FUJITSU AIRSTAGE CENTAURI ducted and GREE ALL MATCH Slim Duct, 12,000 BTU

Home / Comparisons / 12,000 BTU ducted heat pumps

Comparison · Ducted heat pump · 12,000 BTU

FUJITSU AIRSTAGE CENTAURI ducted and GREE ALL MATCH Slim Duct: two 300 mm cabinets, measured

Two 12,000 BTU ducted units on R-32, each certified as a single-zone system with its own outdoor unit. Their cabinets are the same height, 300 mm. The rest differs: the space taken in the ceiling, the clearances required, the pressure the fan accepts in the ducts and the certified values. This page puts them side by side.

Cabinet height : 300 mm and 300 mmStatic pressure : 30 to 200 Pa and 0 to 150 PaSEER2 19.1 and 21HSPF2 Region V 8.9 and 8
700 mm830 mm CENTAURIALL MATCH 300 mm

Drawing, to scale: both cabinets seen from the front, published width × height.

FUJITSU AIRSTAGE CENTAURI ducted (AirGreen image)
FUJITSU AIRSTAGE

CENTAURI ducted 12,000 BTU

ARUH12KUAS / AOUH12KUAS1 · AHRI 215434556

Also sold under the GENERAL AIRSTAGE name. The same indoor unit is also certified with the AOUH12KUBS1 (AHRI 217734522), same seasonal values.

View the product page
GREE ALL MATCH Slim Duct (AirGreen image)
GREE

ALL MATCH Slim Duct 12,000 BTU

DUC12HP230V1R32AH / VIR12HP230V1R32AO · AHRI 215415562

NEEP certified values almost identical to those of the GREE AIRY ducted (AHRI 216618221): only the SEER2 and the rated capacity at −8.3 °C differ.

View the product page
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the point of reference.

How this amount is calculated
  1. Heat needed over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
  4. Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.

AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.

In the ceiling

Same cabinet height; what each manual asks for around it

A ducted unit hides between the structure and the finished ceiling, or in a bulkhead. Both cabinets are 300 mm high, and each manual adds clearances. Set the depth you have: the drawing, to scale, shows the minimum each manufacturer asks for.

400 mm
CENTAURI ducted FUJITSU AIRSTAGE

Manual minimum: 20 mm above + 300 mm cabinet + 20 mm below = 340 mm (13 3/8 in). Manual DR_AR107ES_07, § 2-4.

ALL MATCH Slim Duct GREE

Submittal minimum: 20 mm above + 300 mm cabinet = 320 mm (12 5/8 in). GREE’s figure gives no clearance below. Submittal GREE_DUC12HP_230V_R32_SUB_08272025, p. 7.

Section drawing, to scale. Hatched band: clearance required by the manufacturer. The depth needed on site also depends on the ducts, the drain slope and the access hatch: it is confirmed during the visit.

Around the cabinetCENTAURI ductedALL MATCH Slim Duct
Indoor unit H × W × D, weight300 × 700 × 700 mm, 66 lb11 13/16 × 27 9/16 × 27 9/16 in; 30 kg300 × 830 × 754 mm, 70.6 lb11 13/16 × 32 43/64 × 29 11/16 in; 32 kg
Clearance above20 mm or more (1 in)More than 20 mm (3/4 in)
Clearance below20 mm or more (1 in)Not published by the manufacturer
Clearance, control box side300 mm or more (12 in)More than 300 mm (11 13/16 in)
Clearance, opposite side150 mm or more (6 in)More than 150 mm (5 7/8 in)
Service accessHatch of 300 × 500 mm or more under the control box; for the fan and the filter, 500 mm or more of depth under the fan sideMore than 1,000 mm (39 3/8 in) free in front of the return air; the manual asks for maintenance space, with no hatch size given

FUJITSU AIRSTAGE, manual DR_AR107ES_07, pp. 2, 11 and 12. GREE, submittal GREE_DUC12HP_230V_R32_SUB_08272025, pp. 2 and 7, and service manual JF00305639, p. 36.

