Home / Comparisons / 3-ton central heat pumps
TCL APEX XS and MIDEA EVOX G3, two 3-ton central systems side by side
Two 3-ton central heat pumps offered by AirGreen, both ENERGY STAR cold climate per NEEP. The TCL APEX XS runs on R-32 and its outdoor unit comes in white or black; the MIDEA EVOX G3 runs on R-454B. NEEP tests them at the same four temperatures, from 8.3 °C to −30 °C.


APEX XS 3 tons
H36APH20UDE / H36SDH20XQC · AHRI 218453817

What the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 36,000 BTU/h house in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference. Both systems are certified at 36,000 BTU/h in cooling.
How this amount is calculated
- Heat needed over the winter. A house whose heat loss reaches 36,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: a simplification that ignores the recovery after a setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup planned for when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 36,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. The network access fee, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, insulation, settings and use; this amount is not a promise.
Outside, on the same pad: height, width and floor space
The APEX XS outdoor unit is the lower of the two and the lighter. The EVOX G3 outdoor unit is taller and takes up less ground area. The dashed frames are drawn to the dimensions published by each manufacturer, at the same scale.



Outdoor unit height
Ground area, width × depth
Outdoor unit net weight
Indoor unit height
Front view: frames at the published width and height, to scale; each photo is placed in its frame and remains a photo taken in perspective. Views from above: diagrams to scale, drawn by AirGreen from the dimensions and the clearance figure in each installation manual. Ground area calculated by AirGreen: width × depth ÷ 144. Sources: TCL H36SDH20XQC / H36APH20UDE submittal sheet and TCL APEX XS installation manual (p. 22); MIDEA MAUSE-H36B-2A / MO1SE-H36B-2A submittal sheet and MIDEA EVOX Extreme Heat installation manual (p. 12, fig. C-1). Both APEX XS finishes carry the same model number, H36SDH20XQC.
Four certified temperatures, placed on the same thermometer
For each unit, NEEP publishes test points at 8.3 °C, −8.3 °C, −15 °C and −30 °C. Each point on the chart is a value from the certificate; the dotted lines link each unit’s points, and nothing is measured between two points.
At −30 °C, the certificate gives a minimum capacity and a maximum capacity, with no rated value: the “Rated capacity” view therefore stops at −15 °C. The COP shown is the one NEEP publishes at the maximum capacity of each point.
Below −15 °C: every published figure, at its exact temperature
NEEP certifies both units at −15 °C and at −30 °C, the same temperatures: those two rows compare directly. Neither TCL nor MIDEA publishes a capacity table between those two points for these combinations; at the temperatures in between, the page gives the range between the two certified points and what each manufacturer writes.
What each manufacturer writes, row by row
TCL APEX XS submittal sheet, specification sheet and installation manual; MIDEA EVOX G3 submittal sheet, installation manual and leaflet. Each row repeats what the manufacturer writes.
APEX XS: variable-speed rotary MTH420UKQC8FU (submittal sheet).
EVOX G3: twin-cylinder rotary EKPQ420D1UMUA; “M-Powevi” vapour injection in extreme cold (leaflet).
APEX XS: heating stated down to −30 °C; automatic defrost lasting 2 to 10 minutes (installation manual).
EVOX G3: heating stated down to −30 °C; enhanced defrost setting; base pan and crankcase heaters included as standard (submittal sheet, manual).
APEX XS: 1/2 HP ECM motor; 1,200 CFM in Turbo mode; constant airflow up to 0.8 in w.c.
EVOX G3: 5 speeds, 971 to 1,236 CFM; constant airflow up to 1.0 in w.c.
APEX XS: compatible with 24 V thermostats; RS485 wall controller for the dehumidification, energy-saving and sleep functions (specification sheet).
EVOX G3: MIDEA 120N wall controller, offered with built-in Wi-Fi, a wireless remote or another manufacturer’s 24 V thermostat (submittal sheet).
APEX XS: vertical upflow, downflow or horizontal mounting; automatic detection of 115 V or 230 V.
EVOX G3: horizontal mounting, left or right, or vertical, up or down; compatible with 115 V and 230 V.
APEX XS: 5, 10 or 15 kW element (specification sheet).
EVOX G3: three-stage kit, up to 25 kW (submittal sheet, leaflet).
The sound of each one, per its manufacturer
TCL and MIDEA publish the sound of the indoor unit and of the outdoor unit. TCL speaks of sound pressure; MIDEA writes “Noise Level”. Neither document states the distance or the measurement method: read the values separately.
