Installation of a GREE FreeMatch R32 GWHD(24)ND6MO two-head wall-mounted heat pump in Sainte-Madeleine
Concrete parapet, brick walls on two sides, waterproofing membrane on the floor: on an apartment-building balcony, the real risk isn't the weight of the compressor but the recirculation of its own air. This Sainte-Madeleine project explains how we handle this type of location.

In summer, the outdoor unit rejects the house's heat outside.
Generic illustration of this type of installation, not a survey of this job site. Tap a number.
Mounted level on a wall plate, high enough for the air to reach the whole room, with enough space around it to slide the filters out easily.
The refrigerant lines, the communication cable and the drain go through the wall in a single opening, sealed against water, cold air and insects.
Two insulated copper pipes connect the two units. Outside, a line cover can protect them from sun, knocks and weather.
A shut-off switch near the outdoor unit isolates it safely for service. It must stay accessible at all times.
The compressor and the fan. In heating mode it captures heat from the outdoor air, even in winter, and moves it inside.
On the ground or on the wall, it keeps the unit above accumulated snow. The unit stays clear and defrost water can drain away.
The fan needs to blow freely. Storage, a fence or a wall too close, and efficiency drops while noise goes up.
Installing a compressor on a building balcony: the problem is not the weight, but the air
At Sainte-Madeleine, in the Maskoutains RCM, we installed a two-head GREE FreeMatch R32 wall-mounted heat pump whose outdoor unit had to be installed on a building terrace: a concrete parapet on one side, brick walls on two others, membrane roofing on the ground, and an apartment window less than one meter away.
This type of location comes up repeatedly in heat pump projects in multi-unit buildings and condominiums, in Montreal, Laval, Longueuil, and the surrounding suburbs. Owners see available space there. We see three constraints that, if mishandled, ruin the unit's performance or damage the building.
The system: GREE FreeMatch R32, GWHD(24)ND6MO compressor
Technical data sheet
| Parameter | Value |
|---|---|
| Rated cooling capacity | 24,000 BTU/h (7,030 W) |
| Cooling modulation | 7,500–31,400 BTU/h |
| Rated heating capacity | 24,000 BTU/h |
| Heating modulation | 7,500–31,400 BTU/h |
| SEER2 | 21 |
| HSPF2 | 10 |
| EER2 | 12 |
| EER / COP | 3,8 / 3,9 |
| Connectable indoor units | 2 to 3 |
| Power supply | 208/230 V |
| MCA / MOCP | 19.5 A / 25 A |
| Power input (cooling) | 1,850 W |
| Refrigerant | R32 (A2L), 60 oz (1,700 g) |
| Precharged piping | 98 ft (30 m) |
| Maximum total length | 197 ft (60 m) |
| Maximum height difference | 49 ft (15 m) |
| Airflow | 2,236 cfm |
| Sound level | 58 dB(A) |
| Heating range | -30 °C to 24 °C |
| Weight | 112.5 lb (51 kg) |
| Certifications | ENERGY STAR, ENERGY STAR Cold Climate, AHRI |
| Warranty | 10 years compressor and parts (+2 years upon registration) |
Two figures carry significant weight in a building setting. The 2,236 cfm airflow: this is the volume the unit must be able to draw in and discharge freely, and it is precisely what an enclosed space compromises. And the 58 dB(A): measured at maximum output, at close range. At low modulation—that is, most of the time—the unit is significantly quieter, but a neighbor whose window faces the fan from three meters away will judge the installation by its worst nights, not its average.
The real risk of a recessed location: air recirculation
A heat pump outdoor unit draws air in through the back and sides of the coil and discharges it through the front, through the fan. In cooling mode, the discharged air is hot. In heating mode, it is cold.
Place this unit in a recess closed on three sides, and the discharged air has nowhere to go. It circulates, returns toward the intake, and the unit starts treating its own exhaust air again. This is recirculation, and its effects are measurable:
- In summer, the incoming-air temperature rises. Discharge pressure increases. Efficiency drops, the unit consumes more power, and the SEER2 of 21 becomes a laboratory figure unrelated to the reality of the home.
