Fantech ERV SER 1300 Air Exchanger | Montreal, Laval, Longueuil, South Shore and North Shore

In stock
SKU: SER 1300
ERV
01 · Good to know

What you should know about this one

Published, verifiable facts, not brochure claims.

1300 cfmHighest airflow in the SER series: 1300 cfm at 0.4 in

The brochure gives 1300 cfm at 0.4 in for the SER 1300, versus 1179 cfm for the SER 1100, drawing 10.8 A at 120 V and weighing 208 lb. Its heating effectiveness is 54% sensible and 35% latent (AHRI 1060).

RailsMotors and core mounted on removable sliding rails

The supply and exhaust fan motors and the core are mounted on removable sliding rails for quick access. The door panels are reversible so they can open on the side where service is done.

ExhaustIt defrosts by pausing the fresh air for a few minutes

In cold weather, the supply fan stops for a few minutes while the exhaust keeps running, so warm indoor air thaws the core. During the cycle the house is briefly under negative pressure; if you have a fireplace or a naturally vented combustion appliance, mention it to our estimator.

ERVIt moves moisture too, not just heat

An ERV transfers some moisture between the two airstreams. Useful in a house that gets too dry in winter or takes on a lot of humidity in summer. The trade-off: it generally recovers less heat than a comparable HRV.

02 · Installation

What it needs on site

208 lbUnit weight
120 VPower supply

In a condo with no floor drain, or with little ceiling clearance, we usually look at a side-port model instead. Our estimator checks the location, the drain and the duct route before ordering.

Complete spec sheetData and cited sources
Type
ERV
Defrost cycle
Exhaust only (supply fan off)
Filters
MERV 3 filters (exhaust and supply); MERV 8 or MERV 13 upgrade
Weight
208 lb
Power supply
120 V
Spec sheet (French)
PDF
Spec sheet (English)
PDF

The manufacturer doesn't publish an efficiency at −25 °C for this model; we don't make one up.

Talk to an HVAC technician before you choose

We calculate the airflow room by room, check the location and the drain, and give you an installed price. Balancing is measured at commissioning, not estimated.

Fantech SER 1300: the highest airflow in the SER series

The Fantech SER 1300 sits at the top of the SER series: Fantech's brochure gives it 1,300 cfm at 0.4 in. This light commercial energy recovery ventilator is aimed at schools, gyms, neighbourhood performance halls and good-sized air-conditioned stores, with a 120 V power supply.

The Fantech SER 1300 is not listed in the HVI directory, which rates residential units. It has no certified net airflow to compare with a residential model: instead, we start from the building's ventilation calculation to check that it is suitable.

1,300 cfm, 10.8 A and 208 lb

The brochure gives 1,300 cfm at 0.4 in. for the SER 1300, versus 1,179 cfm for the SER 1100, with 10.8 A on 120 V and 208 lb. It therefore draws slightly less current than the SER 1100 while moving more air. Its power is 1,300 W, or about 1.0 cfm per watt at 0.4 in.

Efficiency

Its heating efficiency is 54% sensible and 35% latent, for 50% total; in cooling, 51% sensible, 32% latent and 49% total, according to the brochure's AHRI 1060 data.

Motors and core on sliding rails

The fresh air and exhaust air fan motors, as well as the core, are mounted on removable sliding rails for quick access. The door panels are reversible so they open on the side where maintenance is done. Defrost shuts off the fresh air fan to keep the core from freezing; the BPM recirculation option is reserved for the SHR units.

Fantech also offers the ECO-Touch IAQ control, which detects volatile organic compounds and automatically increases airflow when air quality drops.

Installation: weight, and data the brochure does not publish

The SER 1300 weighs 208 lb; the suspension or platform must be designed accordingly.

Fantech's brochure is the only document we have for the SER series. It gives neither the cabinet dimensions, nor the position of the connections, nor the drain requirements. We confirm these points with the manufacturer before planning the installation of the Fantech SER 1300.

Fantech presents the SHR and SER as complete air handling solutions: supply and exhaust fans, filters, core and integrated control system. Their compact footprint makes it possible to fit the SER 1300 in a mechanical room where floor space is limited.

ERV or HRV: what makes the difference

In an air-conditioned or heavily occupied space, humidity matters as much as temperature: that is where an ERV makes more sense than an HRV. The enthalpy core limits the moisture that fresh air brings in during the summer. If, on the contrary, your premises produce a lot of moisture in winter, we compare with an SHR from the same series.

Filter maintenance

The Fantech SER 1300 comes with MERV 3 filters on the fresh air and stale air streams. Fantech describes them as starter filters, able to capture about 20% of particles from 3 to 10 microns. A MERV 8 filter captures 70% of these particles and a MERV 13, 95%: that is the upgrade to consider near a busy road.

Warranty

The Fantech documents we have do not specify the warranty for the SER series. We send you the manufacturer's terms for the Fantech SER 1300 with the quote.

Installation by AirGreen in Greater Montreal

We do not sell an ERV at random. For a school, a gym or an air-conditioned store, the starting point is the building's ventilation calculation; for a large residence, it is the room-by-room calculation set out in the CSA F326 standard. We then compare that airflow with the curve of the Fantech SER 1300 and with the pressure of your duct system.

At commissioning, we balance both airstreams to the calculated airflow. This adjustment is what makes a unit actually provide the ventilation it is supposed to, without depressurizing the building. We then show the person in charge of the building how to adjust the speeds and when to clean the filters.

AirGreen serves Montreal, Laval, Longueuil, the North Shore and the South Shore. Free quote: 514 316-2973 or sales@airgreen.ca.