FUJITSU AIRSTAGE ORION XLTH and KINGHOME POLARIS R32, 12,000 BTU

Home / Comparisons / 12,000 BTU wall-mounted heat pumps

Comparison · Wall-mounted heat pump · 12,000 BTU

FUJITSU AIRSTAGE ORION XLTH and KINGHOME POLARIS R32, from 8.3 °C to −30 °C

Two 12,000 BTU wall units, ENERGY STAR cold-climate certified, R-32, both offered by AirGreen. This page lines up their AHRI and NEEP values point by point, explains why their two coldest points cannot be compared directly, and shows what the manufacturers’ sheets add.

FUJITSU AIRSTAGE ORION XLTH 12,000 BTU: indoor unit, outdoor unit and remote control (AirGreen image) FUJITSU AIRSTAGE

ORION XLTH 12,000 BTU

ind. ASUH12KZAS · outd. AOUH12KZAH1 · AHRI 214888802

Also sold under the name GENERAL AIRSTAGE ORION XLTH (same AHRI certificate).

See the product page
KINGHOME POLARIS R32 12,000 BTU: indoor unit, outdoor unit and remote control (AirGreen image) KINGHOME

POLARIS R32 12,000 BTU

ind. KWP12R32C3I · outd. KWP12R32C3O · AHRI 218451122

Listed at NEEP under the “Glovia” series (same AHRI certificate).

See the product page
Maximum capacity at −15 °C
16,600against13,700
BTU/h · ORION XLTH / POLARIS R32
Rated capacity at −8.3 °C
10,000against15,000
BTU/h · ORION XLTH / POLARIS R32
HSPF2, Region IV
12.7against10.0
ORION XLTH / POLARIS R32
Coldest certified point
−26.1and−30
°C · ORION XLTH / POLARIS R32
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec’s Rate D, taxes included. Both heat pumps are calculated in exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference point.

How this amount is calculated
  1. Heat to deliver over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours per day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump as for the baseboards: this simplification does not account for recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario you can set above, from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a ceiling, since a variable-speed unit slows down once the room is at temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. Network access charges, the same with or without a heat pump, are not counted.

AirGreen method v1.1, November 9, 2026. An estimate is used to compare units under the same conditions. The actual bill depends on the house, the insulation, the settings and the use; this amount is not a promise.

The thermometer

Bring the mercury down, one published point at a time

Slide the thermometer down. The red bar (ORION XLTH) and the blue bar (POLARIS R32) show the maximum published capacity at the displayed temperature, the yellow line the rated capacity when there is one. Down to −15 °C, both are certified by NEEP at the same temperatures. Lower, each bar shows only what its manufacturer or NEEP publishes at that exact temperature; between two published points, a band shows the range between them.

−15°C

ORION XLTH FUJITSU AIRSTAGE—BTU/h max.

POLARIS R32 KINGHOME—BTU/h max.

06,00012,00018,00024,000 BTU/h
bar: maximum published capacityline: NEEP-certified rated capacity
Below −15 °C, no shared temperature. FUJITSU AIRSTAGE publishes the ORION XLTH at −20.6 °C (technical manual) and at −26.1 °C (NEEP); KINGHOME publishes the POLARIS R32 only at −30 °C (NEEP). Neither point is measured at the other’s temperature. At a temperature with no published point, the bar shows the range between the two published points on either side, or the last published point with its own temperature. Every point below −15 °C is gathered further down, in “Extreme cold”.
Extreme cold

Below −15 °C: every published number, at its exact temperature

NEEP certifies both units down to −15 °C, at the same temperatures. Lower, each manufacturer publishes its own points: each figure is placed at its exact temperature, with its source. Nothing is calculated between two points.

138%at −15 °C
124%at −21 °C
102%at −26 °C

ORION XLTH: maximum heating capacity as a percentage of the 12,000 BTU/h rated capacity, with 21 °C indoors, per FUJITSU AIRSTAGE brochure FG8153C (revision 4/2025). Vertical line: 100%.