How to read these numbers. dB(A) measures noise level as the ear perceives it: the lower the number, the quieter the unit. Each dot is a value published by the manufacturer.
Why this is not a ranking. Two manufacturers, two documents, with no distance or measurement method stated. Different or unknown method: not comparable.
Indoor unit, in the basement or a closet
Published values
TCL publishes a single value for the indoor unit; MIDEA publishes one per fan speed.
Outdoor unit, outside
Published values
TCL publishes two values, “55 / 64”, without saying what each one corresponds to; MIDEA publishes one.
Measurements taken by each manufacturer with its own unstated method: read them separately, not as a ranking.
In the basement, then along the piping
Indoor units, height and width to scale

Frames to scale, drawn at the published width and height. The TCL unit is a photo placed in its frame. MIDEA does not publish a stand-alone photo of the MAUSE-H36B-2A: it is shown as a diagram. Depth: 21 in and 21 1/2 in. Weight: 134.2 lb and 149 lb.
Line-set length and refrigerant to add
AirGreen calculation from the submittal sheets: length beyond the 25 ft precharged × 0.27 oz per foot (TCL, R-32) or 0.7 oz per foot (MIDEA, R-454B). Maximum published length: 164 ft (TCL) and 246 ft (MIDEA). The TCL manual asks for a line set of at least 15 ft.
| Installation | APEX XS | EVOX G3 |
|---|---|---|
| Maximum piping length | 164 ftTCL submittal sheet and installation manual. | 246 ftMIDEA submittal sheet and installation manual, rev. 5. |
| Precharged length | 25 ft0.27 oz of R-32 per foot beyond. | 25 ft0.7 oz of R-454B per foot beyond. |
| Maximum height difference | 98 ft | 98 ft98.4 ft per the installation manual. |
| Liquid – gas line diameters | 3/8 – 3/4 in | 3/8 – 3/4 in |
| Outdoor unit W × H × D, weight | 43 1/8 × 33 3/4 × 19 7/16 in, 165 lb | 38 9/16 × 38 3/8 × 16 3/8 in, 204 lb |
| Indoor unit, weight | 21 × 46 7/16 × 21 in, 134.2 lb | 17 1/2 × 58 1/8 × 21 1/2 in, 149 lb |
| Minimum clearances, unit alonebehind · sides · front | 3.94 in · 3.94 and 11.81 in · 39.37 inTCL manual, p. 22, walls on three sides. | 4 in · 4 and 14 in · 20 inMIDEA manual, fig. C-1; 20 in at the front when two of the other three sides are clear. |
| Electrical protectionoutdoor unit, 208/230 V | MCA 30 A · MOP 50 AIndoor unit: MCA 5 A, MOP 15 A. | MCA 29 A · MOP 30 AIndoor unit: MCA 6 A at 208/230 V, MOP 15 A. |
| Factory refrigerant charge | 105.8 oz of R-32 | 127 oz of R-454B |
| Dehumidification | 4 pints per hourTCL specification sheet. | 3.41 litres per hourMIDEA submittal sheet. |
| Stated heating / cooling range | −30 to 27 °C / −15 to 55 °C | −30 to 24 °C / −30 to 50 °C |
Sources: TCL “Apex XS Series Unitary HP + Advantage P Series AHU” submittal sheet, TCL “APEX XS & Auto Voltage AHU” specification sheet and TCL APEX XS installation manual; MIDEA “Extreme Heat AHU Series” submittal sheet and MIDEA EVOX Extreme Heat installation manual. The TCL specification sheet prints 33 3/8 in for the outdoor unit height, next to 858 mm: the page follows the 858 mm and the submittal sheet, that is, 33 3/4 in. Both manuals ask that the unit be protected from snow; the MIDEA manual asks that it be mounted at least 11.8 in above the expected snow.
What people ask about these two central systems
Where do the two systems differ the most?
At −30 °C. NEEP certifies a maximum of 18,800 BTU/h for the APEX XS and 27,600 BTU/h for the EVOX G3, at the same temperature. At −15 °C, the certified maximum capacities are 36,000 and 37,400 BTU/h.
Do the white and the black APEX XS have the same values?
Both finishes offered by AirGreen carry the same model number, H36SDH20XQC. The TCL specification sheet gives a single set of values and a single AHRI certificate for this model, 218453817.
