Installation of a MIDEA EVOX G3 electric furnace in a narrow mechanical room in Ange-Gardien, Montérégie
In Ange-Gardien, AirGreen integrates a MIDEA EVOX G3 electric furnace into an ultra-tight mechanical room, with custom plenums, existing ductwork, airflow management, and carefully planned service access.
- City
- Region
- Equipment
- Brand
- Challenges
- Published
The job on one screen

The article, chapter by chapter
In Ange-Gardien, a few inches of clearance determined our entire installation strategy
This MIDEA EVOX G3 electric furnace installation in Ange-Gardien, in Montérégie, perfectly represents a challenge that technical specifications rarely show: how to integrate a modern central system into a mechanical space where the available width is barely greater than that of the equipment.
The photograph taken at our worksite is particularly telling. The new indoor unit, the MIDEA EVOX G3, is positioned between two closely spaced partitions, installed vertically on a lower galvanized-steel cabinet, and connected at the top to an existing ductwork system by means of a custom metal transition. On the left, copper piping runs along the wall; at the back of the room, several existing cables and pieces of equipment further occupy the available space.
In this configuration, the challenge was not simply to determine whether the EVOX G3 could physically fit in the room. Above all, we had to ensure that once installed, it could breathe properly, be connected without unnecessary restrictions, and remain accessible for future maintenance.
This is exactly the kind of situation where a few inches can make the difference between an installation that is merely possible and a truly well-designed HVAC installation.
A narrow mechanical room where nothing could be positioned at random
When a furnace is installed in the center of a large basement, we generally have some flexibility to position the lines, filter, drainage, and service access points.
At Ange-Gardien, this flexibility was much more limited.
The photograph shows that the cabinet occupies practically the entire width of its space. We therefore had to plan carefully:
- the furnace’s exact position;
- its connection to the lower plenum;
- the transition to the upper duct;
- the routing of the various lines;
- access to the panels;
- the clearance required for service work.
It is never enough to say, “the unit fits.”
We need to ask ourselves what will happen in five, ten, or fifteen years when a technician needs to access the fan, an electronic board, the coil, or the auxiliary heater.
The vertical configuration made it possible to use the entire available height
For this project, we worked with a vertical configuration.
Since the main ductwork was above the unit, this orientation allowed for logical integration with the existing duct system without unnecessarily adding several changes in direction.
The EVOX G3 is specifically designed for different installation configurations. Midea provides upflow and downflow orientations, right- and left-horizontal arrangements, as well as low-height configurations for particular applications. The design is also intended to facilitate use of the unit in challenging spaces.
This flexibility is particularly valuable in renovation, because an existing home does not change to fit the equipment. The installation must intelligently adapt to the building.
The lower plenum: an essential return-air component
Under the MIDEA cabinet, a metal plenum fabricated to provide the transition to the lower ductwork is clearly visible.
This type of component deserves much more attention than it generally receives.
The furnace fan must be able to draw in enough air before redistributing it throughout the system. If the return-air opening is too small or if a transition creates excessive restriction, the new unit may be limited by its surroundings.
Poor return airflow can notably lead to:
- more noise;
- an increase in static pressure;
- insufficient airflow;
- poor heat exchange;
- increased fan consumption;
- less even distribution throughout the house.
On an installation such as the one in Ange-Gardien, where physical space is already very limited, it is especially important to not sacrifice air cross-section simply to gain a few inches.
The upper transition had to connect a new unit to an existing geometry
The upper part of the photograph shows another element that is highly representative of replacement work: the outlet of the new furnace does not exactly match the shape of the existing duct.
We therefore need to fabricate a transition.
This transition is sealed to limit air loss, but its geometry is also important. We seek to avoid unnecessarily aggressive changes in cross-section and internal obstacles that would increase resistance to airflow.
When replacing an electric furnace in Ange-Gardien, Longueuil, Montréal, Laval, on the South Shore or the North Shore, this sheet-metal work is often a decisive part of the final result.
The new machine may have excellent rated efficiency; if the transitions were poorly designed, the owner will never fully benefit from its capabilities.