What KINGHOME publishes below −15 °C. Only the NEEP point at −30 °C (7,300 BTU/h, COP 1.51) and a heating range of −30 to 30 °C. The POLARIS R32 submittal sheet, sales brochure and tri-fold brochure give no capacity between −15 and −30 °C. The GREE model with the identical certificate (Glovia) has no public document with these values.
Two figures that cross

Maximum or rated capacity: the order changes with the figure you read

A sheet often shows a single heating capacity. NEEP, however, publishes three at each temperature: the minimum, the rated (the point where the manufacturer has its efficiency measured) and the maximum. For this pair, the last two do not tell the same story.

At maximum capacity, the ORION XLTH is higher at all three shared temperatures: 23,600 against 17,060 BTU/h at 8.3 °C, 18,700 against 15,000 at −8.3 °C, 16,600 against 13,700 at −15 °C. At rated capacity, it is the reverse at −8.3 °C: 15,000 BTU/h for the POLARIS against 10,000 for the ORION XLTH. Each manufacturer chooses where to set its rated point, so a single figure does not sum up a unit.

ORION XLTH FUJITSU AIRSTAGEPOLARIS R32 KINGHOME
● NEEP-certified point · solid line: drawn between certified points, indicativeThe ORION XLTH’s last point is at −26.1 °C: FUJITSU AIRSTAGE states there is no automatic shutoff below that, with no published capacity.

Seasonal efficiency

Over a whole season, the gap shows mainly in heating

SEER2, EER2 and HSPF2 come from the AHRI certificates. They are seasonal averages calculated with the same method for both units, so they compare directly. The higher the figure, the less the unit uses for the same heating or cooling, under those test conditions.

ORION XLTH FUJITSU AIRSTAGEPOLARIS R32 KINGHOME

SEER2

Cooling, whole season

30.5
25.5

EER2

Cooling at 35 °C outside

16.0
14.5

HSPF2 Region IV

Heating, the standard’s reference climate

12.7
10.0

HSPF2 Region V

Heating, colder climate

10.1
8.0

Region V of the HSPF2 standard describes a colder climate than Region IV, closer to a Montréal winter. Both units lose points there, and the heating gap remains: 10.1 against 8.0.

These figures are not converted into dollars on this page. A bill depends on the house, the insulation, the settings and the role given to the heat pump.

Rated COP at −15 °C. For 1 kWh of electricity, the ORION XLTH delivers 2.16 kWh of heat and the POLARIS R32 1.80 kWh, at their respective rated capacities (16,600 and 13,700 BTU/h). At −8.3 °C, the rated COPs are 3.45 and 2.14, but at very different rated capacities (10,000 and 15,000 BTU/h): that COP is therefore read together with the capacity next to it.
To scale

On the wall and on the ground, from the published dimensions

The photos are at the same scale based on the width published by each manufacturer. The ORION XLTH is wider indoors; the POLARIS is wider and deeper outside.

Indoor units, front view

ORION XLTH38 9/16 × 11 × 9 7/16 in · 28 lb
ASUH12KZAS indoor unit to scale
38.56 in
POLARIS R3235.61 × 10.86 × 8.16 in · 20.9 lb
KWP12R32C3I indoor unit to scale
35.61 in

Outdoor units, front view

ORION XLTH31 7/16 × 24 7/8 × 11 7/16 in · 86 lb
AOUH12KZAH1 outdoor unit to scale
31.44 in
POLARIS R3234 3/8 × 21 27/32 × 14 51/64 in · 81.6 lb
KWP12R32C3O outdoor unit to scale
34.38 in

Width × height × depth, per FUJITSU AIRSTAGE brochure FG8153C and the KINGHOME POLARIS R32 sheet. All four photos are at the same scale: 100% of the photo area = 38.56 in. Small framing differences remain possible.

Is your wall wide enough?

Slide to set the free space between two obstacles (window frame, wall corner, furniture). The minimum clearances required around the indoor unit are not included: the installer checks them on site.

40 in

hatched band: obstaclelight area: free space, to scale
Installation

How far can the outdoor unit go?

Slide the piping length between the two units. Below the precharged length, the factory refrigerant is enough; beyond it, each manufacturer specifies an addition from its table; beyond the maximum, the manufacturer does not provide for the installation.

Outdoor unit clearances ORION XLTH

FUJITSU AIRSTAGE installation manual, part 9300793025-01, figure 3.2.1: 4 in behind, 4 in on one side, 10 in on the other, 24 in in front. Top view, diagram.

