Project

Installation of a MIDEA EVOX G3 electric furnace in a horizontal configuration in an attic in Acton Vale, Montérégie

In Acton Vale, AirGreen installs a MIDEA EVOX G3 horizontally in a complex attic space, between the framing, insulation, and large ducts, with precise control of the level, airflow, and future access.

By AirGreen Climatisation & Chauffage Admin16 min read
Installation of a MIDEA EVOX G3 electric furnace in a horizontal configuration in an attic in Acton Vale, Montérégie
Installation of a MIDEA EVOX G3 electric furnace in a horizontal configuration in an attic in Acton Vale, Montérégie
–chapters in this story
16 minreading time
–type of installation
2026year published
The tour

Take a tour of the installation

Each number is a point we check on site. Switch between summer and winter to watch air and heat move.

Generic diagram: central heat pump, indoor module and ducts

In summer, the outdoor unit rejects the house's heat outside.

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.

  2. The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.

  3. A shut-off switch near the outdoor unit isolates it safely for service.

  4. Sitting on the indoor module, it moves heat between the house air and the refrigerant.

  5. Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.

  6. Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.

  7. It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.

  8. It runs the heat pump and the backup heat. It must be compatible with the installed system.

The job

In Acton Vale, an EVOX G3 installation where the framing, level, ducts, and service access dictated every decision

This MIDEA EVOX G3 electric furnace installation in Acton Vale, in the Montérégie region, perfectly illustrates why a central attic installation can never be treated as a simple equipment replacement. The photo taken during our work shows a very concrete reality: the indoor unit is installed horizontally beneath the roof, between the framing members, surrounded by insulated ducts and a substantial layer of insulation.

One element immediately draws attention: a spirit level is placed directly on the MIDEA cabinet. This detail is far from insignificant. In a horizontal configuration, the unit's position affects, among other things, condensate management, duct connections, transition alignment, and how the unit can be serviced later.

Directly in front of the unit, a vertical framing member divides the space. To the right, a large insulated duct occupies almost the entire available passage. On the floor, the insulation makes movement difficult and requires working methodically to avoid unnecessarily compressing the materials or compromising their performance.

This project represents exactly the type of HVAC installation where quality is measured in details that will be almost invisible once everything is finished.

Why a horizontal configuration was the logical solution

The MIDEA EVOX G3 is designed for several installation orientations. The manufacturer's documentation specifically presents upflow, downflow, right horizontal, left horizontal configurations, as well as “low-boy” arrangements intended for spaces where available height is limited.

In the attic photographed in Acton Vale, a vertical installation would have been difficult to consider. The roof slope quickly reduces the available height, while the existing ducts and framework already occupy a significant portion of the space.

The horizontal configuration therefore makes it possible to use the available length rather than the height.

Midea also designed the EVOX G3 with a modular architecture that allows for easier adaptation to complex spaces. The manufacturer specifically mentions attics and basements among the environments where the modular design facilitates handling and positioning of the unit.

The structural post in front of the unit: we cannot reason as though we were in an empty mechanical room

The photograph shows a vertical wooden member located directly in front of part of the cabinet.

In a new construction, the location of the equipment and ducts can often be planned before the walls and ceilings are closed. In a renovation, we must work with what is already there.

The building’s structure is not something that can simply be moved to gain a few inches of space around a furnace.

We must therefore position the new MIDEA EVOX G3 while simultaneously taking into account:

  • structural elements;
  • service panels;
  • the filter;
  • refrigerant connections;
  • drainage;
  • the supply and return ducts;
  • the space required for future servicing.

The correct position is not necessarily the one that leaves the most space on one side. It is the one that allows the entire system to operate and be serviced properly.

Why the level placed on the MIDEA is one of the most important details in the photo

When a central unit is installed horizontally, its positioning must be checked precisely.

The level visible at our Acton Vale worksite allows us to check the installation’s alignment before finalizing the connections.

This step is particularly important in cooling mode.

When warm, humid air passes over the cold indoor coil, water condenses. This water must flow into the drain pan and then be discharged through the designated drain.

In an attic, poor drainage is particularly problematic. A leak may remain invisible for some time before appearing on the ceiling of the room below.

The consequences may include:

  • damage to drywall;
  • wet insulation;
  • material deterioration;
  • the appearance of stains;
  • water infiltration around light fixtures;
  • major repairs inside the house.

That is why leveling, drainage, and the position of the coil must be considered from the beginning of the project rather than at the very end.

An installation surrounded by insulation: working without damaging the building envelope

The attic floor visible in the photograph is covered with a thick layer of insulation.

For our technicians, this means that we must not only install the equipment but also protect the environment in which we work.

Walking directly and continuously on the insulation can compress it. Moving it without properly putting it back in place can also create areas where thermal resistance becomes less uniform.

