Lifebreath 2500ERV-IFD ERV Air Exchanger | Montreal, Laval, Longueuil, South Shore and North Shore
What you should know about this one
Published, verifiable facts, not brochure claims.
IFDIndoor version: four 24 × 16 in connections
The 2500ERV-IFD installs indoors, set on the floor or hung from threaded rods (not provided), with four 24 × 16 in connections. Lifebreath states that various duct configurations are available, whereas the rooftop 2500ERV-EFD connects from underneath.
42 inPanels on both sides, 42 in clear on the electrical side
Removable service panels are on both sides of the cabinet and the membrane core slides out of either side. Lifebreath calls for 42 in of clearance on the electrical-panel side.
ExhaustIt defrosts by pausing the fresh air for a few minutes
In cold weather, the supply fan stops for a few minutes while the exhaust keeps running, so warm indoor air thaws the core. During the cycle the house is briefly under negative pressure; if you have a fireplace or a naturally vented combustion appliance, mention it to our estimator.
ERVIt moves moisture too, not just heat
An ERV transfers some moisture between the two airstreams. Useful in a house that gets too dry in winter or takes on a lot of humidity in summer. The trade-off: it generally recovers less heat than a comparable HRV.
5 yearsThe core warranty
The core does the work and is the most expensive part to replace. Motors and parts: 2 years.
What it needs on site
In a condo with no floor drain, or with little ceiling clearance, we usually look at a side-port model instead. Our estimator checks the location, the drain and the duct route before ordering.
Complete spec sheetData and cited sources
- Type
- ERV
- Condensate drain
- Required
- Defrost cycle
- Exhaust only (supply fan off)
- Filters
- 4 pleated 4 in filters (18 × 24 in), 2 per airstream
- Weight
- 680 lb
- Power supply
- 220 V
- Warranty — core
- 5 years
- Warranty — motors
- 2 years
- Warranty — parts
- 2 years
- Spec sheet (French)
- Spec sheet (English)
The manufacturer doesn't publish an efficiency at −25 °C for this model; we don't make one up.
Talk to an HVAC technician before you choose
We assess your needs on site, check the location and the drain, and give you an installed price. Balancing is measured at commissioning, not estimated.
Lifebreath 2500ERV-IFD: the big ERV for the mechanical room
The Lifebreath 2500ERV-IFD packs into an indoor unit what it takes to ventilate a large air-conditioned building: 2,000 cfm according to its spec sheet, with 1.0 in. of external static pressure, and a core that passes heat and water vapour from the outgoing air to the incoming air. This commercial ERV is aimed at schools, sports centres, offices and stores that have a mechanical room, or a ceiling space strong enough for its 680 lb.
The HVI directory does not list the 2500ERV-IFD, so no certified net airflow allows a comparison with a residential HRV. The values below are those Lifebreath publishes on the unit's spec sheet and in its installation manual.
IFD: Indoor, Four 24 × 16 in. Connections
As with the rooftop version, the name can be read on the spec sheet: fan defrost, interior installation. The 2500ERV-IFD sits on the floor or hangs from threaded rods and brackets, to be supplied by the installer, and connects through four 24 × 16 in. (610 × 406 mm) openings. Lifebreath states that various duct configurations are available, whereas the rooftop 2500ERV-EFD connects from underneath; we choose the one that follows the duct route in your building.
Its 22-gauge G60 galvanized steel panels are powder-coated, and the 16-gauge galvanized frame is lined with 1.0 in. of fibreglass against condensation. Two stainless steel pans, with 1/2 in. (12 mm) NPT drain spouts, collect the defrost water; Lifebreath calls for raising the unit high enough to slope the drain lines. During defrost, whose duration is set at the factory, the fresh-air motor stops and the stale air warms the core.
Airflow and Efficiency
At 1.0 in. of external static pressure, the spec sheet gives 2,000 cfm, and the product page lists 2,000 cfm at 0.6 in. Lifebreath also gives 58% efficiency at 2,500 cfm, without specifying the test conditions. The single core, a cross-flow enthalpy core certified by AHRI (68-2501), comes out of either side of the cabinet.
Power and Controls
Two 1.0 HP single-shaft PSC motors, with three speeds of which two are available, drive two direct-drive centrifugal blowers, one per airstream. The unit is ordered in 208 V or 240 V single-phase; for the amperage, minimum circuit ampacity and protection, the nameplate of the unit delivered is what counts. According to Lifebreath, the 208 V version requires a special inspection. A two-speed remote control can be added as an option, and the built-in microprocessor board has its own interlock contacts.
Installation: Weight and Clearance
At 680 lb (308 kg), or 35 lb less than the rooftop version, the 2500ERV-IFD needs a floor or a hanging structure that is up to the job. The cabinet opens on both sides through removable panels, and 42 in. of clear space is needed on the electrical panel side: that clearance, more than the unit itself, often decides where it goes. Lifebreath also requires a heated space where the surrounding air stays at 16°C (60°F) or above.
2500ERV-IFD or 2500ERV-EFD: Indoors or on the Roof
The two versions share the 68-2501 core, the 1.0 HP PSC motors and the 2,000 cfm at 1.0 in. The IFD fits when a heated mechanical room can take it with its 42 in. of clearance; the EFD, when only the roof has room, with its built-in hoods and its roof curb. Lifebreath states that this series conforms to CSA and UL standards.
Filter Maintenance
Four 4 in. pleated filters, 18 × 24 in., two per airstream; the spec sheet does not give their MERV rating. The 2500 series manual has them inspected and replaced as needed, calls for checking that the condensate drains freely and forbids washing the core: it is removed to be vacuumed or blown clean with low-pressure air. We replace the filters at each service and check the core on the same visit.
Warranty
Manufacturer's warranty: 5 years on the 2500ERV-IFD core, 2 years on replacement parts. Lifebreath does not publish a separate term for the motors.
Installation by AirGreen in Greater Montreal
Before recommending the 2500ERV-IFD, we assess your space's ventilation needs on site. At the same time, we look at the available space, the electrical supply and the duct route.
Outdoors, the two hoods we install follow the 2500 series manual: at least 10 ft (3 m) between them, at least 18 in. (46 cm) of height above the snow or the ground, 1/4 in. mesh against birds and rodents, an air velocity of no more than 1,000 ft/min to limit water entry, and a caulked perimeter. At start-up, we measure the fresh air and the exhaust air, then equalize them, as Lifebreath requires.
Ask for a quote: 514 316-2973 or sales@airgreen.ca. We will call you back, and our team, under AirGreen's RBQ licence 5645-9605-01, works in Montreal, Laval, Longueuil, the North Shore and the South Shore.