Why the dimensions of the EVOX G3 facilitate certain replacements
Midea paid particular attention to the dimensions of the EVOX G3 cabinet.
According to the manufacturer's documentation, the indoor units in the range use approximate widths from 14.5 to 21.5 inches, depending on their capacity. Midea presents this design as a way to facilitate the replacement of certain existing furnaces. The platform also provides for adaptation to different power supplies depending on the application.
In a space as narrow as the one photographed in Ange-Gardien, this feature immediately becomes relevant.
A difference of a few inches in cabinet width can determine:
- if the panels remain accessible;
- if the ducts can be routed properly;
- if a reasonable transition can be fabricated;
- if the new unit can be positioned without rebuilding the entire room.
A modular construction that helps when access is difficult
The EVOX G3 also uses a modular design called Block N Lock.
Midea explains that the unit can be separated or reconfigured more easily to facilitate handling, particularly in areas such as basements and attics.
In a renovation project, this feature is much more important than it may appear in a brochure.
We sometimes have to transport a unit through:
- a narrow staircase;
- a small door;
- a corridor;
- a low ceiling;
- a mechanical room already filled with other equipment.
A system designed with these realities in mind offers more possibilities during installation.
Airflow, heating, R454B, and efficiency: what we need to check after successfully fitting the EVOX G3 into the space
The physical space is only half the job
Once the furnace is positioned, we still need to make sure it operates properly with the building.
This is where the checks concerning the following begin:
- airflow;
- static pressure;
- fan settings;
- auxiliary electric heating;
- communication with the thermostat;
- the outdoor heat pump;
- the filtration;
- the condensate.
In other words, successfully installing the cabinet between two walls is never the final objective.
Computational Constant Airflow 2.0: particularly interesting in a renovation
One of the most relevant EVOX G3 technologies for existing homes is Computational Constant Airflow 2.0.
Midea states that the system can adjust the output and fan speed when ductwork resistance changes. In the applications illustrated by the manufacturer, the platform can operate with a total static pressure of up to 1.2 in. of water column.
The manufacturer also provides up to 60 airflow adjustment levels, allowing operation to be fine-tuned according to the actual ductwork.
In a replacement such as the one in Ange-Gardien, this capability is particularly relevant because we are not necessarily starting with new ducts designed specifically for the new equipment.
Constant-airflow technology does not, however, correct poor ductwork.
This point must be made very clear.
Even a sophisticated fan cannot eliminate the consequences of a severely undersized duct, an overly restrictive filter, or a poorly fabricated transition.
The motor can increase its effort to maintain airflow up to certain limits, but this does not mean that every restriction becomes acceptable.
That is why our approach at AirGreen is first to make the ductwork as coherent as possible, then take advantage of the equipment's adjustment capabilities.
The M-Coil and the symmetrical fan
Midea documentation also describes an internal architecture combining an M-Coil with a symmetrical fan.
The stated objective is to achieve a more even distribution of air across the coil's surface and limit airflow differences between different sections of the heat exchanger.
This technical detail is important because a heat exchanger is truly effective only when air flows properly across its surface.
In a central system, efficiency therefore depends as much on the equipment as on how air enters and leaves it.
A range from 18,000 to 54,000 BTU/h
The expression MIDEA EVOX G3 refers to a complete family of systems, not a single capacity.
Midea documentation covers configurations ranging from 18,000 to 54,000 BTU/h, with efficiencies reaching up to 19 SEER2, 12.5 EER2, 10.8 HSPF2, and a maximum stated COP of 2.14 under the indicated test condition, depending on the selected combination.
The manufacturer's technical table includes configurations of 18,000, 24,000, 30,000, 36,000, 48,000, and 54,000 BTU/h.
The photograph of our Ange-Gardien installation does not allow us to reliably read the full model number. We therefore do not arbitrarily assign it a specific capacity.
Why we do not automatically copy the tonnage of the old furnace
Replacing an old three-ton unit with a new three-ton unit may seem logical.
Yet this is not always the right approach.
The old unit could have been:
- oversized;
- undersized;
- installed with a system unable to carry its airflow;
- selected at a time when the home's insulation was different.
We consider the heat load, building envelope, windows, ducts, air returns, and actual heating and cooling needs.
