Packaged Heat Pump System York XP 7.5 Ton Three-Phase | Montreal, Laval, Longueuil, South Shore and North Shore

In stock
SKU: XP090C00R2B1BAA1A2
Serial Number (Exterior): XP090C00R2B1BAA1A2
Tonnes: T
Cooling Capacity: 90,000 BTU
Energy Star: No
SEER:
HSPF:
CFM: 3000.0
Sound Pressure Level: 83.0 dB(A)
Gas (Freon): R-410A
Dimensions (L x W x H): 59 x 89 x 50.75
Manufacturer's Warranty (Compressor - Coil - Parts): 5-1-1

A mid-size business deserves cooling that follows its traffic

A store that fills up on Saturday, a dining room that goes from a quiet afternoon to the rush of dinner service, offices that empty out at the end of the day: the thermal load of a business changes from hour to hour. This packaged heat pump from the YORK Sun Pro series answers that reality with two scroll compressors and two stages of cooling, on the 208/230 V three-phase supply found in a good number of commercial spaces. At AirGreen, we supply it, install it and maintain it for merchants, owners and building managers in Montreal, Laval, Longueuil, the North Shore and the South Shore.

The whole system in a single cabinet, on the roof

A packaged heat pump brings the compressors, the coils, the fans and the controls together in a single outdoor cabinet. Set on a roof curb, on a pad or on a structure, it connects directly to the building's supply and return ducts. For a business, the gain is concrete: no indoor unit takes up sales or storage space, and our technicians work on the roof without disturbing your customers. The same machine cools in summer and heats by heat pump the rest of the year, with the option of adding electric backup heat.

Every Sun Pro unit leaves the factory charged with refrigerant, wired, piped and tested. It runs on R-410A, the previous-generation refrigerant: a proven technology that refrigeration technicians know well.

Two compressors, two stages, efficiency measured at part load

The two scroll compressors feed two independent refrigeration circuits, with steps at 50% and 100% of capacity. On a mild day, one compressor can be enough; the second comes in when the sun hits the storefront or the space fills up. This staging limits on-off cycling and helps hold a steady temperature for your customers and your staff. A compressor swap function (lead-lag), selectable on the control board, can also even out their running hours.

The efficiency ratings reflect that behaviour. The 11.2 EER measures full-load performance, while the 14.6 IEER, obtained with the IntelliSpeed drive, takes part-load operation into account and gives a better picture of a real season of use. Like every unit of 6 tons and up, this model is rated in EER and IEER, not in SEER.

Technical specifications of the model

  • Rated capacity: 7.5 tons (90,000 BTU/h)
  • AHRI net cooling: 92,000 BTU/h
  • Heating at 47 °F (8.3 °C): 87,000 BTU/h, COP of 3.5
  • Heating at 17 °F (-8.3 °C): 51,000 BTU/h, COP of 2.25
  • Efficiency: 11.2 EER and 14.6 IEER
  • Rated airflow: 3,000 CFM (ft³/min)
  • Power supply: 208/230 V, three-phase, 60 Hz
  • Compressors: 2 scroll, steps at 50% and 100%
  • Refrigerant: R-410A, thermostatic expansion valves (TXV)
  • Dimensions (width x length x height): 59 x 89 x 50.75 in.
  • Operating weight: 1,090 lb
  • Outdoor sound level (AHRI 270): 83 dBA

The factory configuration of this model

The number XP090C00R2B1BAA1A2 reads option by option in the YORK nomenclature. Here is what it includes:

  • IntelliSpeed drive with high static pressure drive package (3 HP motor): the supply fan speed varies with the number of compressors or heating stages running, and the minimum economizer position is set according to the drive frequency.
  • Economizer with barometric relief damper, to take advantage of cool outdoor air in the shoulder seasons.
  • Phase monitor, which protects the unit against phase loss and reverse rotation.
  • Stand-alone Smart Equipment control, compatible with a thermostat or a zone sensor.
  • Standard coils, without E-Coat coating.
  • No factory service option: no disconnect switch and no convenience outlet, the disconnect is planned for in the field.
  • Disposable 2 in. filters, standard cabinet and no factory-installed electric heat.

The Sun Pro strengths that simplify day-to-day management

Fast, tool-free maintenance

Tool-free hinged panels give access to the control box, the compressors, the filters, the motor and the indoor blower. The non-corrosive condensate pan slides out the back of the unit for cleaning, and service windows cut into both condenser walls make coil inspection easier. The motor-and-blower assembly slides out, and a second nameplate, placed inside the control door, stays legible despite the weather.

A control that reports clearly

The Smart Equipment board has an LCD screen and a navigation joystick: unit status, supply, return and outdoor temperatures, fault codes. Its USB port lets you review the fault history, run software updates and pull the self-test and start-up reports. The air sensors are factory-installed, the supply voltage is monitored for brownouts, and an anti-short-cycle delay protects the compressors. If a safety device trips three times in two hours, only the associated compressor is locked out, and a message is displayed.

A build designed for the roof

Freeze thermostats on the suction line, solid-core filter driers, high and low pressure switches and crankcase heaters are standard equipment. The galvanized steel cabinet gets a powder paint proven by a 750-hour salt spray test. The built-in low-ambient control allows cooling down to 0 °F (-17.8 °C) outdoors with no additional component, useful for spaces that give off heat even in winter.

Getting the 208/230 V three-phase installation right

  • Power supply: the YORK guide calls for an applied voltage of 187 to 252 V. We check the three-phase service and the panel capacity, especially if backup heat is planned.
  • Electric heat: for this size, YORK offers 9, 18, 24 or 36 kW kits, designed for a single-point power connection.
  • Roof curb: available in 8 in. or 14 in., with an insulated deck. The roof curb is common to the whole Sun Pro series from 6.5 to 12.5 tons, and a 10 in. transition curb makes it possible to reuse the footprint of an older Sunline unit from 7.5 to 12.5 tons.
  • Lifting: the full-perimeter base rails have lifting holes for the crane and fork slots on three sides.
  • Clearances: 72 in. above, 36 in. at the front, at the back and on the left, 12 in. on the right.
  • Ducts: bottom or side connection; the conversion is done by moving the factory covers, with no panel cutting.

AirGreen supports your Sun Pro project, from the estimate to the maintenance

It all starts with a free on-site estimate. We take down the floor area, the occupancy, the condition of the ducts, the electrical service and the roof access, then we confirm that 7.5 tons really is the right match for your space rather than a neighbouring size in the series. Our teams coordinate the lift, install the unit, connect the ducts and carry out the start-up: economizer setting, IntelliSpeed parameters and Smart Equipment control configuration. We then offer planned maintenance: filters, coils, belt, condensate pan and a reading of the fault history.

As an HVAC contractor, we serve businesses in Montreal, Laval, Longueuil, the North Shore and the South Shore with fast and efficient service calls. To schedule your visit, call us at 514 316-2973 or fill out the form on airgreen.ca: we will get back to you quickly with a clear quote.