Home / Comparisons / 12,000 BTU ducted heat pumps
FUJITSU AIRSTAGE CENTAURI ducted and GREE ALL MATCH Slim Duct: two 300 mm cabinets, measured
Two 12,000 BTU ducted units on R-32, each certified as a single-zone system with its own outdoor unit. Their cabinets are the same height, 300 mm. The rest differs: the space taken in the ceiling, the clearances required, the pressure the fan accepts in the ducts and the certified values. This page puts them side by side.
Drawing, to scale: both cabinets seen from the front, published width × height.
CENTAURI ducted 12,000 BTU
ARUH12KUAS / AOUH12KUAS1 · AHRI 215434556
Also sold under the GENERAL AIRSTAGE name. The same indoor unit is also certified with the AOUH12KUBS1 (AHRI 217734522), same seasonal values.
View the product page
ALL MATCH Slim Duct 12,000 BTU
DUC12HP230V1R32AH / VIR12HP230V1R32AO · AHRI 215415562
NEEP certified values almost identical to those of the GREE AIRY ducted (AHRI 216618221): only the SEER2 and the rated capacity at −8.3 °C differ.
View the product pageWhat the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the point of reference.
How this amount is calculated
- Heat needed over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.
Same cabinet height; what each manual asks for around it
A ducted unit hides between the structure and the finished ceiling, or in a bulkhead. Both cabinets are 300 mm high, and each manual adds clearances. Set the depth you have: the drawing, to scale, shows the minimum each manufacturer asks for.
Manual minimum: 20 mm above + 300 mm cabinet + 20 mm below = 340 mm (13 3/8 in). Manual DR_AR107ES_07, § 2-4.
Submittal minimum: 20 mm above + 300 mm cabinet = 320 mm (12 5/8 in). GREE’s figure gives no clearance below. Submittal GREE_DUC12HP_230V_R32_SUB_08272025, p. 7.
Section drawing, to scale. Hatched band: clearance required by the manufacturer. The depth needed on site also depends on the ducts, the drain slope and the access hatch: it is confirmed during the visit.
| Around the cabinet | CENTAURI ducted | ALL MATCH Slim Duct |
|---|---|---|
| Indoor unit H × W × D, weight | 300 × 700 × 700 mm, 66 lb11 13/16 × 27 9/16 × 27 9/16 in; 30 kg | 300 × 830 × 754 mm, 70.6 lb11 13/16 × 32 43/64 × 29 11/16 in; 32 kg |
| Clearance above | 20 mm or more (1 in) | More than 20 mm (3/4 in) |
| Clearance below | 20 mm or more (1 in) | Not published by the manufacturer |
| Clearance, control box side | 300 mm or more (12 in) | More than 300 mm (11 13/16 in) |
| Clearance, opposite side | 150 mm or more (6 in) | More than 150 mm (5 7/8 in) |
| Service access | Hatch of 300 × 500 mm or more under the control box; for the fan and the filter, 500 mm or more of depth under the fan side | More than 1,000 mm (39 3/8 in) free in front of the return air; the manual asks for maintenance space, with no hatch size given |
FUJITSU AIRSTAGE, manual DR_AR107ES_07, pp. 2, 11 and 12. GREE, submittal GREE_DUC12HP_230V_R32_SUB_08272025, pp. 2 and 7, and service manual JF00305639, p. 36.
What the fan accepts in the ducts
External static pressure is the resistance that ducts, elbows, the filter and grilles put up against the fan. The longer or narrower the duct system, the higher it gets. Each manufacturer publishes the range its fan accepts and the settings offered. Move the slider to place a given pressure in each one.
Each dot is a published setting. Diamond: the CENTAURI ducted Standard setting, 45 Pa, the factory one. Pale band: published range. The pressure of your duct system is calculated from the duct layout: that is the installer’s job, and this page gives no sizing advice.