Same height, different footprint. Seen from above, the CENTAURI ducted takes 700 × 700 mm, or 0.49 m²; the ALL MATCH Slim Duct, 830 × 754 mm, or 0.63 m². The side clearances required are the same for both: 300 mm and 150 mm.
Static pressure and airflow

What the fan accepts in the ducts

External static pressure is the resistance that ducts, elbows, the filter and grilles put up against the fan. The longer or narrower the duct system, the higher it gets. Each manufacturer publishes the range its fan accepts and the settings offered. Move the slider to place a given pressure in each one.

50 Pa
CENTAURI ducted
0 Pa50100150200 Pa
ALL MATCH Slim Duct
0 Pa50100150200 Pa

Each dot is a published setting. Diamond: the CENTAURI ducted Standard setting, 45 Pa, the factory one. Pale band: published range. The pressure of your duct system is calculated from the duct layout: that is the installer’s job, and this page gives no sizing advice.

CENTAURI ducted · airflow by speed

Quiet300 CFM
Low347 CFM
Medium400 CFM
High500 CFM

ALL MATCH Slim Duct · airflow by speed

Speed 1212 CFM
Speed 2247 CFM
Speed 3288 CFM
Speed 4353 CFM

Same scale for both, from 0 to 520 CFM. GREE’s manual gives four airflows without naming the speeds. Each manufacturer measures its airflow at its own test pressure: read these bars one unit at a time.

Fan and ductsCENTAURI ductedALL MATCH Slim Duct
External static pressure range30 to 200 Pa (0.12 to 0.80 in. w.g.)0 to 150 Pa (0.6 in. w.c. maximum)
Static pressure settings18 settings, from 30 to 200 Pa in 10 Pa steps; a Standard setting; an automatic airflow adjustment setting8 notches: 0, 20, 40, 60, 80, 100, 120 and 150 Pa
Factory settingStandard, 45 Pa (0.18 in. w.g.)Not published by the manufacturer
Where the setting is madeRemote controller, function 26; the submittal also lists automatic static pressure detectionWired controller; notches 2 to 9 in the manual, curves P02 to P09 in the submittal
Airflow by speed4 speeds: 300 / 347 / 400 / 500 CFM4 speeds: 212 / 247 / 288 / 353 CFM
Static pressure in the capacity test145 Pa (0.58 in. w.g.)Not published by the manufacturer

FUJITSU AIRSTAGE, manual DR_AR107ES_07, pp. 2, 3 and 87, and submittal 12KUAS1R. GREE, submittal GREE_DUC12HP_230V_R32_SUB_08272025, pp. 2 and 4, and service manual JF00305639, pp. 2 and 46.

Extreme cold

Below −15 °C: every published number, at its exact temperature

At −15 °C, both are certified at the same point: 15,500 and 10,500 BTU/h maximum. Lower down, their certified points are not at the same temperature: −20.6 °C for the CENTAURI ducted, −30 °C for the ALL MATCH Slim Duct.

What each manufacturer publishes below −15 °C. FUJITSU AIRSTAGE: the capacity table in manual DR_AR107ES_07 stops at −5 °F (−20.6 °C), with 13,960 BTU/h for 2.20 kW; the published heating range goes down to −21 °C, and the manual states that a protective function may operate outside that range. GREE: the submittal lists heating from −30 to 30 °C; it gives no capacity table by temperature, and the two points certified by NEEP, −15 and −30 °C, are the only published figures.
Documented features

What each manufacturer writes, group by group

FUJITSU AIRSTAGE: submittal 12KUAS1R and manual DR_AR107ES_07. GREE: submittal GREE_DUC12HP_230V_R32_SUB_08272025 and service manual JF00305639.

Static pressure

CENTAURI ducted : 30 to 200 Pa, 18 settings, a Standard setting and an automatic airflow adjustment; automatic static pressure detection.

ALL MATCH Slim Duct : 0 to 150 Pa in 8 notches, set on the wired controller.

Drain pump

CENTAURI ducted : built-in drain pump; lift height not published in the pages read.

ALL MATCH Slim Duct : internal condensate pump; raising pipe below 850 mm per the service manual.

Return air

CENTAURI ducted : side or bottom air intake.

ALL MATCH Slim Duct : from the rear as shipped, or from the bottom; the manual warns that bottom return is likely to produce more noise.

Controls

CENTAURI ducted : optional controllers: wired, wireless with the UTY-LBTUM kit; optional Wi-Fi, AIRSTAGE Mobile app.