Outdoor unit clearances POLARIS R32

KINGHOME POLARIS 12K submittal sheet, p. 2: 4 in behind, 4 in on one side, 12 in on the other, 40 in in front, 12 in above, and at least 18 in above the ground for snow and defrost water. The KINGHOME outdoor unit owner’s manual (9,000 to 24,000 BTU models) shows larger values: 30 cm behind and on one side, 50 cm on the other, 200 cm in front. The installer goes with the more cautious one.

Installation ORION XLTH POLARIS R32
Piping length, min. to max. 10 to 82 ft 10 to 131 ft
Precharged length 49 ft 24.6 ft (7.5 m)KINGHOME POLARIS 12K submittal sheet; the brochure rounds to 25 ft. 0.2 oz/ft added beyond.
Maximum indoor–outdoor height difference 66 ft 82 ft (25 m)KINGHOME POLARIS 12K submittal sheet
Liquid – gas diameters 1/4 – 3/8 in 1/4 – 1/2 in
Electrical protectionPer the manufacturer 15 A breaker MOCP 15 A (MCA 13 A)
Power supply 208/230 V 208/230 V
Rated heating rangeOutdoor temperature, per the manufacturer −26 to 24 °C −30 to 30 °C
Rated cooling range −10 to 50 °C −29 to 50 °C
Documented features

What each manufacturer writes, line by line

Only the features named in the manufacturers’ documents are listed: FUJITSU AIRSTAGE brochure and manuals; KINGHOME submittal sheet, brochure and owner’s manuals. “Not published” means the document does not mention it for this model, not that the feature is absent.

Feature ORION XLTH POLARIS R32
Winter
Heating with no automatic shutoff in extreme cold “No lockout”, down to −26 °C No published shutoff temperature; heating rated down to −30 °CKINGHOME POLARIS 12K submittal sheet; shutoff field blank at NEEP
Outdoor unit base pan heating element Yes Yes, plus a compressor heating elementKINGHOME POLARIS 12K submittal sheet; NEEP: 72 W, active below 1 °C or during defrost
Defrost Automatic “Forced defrost” namedKINGHOME POLARIS 12K submittal sheet
Rated capacity at −21 °CPercentage of rated capacity, outside the NEEP certificate; calculation base not specified 124% Not published by the manufacturer
Comfort
Power mode “Powerful” “Turbo Mode”
Economy mode “Economy”, “Energy Saving” “G-AI Energy Saving”
Minimum heat / occupancy mode “Minimum Heat”, “Occupancy” “Heating 8 °C”, “I-feel”; no named occupancy modeKINGHOME POLARIS 12K submittal sheet
Published fan speeds 6 (Quiet to Hi) 7 (Sleep to Turbo), 182 to 424 CFMKINGHOME POLARIS 12K submittal sheet
Airflow direction Automatic vertical, manual horizontal louversBrochure FG8153C Automatic up-down; adjustable left-right, with swing (“3D airflow”)KINGHOME indoor unit owner’s manual
DehumidificationPer the manufacturer 1.9 L/h 1.4 L/h
Automatic restart Yes Not published by the manufacturer
Control and maintenance
Built-in Wi-Fi Yes, AIRSTAGE Mobile app Yes; app not named for this modelKINGHOME POLARIS 12K submittal sheet
Remote control Wireless, backlit, included YBE1FBF infrared, includedKINGHOME POLARIS 12K submittal sheet
Wall controls and 24 V thermostat Optional (KAGAMI, wired, UTY-TTRXZ1) Optional: wired controls XE71-44G, XE74-44E, XE72-44E (Wi-Fi) and 24 V interlock control XE71-00/EKINGHOME POLARIS 12K submittal sheet
BACnet / Modbus Through an optional gateway Not published by the manufacturer
Filter / cleaning Washable filter “Smart cleaning”
Compressor Inverter (type not stated) Triple rotary
The fine grey print give the document each KINGHOME value comes from. The POLARIS R32 submittal sheet and owner’s manuals are published on the KINGHOME Canada site. Automatic restart and a BACnet or Modbus gateway do not appear there.
Sound

The sound of each, according to its manufacturer

FUJITSU AIRSTAGE publishes six named speeds for the ORION XLTH. For the POLARIS R32, KINGHOME publishes two sets of figures that do not match; both are shown.

dB(A)

How to read these figures. dB(A) measures a noise level as the ear perceives it: the lower the figure, the quieter the unit. Each dot is a fan speed published by the manufacturer, from the slowest to the fastest.