CENTAURI ducted · airflow by speed
ALL MATCH Slim Duct · airflow by speed
Same scale for both, from 0 to 520 CFM. GREE’s manual gives four airflows without naming the speeds. Each manufacturer measures its airflow at its own test pressure: read these bars one unit at a time.
| Fan and ducts | CENTAURI ducted | ALL MATCH Slim Duct |
|---|---|---|
| External static pressure range | 30 to 200 Pa (0.12 to 0.80 in. w.g.) | 0 to 150 Pa (0.6 in. w.c. maximum) |
| Static pressure settings | 18 settings, from 30 to 200 Pa in 10 Pa steps; a Standard setting; an automatic airflow adjustment setting | 8 notches: 0, 20, 40, 60, 80, 100, 120 and 150 Pa |
| Factory setting | Standard, 45 Pa (0.18 in. w.g.) | Not published by the manufacturer |
| Where the setting is made | Remote controller, function 26; the submittal also lists automatic static pressure detection | Wired controller; notches 2 to 9 in the manual, curves P02 to P09 in the submittal |
| Airflow by speed | 4 speeds: 300 / 347 / 400 / 500 CFM | 4 speeds: 212 / 247 / 288 / 353 CFM |
| Static pressure in the capacity test | 145 Pa (0.58 in. w.g.) | Not published by the manufacturer |
FUJITSU AIRSTAGE, manual DR_AR107ES_07, pp. 2, 3 and 87, and submittal 12KUAS1R. GREE, submittal GREE_DUC12HP_230V_R32_SUB_08272025, pp. 2 and 4, and service manual JF00305639, pp. 2 and 46.
Below −15 °C: every published number, at its exact temperature
At −15 °C, both are certified at the same point: 15,500 and 10,500 BTU/h maximum. Lower down, their certified points are not at the same temperature: −20.6 °C for the CENTAURI ducted, −30 °C for the ALL MATCH Slim Duct.
What each manufacturer writes, group by group
FUJITSU AIRSTAGE: submittal 12KUAS1R and manual DR_AR107ES_07. GREE: submittal GREE_DUC12HP_230V_R32_SUB_08272025 and service manual JF00305639.
CENTAURI ducted : 30 to 200 Pa, 18 settings, a Standard setting and an automatic airflow adjustment; automatic static pressure detection.
ALL MATCH Slim Duct : 0 to 150 Pa in 8 notches, set on the wired controller.
CENTAURI ducted : built-in drain pump; lift height not published in the pages read.
ALL MATCH Slim Duct : internal condensate pump; raising pipe below 850 mm per the service manual.
CENTAURI ducted : side or bottom air intake.
ALL MATCH Slim Duct : from the rear as shipped, or from the bottom; the manual warns that bottom return is likely to produce more noise.
CENTAURI ducted : optional controllers: wired, wireless with the UTY-LBTUM kit; optional Wi-Fi, AIRSTAGE Mobile app.
ALL MATCH Slim Duct : XE72-44/E wired controller and wireless remote included; “WiFi Included: No” per the submittal.
CENTAURI ducted : Economy, Energy Saving, Powerful, Minimum Heat; weekly timer.
ALL MATCH Slim Duct : Energy Saving, Turbo, Sleep, I Feel, X-Fan, Freeze Guard; timer.
CENTAURI ducted : built-in refrigerant leak detection sensor.
ALL MATCH Slim Duct : refrigerant sensor, per the submittal.
CENTAURI ducted : compatible with BACnet and Modbus, with the manufacturer’s accessories.
ALL MATCH Slim Duct : not published by the manufacturer in the documents read.
CENTAURI ducted : automatic defrost and auto-restart.
ALL MATCH Slim Duct : “intelligent” defrosting and power failure recovery.
CENTAURI ducted : heated pan: not published by the manufacturer; DC twin rotary compressor.
ALL MATCH Slim Duct : base pan with electric heater; inverter rotary compressor.