A platform designed for heating in cold climates
When paired with the corresponding EVOX outdoor heat pump, Midea presents the platform as capable of heating operation down to -30 °C. The manufacturer also provides low-temperature results for a three-ton system used during its testing.
This capacity is particularly important in Quebec.
Summer performance is not enough to assess a heat pump intended for a home in Ange-Gardien or Montérégie. Its performance must also be examined when temperatures drop to -15 °C, -20 °C, and below.
Auxiliary heating: up to 25 kW, but not necessarily 25 kW for this house
The EVOX G3 platform can accommodate a multistage auxiliary heating kit.
Midea lists options of 10 kW, 15 kW, and up to 25 kW, with a strategy for adjusting heating use according to conditions.
This maximum value is never a universal recommendation.
Auxiliary heating must be determined according to:
- the heat pump's capacity;
- the property's heat loss;
- the capacity of the electrical panel;
- wiring;
- electrical protection;
- the control strategy.
Adding electrical capacity unnecessarily can increase peak demand without providing any real benefit to the homeowner.
The ducts visible on the left side must also comply with the service clearance
In the photograph, various sections of copper piping run along the left wall.
In such a narrow room, the routing of the ducts must be planned before considering the installation complete.
We seek to prevent a duct from being positioned in a way that would later prevent:
- the removal of a panel;
- the replacement of a component;
- access to a connection;
- the relocation of a filter.
A piping route can look very clean and still cause problems if it blocks the only path that allows access for servicing the unit.
Filtration must also be designed with airflow in mind
The EVOX G3 documentation provides for modules that can accommodate 1-, 2-, or 4-inch filters, including MERV 13 options depending on the configuration. Midea indicates that this filtration can capture more dust, pollen, particles, and pet hair.
However, filtration must always be coordinated with airflow.
A very small or heavily loaded high-efficiency filter can impose significant resistance.
We therefore prefer to consider these together:
filter surface area + MERV rating + required airflow + static pressure.
Conventional thermostat or Midea communication
The EVOX G3 platform offers several control options.
The documentation specifically provides for Midea 485 communication and certain configurations compatible with a conventional 24 V thermostat.
With the appropriate communicating components, Midea also provides for schedule programming, monitoring of certain comfort and consumption parameters, and diagnostic functions through the SmartHome app.
This flexibility can be particularly useful in a renovation when the thermostat wiring is already concealed in the walls.
R454B and A2L classification
The EVOX generation presented in the documentation uses R454B.
Midea states that this refrigerant has a global warming potential, or GWP of 466, and specifies that it was chosen for its new product line.
R454B is an A2L-classified refrigerant. Its installation and servicing must therefore follow procedures adapted to this new generation of equipment.
This is an important difference compared with several older R410A systems still found in Quebec homes.
LogisVert: the complete combination must be verified, not just the indoor furnace
For heat pumps installed since November 26, 2025, Hydro-Québec currently requires ENERGY STAR certification for the LogisVert Heat Pump measure. When all conditions are met, the grant is $50 per 1,000 BTU/h at -8°C for an ENERGY STAR heat pump and $120 per 1,000 BTU/h at -8°C when it is certified ENERGY STAR – Cold Climate.
However, it is essential not to consider the EVOX G3 indoor furnace alone as proof of eligibility.
Eligibility depends in particular on the complete heat pump combination, the outdoor model, the indoor model, certification, and compliance with the program’s other conditions. Hydro-Québec also specifies that replacing only one indoor or outdoor unit is not eligible for this measure.
For this Ange-Gardien project, the photograph does not allow us to identify the exact outdoor combination; we are therefore not presenting any specific amount for this installation.
The particularly costly mistakes in such a narrow mechanical room
Choosing the unit before measuring the actual access
Cabinet dimensions are not enough. The clearances required for servicing must also be considered.
Positioning the furnace against a wall without considering the panels
A few inches gained during installation can make a future service call extremely difficult.
Building a transition that is too restrictive to gain height
The air-distribution network’s section must remain compatible with the desired airflow.
Neglecting the return air
A central system cannot blow air properly if it cannot draw in enough air.