ALL MATCH Slim Duct : XE72-44/E wired controller and wireless remote included; “WiFi Included: No” per the submittal.

Modes

CENTAURI ducted : Economy, Energy Saving, Powerful, Minimum Heat; weekly timer.

ALL MATCH Slim Duct : Energy Saving, Turbo, Sleep, I Feel, X-Fan, Freeze Guard; timer.

Refrigerant sensor

CENTAURI ducted : built-in refrigerant leak detection sensor.

ALL MATCH Slim Duct : refrigerant sensor, per the submittal.

Network and home automation

CENTAURI ducted : compatible with BACnet and Modbus, with the manufacturer’s accessories.

ALL MATCH Slim Duct : not published by the manufacturer in the documents read.

Defrost and restart

CENTAURI ducted : automatic defrost and auto-restart.

ALL MATCH Slim Duct : “intelligent” defrosting and power failure recovery.

Base pan and compressor

CENTAURI ducted : heated pan: not published by the manufacturer; DC twin rotary compressor.

ALL MATCH Slim Duct : base pan with electric heater; inverter rotary compressor.

Sound

Two hidden cabinets, two measurement methods

FUJITSU AIRSTAGE publishes four speeds, measured in an anechoic chamber. GREE’s manual gives four levels, without describing its test conditions.

dB(A)

How to read these numbers. dB(A) measures a noise level the way the ear perceives it: the lower the number, the quieter the unit. Each dot is a published fan speed, from slowest to fastest.

Why this is not a ranking. The methods are not the same, and neither are the airflows: 300 to 500 CFM for the CENTAURI ducted, 212 to 353 for the ALL MATCH Slim Duct. A ducted unit is hidden: what you hear in the room also depends on the ducts and the grilles.

Indoor unit, at the cabinet

Every published speed

Outdoor unit, outside

Published values

Measurements taken by each manufacturer using its own method: read them separately, not as a ranking.

Installation

Outside and in between: clearances, piping, weight

CENTAURI ducted · outdoor unit, top view

Drawing. Obstacles behind and on the sides, open above: manual DR_AR107ES_07, § 3-1.

ALL MATCH Slim Duct · outdoor unit, top view

Drawing. Submittal, p. 7; the clearance behind can drop to 3 in if the underside of the unit is unobstructed.

Indoor units, photos at the same width scale

CENTAURI ducted700 mm wide
Indoor unit ARUH12KUAS
27 9/16 in · 700 mm
ALL MATCH Slim Duct830 mm wide
Indoor unit DUC12HP230V1R32AH
32 43/64 in · 830 mm

Three-quarter photos: the dimension line gives each cabinet’s published width. The section drawing under “In the ceiling” is to scale.

InstallationCENTAURI ductedALL MATCH Slim Duct
Maximum piping length98 ft66 ft
Precharged length66 ft25 ft
Maximum height difference49 ft40 ft
Liquid – gas diameters1/4 – 3/8 in1/4 – 3/8 inIndoor side; the outdoor connection is 1/4 – 1/2 in, with a flare adapter
Outdoor unit W × H × D, weight31 7/16 × 24 7/8 × 11 7/16 in, 84 lb31 37/64 × 21 27/32 × 13 25/32 in, 67.3 lb
Indoor unit, weight66 lb70.6 lb
Electrical protectionAccording to the manufacturer; the two published measures are not the sameMaximum operating current: 11.7 AMaximum protection (MOCP): 15 A; minimum circuit ampacity (MCA): 10 A
Heated base panNot published by the manufacturerYes
Dehumidification0.7 L/h1.5 pints/h1.4 L/h2.96 pints/h per the submittal, converted
Advertised heating / cooling range−21 to 24 °C / −21 to 50 °C−30 to 30 °C / −29 to 50 °C

FUJITSU AIRSTAGE, manual DR_AR107ES_07, pp. 2 and 102. GREE, submittal GREE_DUC12HP_230V_R32_SUB_08272025, pp. 2 and 3; values with the VIR12HP230V1R32AO outdoor unit. GREE ranges published in °F: −22 to 86 °F and −20 to 122 °F.

Frequently asked questions

What people ask about these two ducted units

Which one is thinner?