Which one takes up less space outside?
It depends on the measure. The APEX XS outdoor unit is 33 3/4 in high and the EVOX G3 outdoor unit, 38 3/8 in. On the ground, the APEX XS takes up 43 1/8 × 19 7/16 in and the EVOX G3, 38 9/16 × 16 3/8 in. The clearances each manual asks for are added to that; they are drawn in the section “The footprint”.
R-32 or R-454B, what does it change?
Both refrigerants are class A2L under the ASHRAE 34 standard. Their global warming potential per the IPCC (AR4) is 675 for R-32 and 466 for R-454B. Our page R-32 or R-454B covers both in detail.
Is the winter cost very different?
The estimated cost uses Region V HSPF2, 8.0 for the APEX XS and 8.2 for the EVOX G3: the yearly gap shown above follows from that. In summer, both have the same SEER2, 18.0, so the same estimate.
Which one makes less noise?
TCL publishes 57 dB(A) for the indoor unit and “55 / 64” dB(A) for the outdoor unit; MIDEA publishes 33 to 48 dB(A) depending on the speed for the indoor unit and 63 dB(A) for the outdoor unit. No document states the method: these numbers cannot be used to rank the units.
Are they eligible for rebates?
Per NEEP, both combinations are ENERGY STAR and ENERGY STAR cold climate. Eligibility depends on the official list in force on the date of purchase; this page promises no amount.
All the AHRI and NEEP values
| Certified value | APEX XS | EVOX G3 |
|---|---|---|
| Cooling | ||
| Rated capacity at 35 °C | 36,000 BTU/h | 36,000 BTU/h |
| SEER2 | 18.0 | 18.0 |
| EER2 | 11.0 | 12.0 |
| Heating, same conditions | ||
| HSPF2 Region IV | 9.5 | 10.0 |
| HSPF2 Region V | 8.0 | 8.2 |
| 8.3 °C: min. / rated / max.BTU/h | 22,800 / 36,000 / 45,000 | 11,400 / 37,000 / 47,000 |
| 8.3 °C: COP min. / rated / max. | 4.51 / 3.60 / 3.50 | 4.45 / 3.50 / 3.27 |
| −8.3 °C: min. / rated / max.BTU/h | 22,000 / 36,000 / 36,000 | 11,000 / 33,000 / 41,500 |
| −8.3 °C: COP min. / rated / max. | 2.60 / 2.30 / 2.30 | 2.58 / 2.50 / 2.21 |
| −15 °C: min. / rated / max.BTU/h | 22,800 / 36,000 / 36,000 | 8,900 / 37,400 / 37,400 |
| −15 °C: COP min. / rated / max. | 2.00 / 1.85 / 1.85 | 2.16 / 1.90 / 1.90 |
| Coldest point — same temperature for both | ||
| Test temperature | −30 °C (−22 °F) | −30 °C (−22 °F) |
| Min. / max. capacity | 18,800 / 18,800 BTU/h | 4,700 / 27,600 BTU/h |
| COP at maximum capacity | 1.20 | 1.56 |
| Listings and refrigerant | ||
| ENERGY STAR / cold climate (NEEP) | Yes / Yes | Yes / Yes |
| AHRI certificate · NEEP record | 218453817 · 505368 | 215471343 · 387396 |
| RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class | R-32 · GWP 675 · A2L | R-454B · GWP 466 · A2L |
higher marks the higher value of the same measure, under the same conditions. It is not a recommendation. Capacities and COPs at each point are not highlighted; they are compared in “From 8 to −30 °C” and “Extreme cold”. When a TCL or MIDEA document departs from the certificate (TCL, for example, writes a maximum of 46,000 BTU/h at 8.3 °C, and a COP of 2 at −15 °C in its submittal sheet), the page follows the certificate.
Both are on the AirGreen website.
To choose for your home, talk it over with our team: bring the heated floor area, the condition of your ducts and the spot planned for the outdoor unit.
Where every figure comes from
Data verified on November 9, 2026. Performance: AHRI certificates and the NEEP database. Dimensions, sound, piping, clearances and features: per each manufacturer. When a source contradicts the AHRI certificate, the certificate prevails.
Trademarks. TCL, APEX XS, MIDEA and EVOX are trademarks of their respective owners. Logos are used only to identify the products compared. AirGreen is a dealer for these brands; this page is not produced, sponsored or endorsed by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong to you? Write to us : every reported figure is checked again.