- In winter, the intake air is cooled by the discharge air. The coil frosts more quickly. Defrost cycles multiply, each consuming energy and interrupting the heating.
- In the long term, the compressor operates outside its design range. Its lifespan decreases.
How we addressed it in Sainte-Madeleine
- Discharge directed toward the only open side. The unit was positioned so that the fan blows toward the clearance, never toward the parapet or brick.
- Rear and side clearances verified with a tape measure, against the GREE installation manual values—not “by eye.” These clearances are not comfort recommendations; they are performance requirements.
- Verification of the discharged-air path. Discharge directed straight at a parapet one meter away returns toward the unit, even if the side clearance is compliant. We look at where the air goes, not just where it exits.
- No future obstructions allowed. We tell the customer, and we write it in the report: no flower box, storage unit, or decorative screen may be added around the unit. This is the number-one cause of efficiency loss in the years following an installation.
When a location does not allow the required clearances to be respected, we refuse to install the unit there. A unit that operates poorly from its first summer is not a compromise; it is a problem we will have to resolve at our own expense.
The waterproofing membrane: do not drill, do not load
The floor of this terrace is covered with a waterproofing membrane. Beneath it is a living space or parking area. Drilling through this membrane to anchor a support, or placing a 51 kg compressor on four point supports, is essentially scheduling a leak.
Our method:
- Elevated aluminum support, visible in the photo, that completely lifts the unit off the membrane surface.
- Load distribution across pads or sleepers that spread the weight rather than concentrating it.
- No fasteners penetrating the membrane. Lateral support is provided by anchoring to the wall above the waterproofing line, or by ballast, never by drilling into the floor.
- Clearance beneath the unit so that defrost water flows toward the terrace drain and does not freeze against the frame.
This last point deserves emphasis: on a balcony, defrost water must reach the existing drain. If it stagnates, it freezes, and the ice exerts pressure on the membrane as it expands. We check the actual slope of the surface before fixing the location.
What Condominium Associations and Property Managers Need to Know
In a multi-unit building, an HVAC installation never concerns just one occupant.
Prior Authorization
The façade, parapet, membrane, and often the balcony itself are common elements. An installation carried out without the written consent of the condominium association or owner exposes the occupant to a removal order at their expense. We systematically request this authorization before ordering the equipment, and we provide the association with the unit's technical data sheet, dimensions, weight, and sound level to support the request.
Electrical Power Supply
The GWHD(24) requires a dedicated 208/230 V circuit protected by 25 A, with a disconnect switch within sight. In a multi-unit building, this circuit must run from the panel of the served unit, never from a shared circuit. Charging its air conditioning to all the co-owners is a guaranteed source of conflict.
Noise and Neighbors
We position the unit with neighboring windows in mind, not just the customer's. When space is tight, the unit's quiet operating mode is enabled for nighttime operation during commissioning.
A2L Refrigerant
R32 is classified as A2L: mildly toxic and slightly flammable. In a multi-unit building, this requires sizing the charge according to the volume of the rooms served by each head, a calculation we document in the file. The A2L leak detection sensor supplied with the system is checked and recorded in the commissioning report, which is provided to both the occupant and the property manager.
Errors we regularly correct in multi-unit buildings
- Compressor pressed against the rear wall. The intake clearance is restricted. The unit operates, the customer sees nothing, and the summer electricity bill never drops as much as promised.
- Support placed flat on the membrane. No clearance, standing water, ice, or leaks two or three winters later.
- Condensate discharged over the parapet. The water falls onto the balcony below. That leads to a complaint, followed by a formal notice.
- Refrigerant charge not adjusted. In a building, piping runs are long. Beyond the 30 m precharged length, adding 20 g/m is mandatory, and the 15 m height difference must be respected to ensure oil returns to the compressor.
- No documentation left with the building. Occupants change, and property managers change. The AHRI sheet, evacuation report, final charge, and HVAC maintenance schedule must be kept in the building's records.