Why this is not a ranking. FUJITSU AIRSTAGE measures sound pressure in its own anechoic chamber. KINGHOME publishes neither the distance nor the measurement conditions, and its two documents differ by 10 dB(A). A gap of a few dB(A) can come from the method as much as from the unit.

Indoor unit, in the room

Cooling, every published speed

Outdoor unit, outside

Highest published speed

Measurements taken by each manufacturer using its own method: read them separately, not as a ranking.

Sources: FUJITSU AIRSTAGE brochure FG8153C and technical manual DR_AS233ES; KINGHOME POLARIS sales brochure (20260722) and KINGHOME POLARIS 12K submittal sheet. The 10 dB(A) gap between the two KINGHOME documents is not explained by the manufacturer.

What the data does not say

Four questions to settle at the quote

The room’s heat loss

Certified capacities only matter once compared with the room’s real need in extreme cold. That calculation is what tells whether 13,700 or 16,600 BTU/h at −15 °C changes anything in your home.

The heat pump’s role

Main heating or backup to existing baseboards: the answer changes how much the points below −15 °C matter, and how much coordination with the backup heat matters.

Where the outdoor unit goes

Piping distance, height difference, height above the snow and clearances. The published limits differ: 82 ft for one, 131 ft for the other.

The electrical circuit

Both require 208/230 V and 15 A protection according to the manufacturers. The panel capacity still needs checking.

Reference points for Montréal. The January average at Montréal–Trudeau is −9.2 °C and the average daily minimum −13.5 °C (1991–2020 normals). The winter design temperature is −23 °C (National Building Code, Appendix C). The certified points at −8.3 and −15 °C therefore bracket an ordinary winter; the points at −26.1 and −30 °C describe a cold snap.
Frequently asked questions

Before choosing between these two wall units

Which one keeps more heat at −15 °C?

According to NEEP, the ORION XLTH is certified at 16,600 BTU/h maximum at −15 °C, the POLARIS R32 at 13,700 BTU/h. In both cases, the rated capacity at −15 °C equals the maximum. This is the lowest temperature at which both units are measured under the same conditions.

Why aren’t both measured at −30 °C?

The coldest point published by NEEP is chosen by each manufacturer according to its unit’s range. FUJITSU AIRSTAGE rates the ORION XLTH’s heating down to −26 °C and has it measured at −15 °F (−26.1 °C). KINGHOME rates the POLARIS R32 down to −30 °C and has it measured at −22 °F (−30 °C). No measurement is published for the ORION XLTH at −30 °C, nor for the POLARIS R32 at −26.1 °C.

Why does the POLARIS have a higher rated capacity at −8.3 °C?

Rated capacity is a setting point the manufacturer chooses for the test. KINGHOME set it at 15,000 BTU/h at −8.3 °C, FUJITSU AIRSTAGE at 10,000 BTU/h. The maximum capacities at the same point are 15,000 and 18,700 BTU/h. Both readings are accurate; they answer two different questions.

KINGHOME, is it the same thing as GREE?

At NEEP, the record of the POLARIS R32 (“Glovia” series) and that of the GREE Glovia 12,000 BTU (GWH12BDCXE, AHRI 218338205, record 368049) carry exactly the same certified values, and both are listed under the same manufacturer, Gree Electric Appliances (Zhuhai). Indoor units, remote control, documentation and warranty may differ from one brand to the other.

What changes for the installation?

The POLARIS R32 accepts longer piping (131 ft against 82 ft) and a greater height difference (82 ft against 66 ft), but it is precharged for 24.6 ft against 49 ft for the ORION XLTH. Its published outdoor clearances are larger in front (40 in against 24 in), and KINGHOME requires at least 18 in above the ground.

Are they eligible for rebates?

Eligibility depends on the official list in force on the date of purchase (for example Hydro-Québec’s LogisVert). This page promises no amount; check the current list or ask for it with the quote.

Why aren’t the warranties compared?

Warranty terms vary with the manufacturer, registration and date of purchase. They are set out in the documents each manufacturer publishes.