Neither: both cabinets are 300 mm high (11 13/16 in). The difference is elsewhere: 700 × 700 mm for the CENTAURI ducted, 830 × 754 mm for the ALL MATCH Slim Duct, and a 20 mm clearance below that only the FUJITSU AIRSTAGE manual gives.

How deep does the ceiling space need to be?

The documents give a minimum of 340 mm for the CENTAURI ducted and 320 mm for the ALL MATCH Slim Duct, cabinet and clearances included. Ducts, drain slope and the access hatch come on top depending on the job; the measurement is confirmed on site.

Which one accepts the longest ducts?

The possible length depends on the static pressure of the duct system, which the installer calculates. The published ranges are 30 to 200 Pa for the CENTAURI ducted and 0 to 150 Pa for the ALL MATCH Slim Duct. Below 30 Pa, only the second has a published setting; above 150 Pa, only the first.

Are they certified on their own, or as heads of a multi-zone system?

This page compares two single-zone systems, each with its own AHRI certificate: ARUH12KUAS with AOUH12KUAS1 (215434556) and DUC12HP230V1R32AH with VIR12HP230V1R32AO (215415562). GREE’s submittal also lists two other outdoor units for the same cabinet, with their own certificates; the values on this page are those of the combination shown.

And in extreme cold?

At −15 °C, NEEP certifies 15,500 BTU/h maximum for the CENTAURI ducted and 10,500 for the ALL MATCH Slim Duct. Lower down, the points are no longer at the same temperature: 14,000 BTU/h at −20.6 °C for the first, 6,500 BTU/h at −30 °C for the second.

Do they go by other names?

The CENTAURI ducted is also sold under the GENERAL AIRSTAGE name. For GREE, the NEEP record of the GREE AIRY ducted (AHRI 216618221) carries almost the same certified values as the ALL MATCH Slim Duct: the SEER2 (21.5 versus 21) and the rated capacity at −8.3 °C (10,300 versus 10,000 BTU/h) differ.

Are they eligible for grants?

Eligibility depends on the official list in effect on the purchase date. This page promises no amount; the current list is checked when the quote is prepared.

Certified data

All AHRI and NEEP values

Certified valueCENTAURI ductedALL MATCH Slim Duct
Cooling
35 °C: min. / rated / max.BTU/h3,100 / 12,000 / 13,6002,700 / 12,000 / 15,354
SEER219.121.0
EER212.713.0
Heating, same conditions
HSPF2 Region IV / V10.5 / 8.99.0 / 8.0
8.3 °C: min. / rated / max.BTU/h3,400 / 16,000 / 19,4003,070 / 12,000 / 14,160
8.3 °C: COP min. / rated / max.5.54 / 3.75 / 3.095.29 / 3.78 / 3.61
−8.3 °C: min. / rated / max.BTU/h2,300 / 10,700 / 17,3002,700 / 10,000 / 12,000
−8.3 °C: COP min. / rated / max.4.49 / 2.93 / 2.393.04 / 2.79 / 2.20
−15 °C: min. / rated / max.BTU/h2,100 / 15,500 / 15,5002,600 / 10,500 / 10,500
−15 °C: COP min. / rated / max.4.10 / 2.02 / 2.022.54 / 1.90 / 1.90
Coldest point — different temperatures, not highlighted
Test temperature−20.6 °C (−5 °F)−30 °C (−22 °F)
Capacity min. / max.2,000 / 14,000 BTU/h2,000 / 6,500 BTU/h
COP at maximum capacity1.861.42
Certifications and refrigerant
ENERGY STAR / cold climate (NEEP)Yes / YesYes / Yes
Certificate type (NEEP)Single-zone, compact ductedSingle-zone, compact ducted
AHRI certificate · NEEP record215434556 · 388257215415562 · 388979
RefrigerantGWP per the IPCC (AR4); ASHRAE 34 classR-32 · GWP 675 · A2LR-32 · GWP 675 · A2L

higher marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Capacities and COPs at each point are not highlighted: the order changes depending on the point.

Both are on the AirGreen website.

To choose for your home, talk to our team: bring the free depth in the ceiling, the planned duct route and the planned outdoor location.

Sources and documents

Where each number comes from