Home / Comparisons / 3-ton central heat pumps
HITACHI airCore 700 HEATFORCE and LG LGRED R32, head to head down to −25 °C
Two 3-ton central heat pumps on R-32, offered by AirGreen and ENERGY STAR cold climate per NEEP. NEEP tests them at the same four heating temperatures, from 8.3 °C to −25 °C: their values read row by row. In cooling, the certificate gives 36,000 BTU/h for the airCore 700 and 33,000 BTU/h for the LGRED.

airCore 700 HEATFORCE 3 tons
JPE36B3XD2HS1A / PAS-36BLFASDQ1 · AHRI 216439113
See the product page
What the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 36,000 BTU/h house in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference. The certificate gives 36,000 BTU/h in cooling for the airCore 700 and 33,000 BTU/h for the LGRED: the calculation uses their common nominal size, 3 tons.
How this amount is calculated
- Heat needed over the winter. A house whose heat loss reaches 36,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: a simplification that ignores the recovery after a setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup planned for when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 36,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. The network access fee, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, insulation, settings and use; this amount is not a promise.
At each certified temperature, what the heat pump covers and what is left to backup heat
One house, the same assumption as in the estimated cost: its heat loss is set at −23.1 °C and decreases when it is milder. At each of the four certificate temperatures, the column shows the house’s need, the share that the certified maximum capacity covers, and the rest, which falls to electric backup heat.
How this illustration is calculated
- The house’s need. Heat loss chosen at −23.1 °C × (18 − outdoor temperature) ÷ (18 − (−23.1)). It is the same straight line as in the estimated operating cost: no need at 18 °C, the chosen need at −23.1 °C, Montréal’s design temperature (Natural Resources Canada, HOT2000).
- The heat pump’s share. The smaller of the two values: the need, or the certified maximum heating capacity at that temperature (AHRI, published by NEEP). The four temperatures are those of the certificate; nothing is calculated between them.
- Left to backup heat. Need − certified maximum capacity, when the need is greater, converted to kW (÷ 3,412). Electric backup heat supplies 1 kW of heat per kW of electricity.
AirGreen illustration, November 9, 2026. Maximum capacity is measured in steady state, without defrost cycles. This is not a heat-loss calculation for your house or a choice of backup heat: the study of the house and the written quote establish those.
Below −15 °C: every published figure, at its exact temperature
NEEP certifies both units at −15 °C and at −25 °C, the same temperatures: those two rows compare directly. Between the two, LG publishes a maximum capacity at −20 °C; HITACHI publishes a percentage. Below −25 °C, neither manufacturer publishes a capacity: the page repeats the last point of each.
What HITACHI publishes for the HeatForce series, as a percentage
“Heating capacity ratio” from the airCore 700 brochure, HeatForce series: outdoor air wet-bulb temperature, 25 ft of piping, fan on high, frost and defrost losses not included. The brochure does not say which capacity the percentage is calculated on: it is not converted to BTU/h. Dark line: 100%.
What each manufacturer writes, row by row
HITACHI airCore 700 technical catalogue, brochure and installation manual; LG LGRED R32 submittal sheet for the KSSLA361A set. Each row repeats what the manufacturer writes.
airCore 700: R-32 DC inverter, model ATH356SKRC9EQ; preheating by multi-pulse control, with no external crankcase heater (brochure, catalogue).
LGRED: variable-speed (inverter) compressor; the submittal sheet does not state its model.
airCore 700: heating range down to −25 °C; defrost triggered according to the estimated amount of frost (catalogue).
LGRED: heating range down to −25 °C wet-bulb; outdoor unit base pan heater included as standard (submittal sheet).
airCore 700: 5 speed settings; 1,200 CFM at the medium-high setting; 0.1 to 1.0 in w.c.
LGRED: 3 speeds, 900 to 1,050 CFM; constant airflow with an ECM motor; 0.1 to 1.0 in w.c.
airCore 700: CIW03-H wall controller; adapter for a 5-wire thermostat (installation manual).
LGRED: LG wall controller, required to use a wireless remote; Wi-Fi through the optional PWFMDD200 module (submittal sheet).
airCore 700: 8HK kits from 2.4 to 19.2 kW nominal at 240 V (installation manual).