Two hidden cabinets, two measurement methods
FUJITSU AIRSTAGE publishes four speeds, measured in an anechoic chamber. GREE’s manual gives four levels, without describing its test conditions.
How to read these numbers. dB(A) measures a noise level the way the ear perceives it: the lower the number, the quieter the unit. Each dot is a published fan speed, from slowest to fastest.
Why this is not a ranking. The methods are not the same, and neither are the airflows: 300 to 500 CFM for the CENTAURI ducted, 212 to 353 for the ALL MATCH Slim Duct. A ducted unit is hidden: what you hear in the room also depends on the ducts and the grilles.
Indoor unit, at the cabinet
Every published speed
Outdoor unit, outside
Published values
Measurements taken by each manufacturer using its own method: read them separately, not as a ranking.
Outside and in between: clearances, piping, weight
CENTAURI ducted · outdoor unit, top view
Drawing. Obstacles behind and on the sides, open above: manual DR_AR107ES_07, § 3-1.
ALL MATCH Slim Duct · outdoor unit, top view
Drawing. Submittal, p. 7; the clearance behind can drop to 3 in if the underside of the unit is unobstructed.
Indoor units, photos at the same width scale


Three-quarter photos: the dimension line gives each cabinet’s published width. The section drawing under “In the ceiling” is to scale.
| Installation | CENTAURI ducted | ALL MATCH Slim Duct |
|---|---|---|
| Maximum piping length | 98 ft | 66 ft |
| Precharged length | 66 ft | 25 ft |
| Maximum height difference | 49 ft | 40 ft |
| Liquid – gas diameters | 1/4 – 3/8 in | 1/4 – 3/8 inIndoor side; the outdoor connection is 1/4 – 1/2 in, with a flare adapter |
| Outdoor unit W × H × D, weight | 31 7/16 × 24 7/8 × 11 7/16 in, 84 lb | 31 37/64 × 21 27/32 × 13 25/32 in, 67.3 lb |
| Indoor unit, weight | 66 lb | 70.6 lb |
| Electrical protectionAccording to the manufacturer; the two published measures are not the same | Maximum operating current: 11.7 A | Maximum protection (MOCP): 15 A; minimum circuit ampacity (MCA): 10 A |
| Heated base pan | Not published by the manufacturer | Yes |
| Dehumidification | 0.7 L/h1.5 pints/h | 1.4 L/h2.96 pints/h per the submittal, converted |
| Advertised heating / cooling range | −21 to 24 °C / −21 to 50 °C | −30 to 30 °C / −29 to 50 °C |
FUJITSU AIRSTAGE, manual DR_AR107ES_07, pp. 2 and 102. GREE, submittal GREE_DUC12HP_230V_R32_SUB_08272025, pp. 2 and 3; values with the VIR12HP230V1R32AO outdoor unit. GREE ranges published in °F: −22 to 86 °F and −20 to 122 °F.
What people ask about these two ducted units
Which one is thinner?
Neither: both cabinets are 300 mm high (11 13/16 in). The difference is elsewhere: 700 × 700 mm for the CENTAURI ducted, 830 × 754 mm for the ALL MATCH Slim Duct, and a 20 mm clearance below that only the FUJITSU AIRSTAGE manual gives.
How deep does the ceiling space need to be?
The documents give a minimum of 340 mm for the CENTAURI ducted and 320 mm for the ALL MATCH Slim Duct, cabinet and clearances included. Ducts, drain slope and the access hatch come on top depending on the job; the measurement is confirmed on site.
Which one accepts the longest ducts?
The possible length depends on the static pressure of the duct system, which the installer calculates. The published ranges are 30 to 200 Pa for the CENTAURI ducted and 0 to 150 Pa for the ALL MATCH Slim Duct. Below 30 Pa, only the second has a published setting; above 150 Pa, only the first.
Are they certified on their own, or as heads of a multi-zone system?