Certified record

Every AHRI and NEEP value, line by line

Certified value ORION XLTH POLARIS R32
Cooling
Rated capacity at 35 °C 12,000 BTU/h 12,000 BTU/h
SEER2 30.5 25.5
EER2 16.0 14.5
Heating, same conditions
HSPF2 Region IV 12.7 10.0
HSPF2 Region V 10.1 8.0
8.3 °C: min. / rated / max.BTU/h 3,500 / 16,000 / 23,600 3,070 / 12,000 / 17,060
8.3 °C: COP min. / rated / max. 5.13 / 4.64 / 3.07 5.62 / 4.19 / 3.29
−8.3 °C: min. / rated / max.BTU/h 2,200 / 10,000 / 18,700 2,700 / 15,000 / 15,000
−8.3 °C: COP min. / rated / max. 3.39 / 3.45 / 2.44 3.04 / 2.14 / 2.00
−15 °C: min. / rated / max.BTU/h 1,950 / 16,600 / 16,600 2,600 / 13,700 / 13,700
−15 °C: COP min. / rated / max. 3.36 / 2.16 / 2.16 3.17 / 1.80 / 1.80
Coldest point — different temperatures, not highlighted
Test temperature −26.1 °C (−15 °F) −30 °C (−22 °F)
Capacity min. / max.NEEP publishes no rated value at this point 1,400 / 12,200 BTU/h 2,000 / 7,300 BTU/h
COP min. / max. 2.74 / 1.81 2.79 / 1.51
Listings and refrigerant
ENERGY STAR / cold climate Yes / Yes Yes / Yes
AHRI certificate · NEEP record 214888802 · 392122 218451122 · 426104
RefrigerantGWP per the IPCC (AR4); ASHRAE 34 safety class R-32 · GWP 675 · A2L R-32 · GWP 675 · A2L

higher marks the higher value of the same measure taken under the same conditions. It is not a recommendation. Capacities are not highlighted: depending on the point read (minimum, rated or maximum), the order changes.

Both are on the AirGreen website.

To find out which one suits your room, talk it over with our team: bring the room’s dimensions, the planned location for the outdoor unit and your current heating.

Sources and documents

Where every figure on this page comes from

FUJITSU AIRSTAGE, technical manual DR_AS233ES_02January 17, 2025 · section 5-2, ASUH12KZAS heating capacity at −5 °F and −15 °F · consulted November 9, 2026 FUJITSU AIRSTAGE, brochure FG8153C (Canada)Revision 4/2025 · maximum capacity as % of rated at −15, −21 and −26 °C · copy hosted by a distributor Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · estimated operating cost Natural Resources Canada, HOT2000 climate mapMontréal Intl station: 4,167 degree-days (18 °C), −23.1 °C design · consulted November 9, 2026 Fujitsu General America, article on ductless heat pumpsNo mechanical shutoff below the published temperatures · with the “No lockout” wording in brochure FG8153C NEEP, record 392122 (ORION XLTH)AHRI 214888802 · consulted November 6, 2026 NEEP, record 426104 (POLARIS R32, “Glovia” series)AHRI 218451122 · consulted November 6, 2026
ENERGY STAR directory (data.energystar.gov, dataset 83eb-xbyy)Both certificates listed, cold climate: yes · consulted November 6, 2026
FUJITSU AIRSTAGE, ORION XLTH brochure (French)Part FG8153D, rev. 4/2025 · English version FG8153C
FUJITSU AIRSTAGE, installation manual and technical manualPart 9300793025-01, § 3.2.1 (clearances) · DR_AS233ES (sound measurement conditions)
KINGHOME, POLARIS R32 technical sheet (French)Undated, unnumbered · English version available KINGHOME, POLARIS 12K submittal sheetUndated · piping, clearances, features, controls, sound by speed KINGHOME, POLARIS sales brochure20260722 · sound pressure 27 to 47 dB(A)
KINGHOME, POLARIS R32 owner’s manualsIndoor and outdoor units, KWP09 to 24R32C3 · airflow direction, clearances
NEEP, record 368049 (GREE Glovia)AHRI 218338205 · same values as record 426104 · consulted November 6, 2026
Montréal climate1991–2020 normals, Montréal–Trudeau (ECCC) · National Building Code of Canada, Appendix C