Packaged Heat Pump System York PH3 4 Ton Three-Phase | Montreal, Laval, Longueuil, South Shore and North Shore

In stock
SKU: PH3E48N00S31
Serial Number (Exterior): PH3E48N00S31
Tonnes: 4 T
Cooling Capacity: 48,000 BTU
Energy Star: No
SEER: 13.4
HSPF: 6.7
CFM: 1700.0
Sound Pressure Level: 72.0 dB(A)
Gas (Freon): R-454B
Dimensions (L x W x H): 45.75 x 51.25 x 50
Manufacturer's Warranty (Compressor - Coil - Parts): 10-10-10

Common areas and small offices: a reliable heat pump, simple to maintain

Entrance hall, corridors, community room, ground floor offices in a mixed-use building: the common areas of a plex or a small building have to stay comfortable without becoming a headache for the owner or the manager. The 4 ton YORK PH3 heat pump in the 208/230 V three-phase version suits this kind of assignment particularly well: 48,000 BTU/h of nominal capacity, proven construction, easy service access and straightforward control. We install it for owners, condo boards and building managers across the greater region: Montreal, Laval, Longueuil, the North Shore and the South Shore.

Why a packaged unit in a building

A packaged heat pump concentrates the whole refrigeration system and the supply fan in a single cabinet, set on the roof or at ground level. The ducts carry the conditioned air into the common areas, then bring it back to the unit. No mechanical room to build, no indoor unit to fit into a corridor closet, and above all no need to enter the apartments for maintenance: the technician works outside, at the time that suits the building.

Reliability starts at the factory

The PH3 units are assembled in a plant whose quality management system is ISO 9001:2015 certified. Every unit is fully wired, charged with R-454B refrigerant and tested before shipping on computerized test stations. The refrigerant charge and the component numbers are verified by barcode scanning during assembly, and the run test data, such as the system pressures and the motor currents, is recorded. On request, this data can be retrieved from the serial number, an advantage for anyone who keeps a maintenance log. The unit is CSA certified to the UL 60335-2-40 and CAN/CSA-C22.2 No 60335-2-40:22 standards.

The standard protections

  • Hermetic scroll compressor whose internal protection combines a high pressure relief valve and a temperature sensor, which shut it down if operating conditions become inadequate;
  • high pressure switch that locks the unit out under abnormal conditions, until it is reset;
  • loss of refrigerant pressure switch, supplied with the unit, for a safe compressor shutdown;
  • totally enclosed outdoor fan motor, internally protected against overloads;
  • filter drier or strainer to catch the impurities in the refrigeration circuit, and refrigerant detection (RDS) built in at the factory.

Service access designed for technicians

Every major component has its own access panel: compressor, indoor coil, fan, controls, electric heat kit and filters. The electrical box is not housed in the compressor compartment, and the controls are mounted so that their panel can be removed for diagnostics without disturbing the normal system pressures. The fan assembly and the indoor coil assembly slide out of the cabinet for cleaning. According to YORK, no special training is required to replace a component, and the number of unique parts has been reduced, which makes sourcing easier.

The data for the 4 ton three-phase PH3

Data Value What it means
Model PH3E48N00S31 YORK LX series, three-phase version
Net cooling (AHRI) 48,500 BTU/h Net cooling capacity, fan heat deducted
Heating at 47 °F (8.3 °C) 47,000 BTU/h, COP of 3.7 Heating performance in mild weather
Heating at 17 °F (-8.3 °C) 28,600 BTU/h Capacity kept in cold weather, before the electric backup
Efficiency SEER2 of 13.4, HSPF2 of 6.7 and EER2 of 11.1 Ratings established under the requirements of the United States Department of Energy (DOE) and the AHRI methods
Nominal airflow 1,700 CFM (ft³/min) Volume of air delivered to the areas served
Power supply 208/230 V three-phase, 60 Hz Direct connection to the building's three-phase service
Dimensions (W x D x H) 45.75 in. x 51.25 in. x 50 in. Width, depth and height of the cabinet
Operating weight 482 lb Useful figure for checking the roof
Sound level (AHRI 270) 72.0 dBA Standardized sound rating of the unit

Straightforward control

No complex programming to pass on to the caretaker: the PH3 is driven by a 24 V standard thermostat, either an electronic model that does not draw its power from the control circuit, or an electromechanical model, single stage in heating as in cooling. The thermostat wires land on the screw terminals of the refrigerant detection system. Inside, the cooling controls rely on a contactor and relays, the connectors are the MATE-N-LOK type, and all the internal wiring is colour coded and numbered. A status and diagnostic indicator light on the board, along with a demand defrost control with preloaded curves, round out the package.

Power supply and backup heat in three-phase

Without a heat kit, the 4 ton three-phase PH3 calls for a circuit with a minimum circuit ampacity of 24.5 A, protected at 35 A maximum by an HACR breaker or a time-delay fuse, plus a field-supplied disconnect switch. Three three-phase 6HK kits are planned for this model, of 10, 15 and 20 kW. The last one heats in two stages, delivers 17.6 kW at 230 V and includes its own breakers. Single point wiring kits (S1-2SPWK032, S1-2SPWK034 or S1-2SPWK035, depending on the kit chosen) allow a single power supply.

What we check at every maintenance visit

  1. Replacement of the 1 in. filters, housed in the filter rack supplied with the three-phase models;
  2. inspection and cleaning of the indoor coil and the blower wheel, pulled out of their housing if needed;
  3. cleaning of the outdoor coil and check of its protective grille;
  4. check of the condensate pan and drain, whose 3/4 in. NPT connection is rigidly fixed;
  5. check of the electrical connections, the pressures and the operation in heating as in cooling.

The bearings on the indoor fan motor and the outdoor fan motor are lubricated for life: they call for no annual lubrication, which shortens the task list by that much.

A single point of contact for the installation and the maintenance of your buildings

An HVAC contractor based in Montreal, AirGreen inc. sells, installs and maintains. For an owner or a manager, that means a single team from start to finish. It all begins with a free on-site estimate: a review of the areas to be served, of the duct system, of the three-phase electrical service and of the location on the roof or at ground level. We calculate the load, prepare a clear quote, coordinate the lift and the access with you, then our crews install and commission the unit. After that, we can schedule the periodic maintenance of your equipment.