Kinghome Rooftop R410A 3-Ton Packaged Heat Pump | Montréal, Laval, Longueuil, South Shore and North Shore
A rooftop packaged unit chosen first for the cooling load
In a professional office, a clinic, a hair salon or a small neighbourhood store, heat comes from inside as much as from outside: the occupants, the lighting, the computers, the equipment. As a result, these spaces often need more cooling than heating, and it's the summer load that decides the capacity. The KRH03TCU, a 3-ton rooftop packaged heat pump, fits that profile. It sits on the building's flat roof, connects to the space's ducts and completely frees up floor space and the façade.
This light commercial unit also suits a top-floor apartment in a Montréal plex when the on-site assessment of heating and cooling needs justifies it, especially in an apartment with a lot of south-facing glass.
Reading the published capacities correctly
The unit is certified at 17.8 SEER2, 8.8 HSPF2 and an EER2 of 11. In heating, the capacities listed on NEEP (AHRI No. 213685845) are as follows:
- At -8.3 °C: 23,400 BTU/h, with a COP of 2.46
- At -15 °C: 26,000 BTU/h, with a COP of 1.75
- At -30 °C: 20,800 BTU/h, with a COP of 1.33
These values deserve some honest context. The certified capacity at -8.3 °C is the same as the two-ton model's; what sets the three-ton apart in winter is its better COP at that test point (2.46) and slightly higher capacities at -15 °C and -30 °C. At -15 °C, it delivers 72% of its nominal capacity of 36,000 BTU/h. In practice, we recommend this model when cooling dictates the capacity, and we make sure the space's heating load is still covered by these figures, with electric backup heat in the ducts if the on-site assessment of heating needs calls for it. The figures are published as ENERGY STAR and NEEP report them. The heating range goes down to -30 °C, and the unit carries the ENERGY STAR cold climate designation (ID 2842328).
Cooling an occupied space
A SEER2 of 17.8 and an EER2 of 11 put this unit well above the old fixed-speed rooftop units we replace on small commercial buildings. The inverter rotary compressor modulates its speed: when the business opens, it ramps up to bring the temperature down, then slows down and holds the set point without on-off cycling. That steady low-speed operation also removes humidity better, which clinic or salon customers notice right away in July.
Packaged unit: the whole circuit in one cabinet
The compressor, coils and fans are housed in a single assembled cabinet, charged with R-410A and sealed at the factory. There's no refrigerant line to run through the building and no indoor unit to find room for in the space, which frees up floor space and simplifies the work in a business that stays open. The duct connection can be horizontal or downflow. The outdoor coil gets a Golden Fin anti-corrosion treatment, the unit has been salt-spray tested, and the smart defrost adapts to actual conditions. Control is through a conventional low-voltage thermostat or by digital communication. The published sound level is 65 dB(A), and the dimensions are 44.00 x 35.44 x 49.25 inches, the same footprint as the two-ton model.
Maintaining a rooftop unit
A rooftop packaged unit is serviced entirely from the outside, without disturbing customers or moving furniture. In spring, we clean the outdoor coil, check the condensate drain and its trap, and replace the filters; in fall, we check the defrost and the electrical connections before the cold season. In a commercial space, where the filter clogs faster than at home because of foot traffic and doors that are often open, we adjust how often it's replaced based on actual use. A clean coil and a clear filter keep cooling capacity up just when summer heat and peak traffic add up.
What we check before installation
Here is what we validate during a building visit in Montréal, Laval, Longueuil, on the North Shore or on the South Shore.
The on-site assessment of heating and cooling needs
We assess the space's cooling needs and heating needs on site, separately: occupancy, equipment, lighting, glazing, roof insulation. If heating calls for more than the certified capacities cover, we plan the necessary backup heat, or we recommend the four-ton model.
Roof structure and access
We check the roof's load-bearing capacity at the planned location, the condition of the membrane and the roof curb. The unit is lifted by crane or hoist, and we schedule this around the business's opening hours. Enough clearance is left around the unit for maintenance.
Electrical supply
The unit requires a 220 V single-phase supply, an MCA of 35 A and a maximum overcurrent protection (MOP) of 40 A. In a small commercial building, we check which panel the unit will be tied into, and therefore which meter. A disconnect is installed near the unit on the roof.
Drain, snow and ducts
The condensate drain is connected with a trap to a roof drain. The curb keeps the unit above the snow buildup, and we take prevailing winds into account. Ducts exposed to the cold are insulated, and the connections at the roof curb are sealed.
LogisVert assistance
This unit is on Hydro-Québec's LogisVert list with an indicative amount of $2,808; eligibility is confirmed on the installation date. Only Hydro-Québec confirms the assistance granted. The program targets residential buildings: an apartment in a plex may be eligible, while a commercial space generally is not. The file references are AHRI 213685845 and ENERGY STAR ID 2842328.
Why go with AirGreen
- Salaried refrigeration technicians who plan the work around your opening hours.
- Civil liability insurance of $5,000,000, something commercial building owners ask about.
- Warranty registration handled by us.
- After-sales service for periodic maintenance on the roof.
Request your free estimate for the 3-ton rooftop packaged unit: we assess your space's heating and cooling needs on site, check the roof and the panel, then give you a detailed quote.
Documentation
Warranty: 5 years on the compressor and 7 years on parts, on registered models, according to the Kinghome brochure.