LGRED: ANEH series kits and PRARH1 auxiliary heater (submittal sheet).
airCore 700: 20 × 20 × 1 in filter supplied at installation, outside the unit; 36 in of access at the front for maintenance (installation manual).
LGRED: access panel for a 20 × 20 × 1 in filter supplied at installation (submittal sheet).
The sound of each one, per its manufacturer
LG publishes the sound pressure of the indoor unit and of the outdoor unit, measured in an anechoic chamber under the ISO 3745 standard. HITACHI publishes the sound pressure of the outdoor unit, without stating the method. Read the values separately.
How to read these numbers. dB(A) measures noise level as the ear perceives it: the lower the number, the quieter the unit. Each dot is a value published by the manufacturer.
Why this is not a ranking. LG states its method, HITACHI does not. Different or unknown method: not comparable.
Indoor unit, in the basement or a closet
Published values
airCore 700: the HITACHI technical catalogue and installation manual consulted do not give the sound of the JPE36B3XD2HS1A indoor unit.
Outdoor unit, outside
Published values
Measurements taken by each manufacturer with its own method: read them separately, not as a ranking.
Four cabinets at the same scale, then the piping
Outdoor units and indoor units, width and height to scale


Frames drawn at the published width and height, at the same scale. The LG units are the photos from the submittal sheet, placed in their frames. The HITACHI units are shown as diagrams; the AirGreen card at the top of the page shows the series.
Line-set length and refrigerant to add
AirGreen calculation from the manufacturers’ documents. HITACHI: nothing to add up to 98.4 ft, then 0.376 oz per foot. LG: nothing to add up to 24.6 ft, then 0.43 oz per foot; minimum length of 16.4 ft. Maximum published length: 246 ft for both.
| Installation | airCore 700 | LGRED |
|---|---|---|
| Maximum piping length | 246 ft | 246 ftEquivalent length; minimum of 16.4 ft. |
| Precharged length | 98.4 ft0.376 oz of R-32 per foot beyond. | 24.6 ft0.43 oz of R-32 per foot beyond. |
| Maximum height difference | 98.4 ft | 98.4 ft |
| Liquid – gas line diameters | 3/8 – 3/4 inTechnical catalogue, with the indoor unit; the brochure prints 5/8 in for the gas line. | 3/8 – 5/8 in |
| Outdoor unit W × H × D, weight | 37 13/32 × 54 21/64 × 12 19/32 in, 250.2 lb | 37 13/32 × 54 1/4 in, 190.2 lbThe depth was not taken from the drawing in the submittal sheet. |
| Indoor unit, weight | 17 1/2 × 48 3/8 × 21 7/16 in, 100 lb | 21 × 55 3/16 × 21 3/8 in, 141 lb |
| Electrical protectionoutdoor unit, 208/230 V | MCA 22.2 A · MOP 35 A | MCA 32 A · MOP 35 A |
| Factory refrigerant charge | 7.50 lb of R-32 | 106 oz of R-32 |
| Stated heating / cooling range | −25 to 24 °C / −18 to 46 °C | −25 to 18 °C / −15 to 48 °CHeating: outdoor wet-bulb temperature. |
Sources: HITACHI airCore 700 “Low Ambient Heating Series” technical catalogue (form HC2024583B), airCore 700 brochure and installation manual for the indoor units, no. 6554123; LG submittal sheet for the KSSLA361A set (KUSXA361A / KNSLA361A), file dated March 10, 2026. The HITACHI catalogue also prints a SEER2 of 19.5, an EER2 of 12.5 and an HSPF2 of 9.7: the page follows the AHRI certificate.
What people ask about these two central systems
Where do the two systems differ the most?
On seasonal efficiencies and at two of the four temperatures. SEER2 is 16.5 for the airCore 700 and 18.2 for the LGRED; Region V HSPF2, 8.4 and 7.85. The certified maximum capacity is 35,000 and 39,000 BTU/h at −8.3 °C, then 36,600 and 33,000 BTU/h at −15 °C. At −25 °C, they are close: 27,100 and 28,000 BTU/h.