Running the pipes in front of the only service access
The shortest route is not always the best.
Assuming that 19 SEER2 applies to all EVOX G3 units
Performance varies depending on the combination and capacity. The Midea table clearly shows different values from one model to another.
This Ange-Gardien project illustrates exactly why we inspect the space before choosing the final configuration
This installation appears relatively simple once the machine is in place: a vertical unit, a lower plenum, and an upper duct.
The photograph nevertheless shows just how limited the room for maneuver was.
The MIDEA EVOX G3 had to be integrated between two walls, connected to an existing ductwork layout, and positioned so as not to block access to components that will need servicing later.
This is the reality we regularly encounter during our electric furnace and central heat pump installations in Ange-Gardien, Montérégie, Longueuil, the South Shore, Montreal, Laval, and the North Shore.
At AirGreen, we do not consider an installation successful simply because the new unit occupies the former unit’s location.
We want the system to move the right airflow, operate with the planned heat pump and auxiliary heating, remain accessible, and fit cleanly within the building’s actual constraints.
In this Ange-Gardien installation, the challenge was not finding an empty spot for a new furnace. It was using a space intelligently when there was almost no room to spare.
The job tools
Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.
Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.
How the job unfolds
The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.
We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
The equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
Access protected, old unit disconnected and removed when it is being replaced.
Electric furnace or air handler, with its coil, connected to the supply and return ducts.
On a level base, raised above the snow, with free space all around.
Insulated, they enter through a sealed opening and run to the indoor coil.
Dedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
Leak test, vacuum, start-up, airflow check and a test of both modes.
Filter, thermostat, backup heat in extreme cold: what to know before winter.
- The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
- The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
- Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
- The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
- The outdoor unitOn a level base, raised above the snow, with free space all around.
- The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
- Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
- Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
- The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
What we check on a job like this one
Each number is a point we check on site. Switch between summer and winter to watch air and heat move.
In summer, the outdoor unit rejects the house's heat outside.
Generic illustration of this type of installation, not a survey of this job site. Tap a number.
It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.
The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.
A shut-off switch near the outdoor unit isolates it safely for service.
Sitting on the indoor module, it moves heat between the house air and the refrigerant.
Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.
Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.
It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.
It runs the heat pump and the backup heat. It must be compatible with the installed system.
Is your home ready?
Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.
Good habits, once the unit is in place
Six simple habits that keep the unit going. Your list stays on this device.
What to do, season by season
Three habits per season for this unit. They take a few minutes and prevent many calls.
- Check the indoor module's filter.
- Clear winter debris from the outdoor unit.
- Test cooling before the heat arrives.
- Check the filter more often in peak season.
- Keep registers and returns clear.
- Watch condensate drainage near the coil.
- Change or clean the filter.
- Test heating and backup heat before the cold.
- Book periodic maintenance.
- Clear snow around the outdoor unit.
- Store nothing in front of the indoor module.
- Note any unusual noise or smell and call us.
The right pages, at the right time
Four statements: true or false?
It all comes down to details you have just seen.
1. A central heat pump uses the house's ducts.
It connects to the existing ducts to heat and cool everywhere.
2. In extreme cold, electric backup heat can take over.
The indoor module (furnace or air handler) works with the heat pump and takes over in extreme cold.
3. The filter only gets changed when the unit breaks down.
A dirty filter cuts airflow. It gets checked regularly.
4. You can reuse the old unit's size without checking.
The house may have changed: insulation, windows, added rooms. Capacity is confirmed on site.
0 / 4 right answers
What people ask us about this kind of work
Can I keep my current ducts?
What happens in extreme cold?
Furnace, air handler, ducted: what is the difference?
Are there grants?
Do I need a permit?
How much can I save?
How is the LogisVert assistance calculated?
Will my current thermostat work?
Central or wall units: which one?
Does AirGreen hold the required licences?
Is the estimate free?
No question matches. Write to us: we answer.
More jobs to see, near you
By town, by equipment or by region: browse more than 4,700 published projects.
Each dot: a town where AirGreen has published projects. The glowing dot: this job.
An on-site estimate, the right capacity, the right equipment.
The on-site estimate is free and the quote follows within 24 hours.
Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).
