 27, 2026. The Canada Greener Homes Grant is closed: applications ended Sept. 30, 2025.
Does it heat through a cold snap?
GREE publishes a heating range down to −30 °C, and its sales guide claims continuous heating down to −25 °C. No NEEP record certifies the cold-weather capacity of these two models, though, and the 2023 catalogue gives them a COP of 1.50 at −15 °C. So backup heat gets planned at the visit.
Are these two models still offered in Canada?
GREE Comfort, in the United States, has moved their documents to its archive, and GREE Canada now sells another Mini-GMV, the Ultra Heat GMV6 Mini. Supply of these two models and the warranty that applies in Canada are confirmed at the quote.
AirGreen

A large space, many rooms, one unit outside? Let’s talk it through on site, plans in hand.

Free estimate at home. Montréal, Laval, Longueuil, South Shore and North Shore.

GREE Elite dealerGREE training completed, priority access to original parts.
5 GREE VRF installationsPublished with photos on our installations blog, counted on Oct. 14, 2026.
RBQ 5645-9605-01Licences 15.8, 15.10 and 16.
Two documents, two limitsWhen the 2021 submittal and the 2017 sales guide differ, this page shows both.
Sources

Limits, ratings and sound: the GREE Comfort documents above; Canadian supply and warranty are confirmed at the quote. Checker calculations: AirGreen, from those limits. Page updated Oct. 26, 2026.