What does “the heat pump’s share” show?
An illustration: for a house whose heat loss you choose, it compares the need at each certificate temperature with the certified maximum capacity of each unit. The rest, if any, falls to electric backup heat. This is not a heat-loss calculation for your house.
Why is the cooling capacity not the same?
Both units are sold as 3-ton units. The AHRI certificate gives a rated capacity of 36,000 BTU/h at 35 °C for the airCore 700 and 33,000 BTU/h for the LGRED. The estimated cost uses the common nominal size, 36,000 BTU/h, for both.
What do the manufacturers publish below −15 °C?
HITACHI publishes percentages for the HeatForce series: 100% at −15 °C, 85% at −20 °C and more than 70% at −25 °C, without saying on which capacity. LG publishes maximum capacities: 31,000 BTU/h at −20 °C and 29,000 BTU/h at −25 °C. At −25 °C, NEEP certifies 27,100 and 28,000 BTU/h; the certificate prevails.
Which one makes less noise?
HITACHI publishes 56 dB(A) for the outdoor unit, with no method; LG publishes 52 dB(A) in cooling and 54 dB(A) in heating, in an anechoic chamber. The methods are not the same: these numbers cannot be used to rank the units.
Are they eligible for rebates?
Per NEEP, both combinations are ENERGY STAR and ENERGY STAR cold climate. Eligibility depends on the official list in force on the date of purchase; this page promises no amount.
All the AHRI and NEEP values
| Certified value | airCore 700 | LGRED |
|---|---|---|
| Cooling | ||
| Rated capacity at 35 °C | 36,000 BTU/h | 33,000 BTU/h |
| SEER2 | 16.5 | 18.2 |
| EER2 | 12.0 | 13.0 |
| Heating, same conditions | ||
| HSPF2 Region IV | 10.2 | 9.6 |
| HSPF2 Region V | 8.4 | 7.85 |
| 8.3 °C: min. / rated / max.BTU/h | 14,200 / 38,000 / 47,000 | 11,904 / 40,000 / 43,000 |
| 8.3 °C: COP min. / rated / max. | 4.78 / 3.40 / 3.22 | 4.53 / 3.78 / 3.07 |
| −8.3 °C: min. / rated / max.BTU/h | 13,000 / 35,000 / 35,000 | 15,240 / 25,400 / 39,000 |
| −8.3 °C: COP min. / rated / max. | 2.91 / 2.30 / 2.30 | 2.83 / 2.80 / 2.38 |
| −15 °C: min. / rated / max.BTU/h | 12,300 / 36,600 / 36,600 | 8,628 / 33,000 / 33,000 |
| −15 °C: COP min. / rated / max. | 2.37 / 2.00 / 2.00 | 2.61 / 2.00 / 2.00 |
| Coldest point — same temperature for both | ||
| Test temperature | −25 °C (−13 °F) | −25 °C (−13 °F) |
| Min. / max. capacity | 10,000 / 27,100 BTU/h | 3,600 / 28,000 BTU/h |
| COP at maximum capacity | 1.70 | 1.64 |
| Listings and refrigerant | ||
| ENERGY STAR / cold climate (NEEP) | Yes / Yes | Yes / Yes |
| AHRI certificate · NEEP record | 216439113 · 508939 | 215588576 · 422333 |
| RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class | R-32 · GWP 675 · A2L | R-32 · GWP 675 · A2L |
higher marks the higher value of the same measure, under the same conditions. It is not a recommendation. Capacities and COPs at each point are not highlighted; they are compared in “The heat pump’s share” and “Extreme cold”. NEEP keeps a second record, 506725, for the same HITACHI combination, with the same values.
Both are on the AirGreen website.
To choose for your home, talk it over with our team: bring the heated floor area, the condition of your ducts and your current heating.
Where every figure comes from
Data verified on November 9, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, sound, piping and features: per each manufacturer. When a source contradicts the AHRI certificate, the certificate prevails.
Trademarks. HITACHI, airCore, HEATFORCE, LG and LGRED are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for these brands; this page is not produced, sponsored or endorsed by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong to you? Write to us : every reported figure is checked again.