Performance and financial assistance
The GWHD(24)ND6MO delivers a SEER2 of 21, an HSPF2 of 10, and a COP of 3.9, with heating capacity maintained down to -30 °C thanks to its ENERGY STAR Cold Climate designation. For a home heated with electric baseboards, partially replacing them with a heat pump of this efficiency significantly changes winter consumption, particularly during the shoulder seasons, when the inverter modulates below one-third of its nominal capacity.
The unit falls within the performance categories generally accepted by energy-efficiency programs offered in Quebec, including LogisVert. The criteria, amounts, and required documents vary according to the program, building type, and year: we validate each application when the quote is prepared and provide the AHRI certification numbers and proof of installation required for processing.
Our approach
On a building balcony, a successful installation is recognized by what it does not produce: no leaks beneath the membrane, no complaints from neighbors, no loss of capacity by the third summer, and no dispute with the condo association. This comes down to three checks carried out before drilling anything—the airflow path, the water drainage route, and written authorization.
AirGreen performs the load calculation, supplies and completely installs the HVAC system, provides the dedicated electrical connection, documented commissioning, and annual HVAC maintenance for your wall-mounted heat pump in residential properties, condominiums, and multi-unit buildings in Montreal, Laval, Longueuil, the North Shore, the South Shore, and Montérégie, including Sainte-Madeleine and the Saint-Hyacinthe area.
Contact our team for an assessment of your project.
How it goes, from the first call to the end
The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.
We look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
Model, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
Floors and furniture protected, wall plate position marked level, wall opening located.
A single opening, with the slope the drain needs to flow outside.
Set on a stand raised above the snow, with the clearances the manufacturer requires.
Connected, insulated and protected. The opening is then sealed against water, cold air and insects.
A dedicated circuit and an accessible disconnect near the outdoor unit.
Leak test, vacuum, then start-up and a check of heating and cooling.
Remote, modes, filters: we show you the essentials before we leave.
- The on-site estimateWe look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
- The quoteModel, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
- Getting readyFloors and furniture protected, wall plate position marked level, wall opening located.
- The wall openingA single opening, with the slope the drain needs to flow outside.
- The outdoor unitSet on a stand raised above the snow, with the clearances the manufacturer requires.
- Lines, cable and drainConnected, insulated and protected. The opening is then sealed against water, cold air and insects.
- The electrical workA dedicated circuit and an accessible disconnect near the outdoor unit.
- Tests and start-upLeak test, vacuum, then start-up and a check of heating and cooling.
- The walkthroughRemote, modes, filters: we show you the essentials before we leave.
And at your place?
Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.
Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.
What to do, season by season
Three habits per season for this unit. They take a few minutes and prevent many calls.
- Clean the indoor unit's filters.
- Clear leaves and debris left on the outdoor unit by winter.
- Test cooling before the first hot days.
- Clean the filters more often when the unit runs a lot.
- Keep plants away from the outdoor unit.
- Check that no water drips from the indoor unit.
- Rake the leaves around the outdoor unit.
- Test heating before the first cold days.
- Book periodic maintenance before winter.
- Keep snow away from the stand and the front of the unit.
- Let the unit defrost: it is normal.
- Never hit the ice on the fins; call us if the unit stays iced up.
Which type of equipment for your project?
Pick what looks like your need.
Four mistakes we do not make
Flip each card to see what we do instead.
What people ask us about this kind of work
Does a wall-mounted heat pump heat in winter?
Wall-mounted or multi-zone: how do I choose?
Where does the outdoor unit go?
Are there grants?
Do I need a permit?
How cold can it heat?
How much can I save?
How is the LogisVert assistance calculated?
Is it noisy?
The outdoor unit is covered in ice: is that normal?
Does AirGreen hold the required licences?
Is the estimate free?
No question matches. Write to us: we answer.
Useful pages for what comes next
More jobs to see, near you
By town, by equipment or by region: browse more than 4,700 published projects.
Each dot: a town where AirGreen has published projects. The glowing dot: this job.
Tell us about your house. We come and see it for free.
The on-site estimate is free and the quote follows within 24 hours.
Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).