This page compares two single-zone systems, each with its own AHRI certificate: ARUH12KUAS with AOUH12KUAS1 (215434556) and DUC12HP230V1R32AH with VIR12HP230V1R32AO (215415562). GREE’s submittal also lists two other outdoor units for the same cabinet, with their own certificates; the values on this page are those of the combination shown.
And in extreme cold?
At −15 °C, NEEP certifies 15,500 BTU/h maximum for the CENTAURI ducted and 10,500 for the ALL MATCH Slim Duct. Lower down, the points are no longer at the same temperature: 14,000 BTU/h at −20.6 °C for the first, 6,500 BTU/h at −30 °C for the second.
Do they go by other names?
The CENTAURI ducted is also sold under the GENERAL AIRSTAGE name. For GREE, the NEEP record of the GREE AIRY ducted (AHRI 216618221) carries almost the same certified values as the ALL MATCH Slim Duct: the SEER2 (21.5 versus 21) and the rated capacity at −8.3 °C (10,300 versus 10,000 BTU/h) differ.
Are they eligible for grants?
Eligibility depends on the official list in effect on the purchase date. This page promises no amount; the current list is checked when the quote is prepared.
All AHRI and NEEP values
| Certified value | CENTAURI ducted | ALL MATCH Slim Duct |
|---|---|---|
| Cooling | ||
| 35 °C: min. / rated / max.BTU/h | 3,100 / 12,000 / 13,600 | 2,700 / 12,000 / 15,354 |
| SEER2 | 19.1 | 21.0 |
| EER2 | 12.7 | 13.0 |
| Heating, same conditions | ||
| HSPF2 Region IV / V | 10.5 / 8.9 | 9.0 / 8.0 |
| 8.3 °C: min. / rated / max.BTU/h | 3,400 / 16,000 / 19,400 | 3,070 / 12,000 / 14,160 |
| 8.3 °C: COP min. / rated / max. | 5.54 / 3.75 / 3.09 | 5.29 / 3.78 / 3.61 |
| −8.3 °C: min. / rated / max.BTU/h | 2,300 / 10,700 / 17,300 | 2,700 / 10,000 / 12,000 |
| −8.3 °C: COP min. / rated / max. | 4.49 / 2.93 / 2.39 | 3.04 / 2.79 / 2.20 |
| −15 °C: min. / rated / max.BTU/h | 2,100 / 15,500 / 15,500 | 2,600 / 10,500 / 10,500 |
| −15 °C: COP min. / rated / max. | 4.10 / 2.02 / 2.02 | 2.54 / 1.90 / 1.90 |
| Coldest point — different temperatures, not highlighted | ||
| Test temperature | −20.6 °C (−5 °F) | −30 °C (−22 °F) |
| Capacity min. / max. | 2,000 / 14,000 BTU/h | 2,000 / 6,500 BTU/h |
| COP at maximum capacity | 1.86 | 1.42 |
| Certifications and refrigerant | ||
| ENERGY STAR / cold climate (NEEP) | Yes / Yes | Yes / Yes |
| Certificate type (NEEP) | Single-zone, compact ducted | Single-zone, compact ducted |
| AHRI certificate · NEEP record | 215434556 · 388257 | 215415562 · 388979 |
| RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class | R-32 · GWP 675 · A2L | R-32 · GWP 675 · A2L |
higher marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Capacities and COPs at each point are not highlighted: the order changes depending on the point.
Both are on the AirGreen website.
To choose for your home, talk to our team: bring the free depth in the ceiling, the planned duct route and the planned outdoor location.
Where each number comes from
Data verified on November 9, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, clearances, static pressure, sound, piping and features: according to the manufacturer. When a source contradicts the AHRI certificate, the certificate prevails.
Trademarks. FUJITSU AIRSTAGE, CENTAURI, GREE and ALL MATCH are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for these brands; this page is not produced, sponsored or endorsed by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong? Write to us: every reported figure is checked again.