Therefore, we must plan for:

  • the technicians’ passage;
  • temporarily positioning the tools;
  • accessing the connections;
  • removing the debris;
  • reinstalling the insulation around the work area.

A highly efficient new furnace loses some of its value if the work simultaneously creates thermal losses in the home’s envelope.

The large flexible ducts visible on the right are just as important as the new unit

The photograph shows several insulated ducts, including a large main section located immediately to the right of the EVOX G3.

During a central-system installation, we never consider these ducts to be mere accessories.

Their role is essential: they must carry all the airflow produced by the unit to the various areas of the house.

A flexible duct can lose a significant portion of its usable cross-sectional area when it is:

  • crushed;
  • bent too sharply;
  • not stretched tightly enough;
  • trapped between two structural elements;
  • compressed against the new unit.

In such a tight space, it might be tempting to simply move a duct a few inches to create more room. However, this can increase its resistance and reduce the available airflow.

The priority, therefore, is to make the equipment, framing, and ducts work together without sacrificing one to facilitate the installation of another.

Computational Constant Airflow 2.0: an interesting technology when the ducts are already in place

The MIDEA EVOX G3 incorporates a technology called Computational Constant Airflow 2.0.

According to Midea, the system can automatically adjust the fan’s power and speed to better adapt to changes in system resistance. The documentation describes operation at up to 1.2 in. of static pressure under certain conditions.

The manufacturer also provides up to 60 levels of airflow adjustment, accessible in the system’s engineering settings.

This flexibility is particularly valuable in a renovation in Acton Vale, because we work with ducts that were already built around the house.

However, it never replaces a good installation.

A constant-pressure fan cannot turn a severely crushed duct or an undersized return-air duct into a properly sized system.

Static pressure: a figure often overlooked when replacing a furnace

Homeowners frequently compare equipment based on:

  • the number of BTUs;
  • the SEER2;
  • the HSPF2;
  • the price;
  • the brand.

The network’s static pressure is nevertheless a very important factor.

Imagine the fan as a pump that must move air through:

  1. the filter;
  2. the coil;
  3. the plenum;
  4. the main ducts;
  5. the branches;
  6. the grilles.

Each restriction adds resistance.

If this resistance becomes excessive, the system may operate at a lower airflow than intended, even if the heat pump itself has excellent rated performance.

An M-Coil architecture designed to distribute air more evenly

Midea also uses an indoor configuration with an M-Coil and symmetrical fan.

The documentation compares this architecture with certain traditional heat exchangers and shows more uniform air distribution across the different sections of the coil.

For a central installation, this uniformity makes better use of the heat exchanger’s surface area.

The goal is not simply to move a large volume of air, but to move it properly through the coil before sending it to the rooms in the home.

EVOX G3: an electric furnace, but also a central heat pump platform

In everyday Québec usage, we refer to it as the MIDEA EVOX G3 electric furnace.

Technically, the indoor unit is part of a central platform that can be paired with an inverter heat pump and an auxiliary electric heating kit.

The heat pump can then handle a large portion of the heating, while the electric elements supplement demand when necessary.

Midea offers 10 kW, 15 kW, and up to 25 kW auxiliary heating kits, with controls that can operate in multiple stages depending on the configuration.

This system enables a more precise heating strategy than simple on-off operation.

Why we do not automatically choose the highest auxiliary heating capacity

It might seem reassuring to always install the maximum 25 kW.

That would nevertheless be a poor method.

We must determine the auxiliary capacity based on:

  • the home’s heat loss;
  • heat pump capacity at low temperatures;
  • electrical panel capacity;
  • conductor gauge;
  • circuit breakers;
  • air-distribution system sizing;
  • the desired operating strategy.

An oversized electrical system may unnecessarily require substantial electrical capacity and increase power peaks.

A lineup designed for cold-climate heating

Midea presents EVOX as a platform capable of continuing heat pump operation down to -30 °C, depending on the combination.

The data published for the three-ton system used during the manufacturer’s tests also show performance at very low temperatures, including around -25 °C.

For a property in Acton Vale, cold-weather heating performance is particularly important.

SEER2 remains useful for comparing cooling efficiency, but a Quebec homeowner should also consider:

  • HSPF2;
  • low-temperature COP;
  • heating capacity maintenance;
  • actual need for auxiliary heating.

Up to 19 SEER2 depending on the selected EVOX G3 combination

The lineup covered by Midea’s documentation includes systems ranging from 18,000 to 54,000 BTU/h. Performance can reach 19 SEER2, 12.5 EER2, and 10.8 HSPF2, depending on the specific combination.

The technical table on page 11 shows several capacities, including:

  • 18,000 BTU/h;
  • 24,000 BTU/h;
  • 30,000 BTU/h;
  • 36,000 BTU/h;
  • 48,000 BTU/h;
  • 54,000 BTU/h.

Efficiency and heating values vary from one model to another.

The nameplate shown in our photo is visible, but its complete model number is not clear enough to identify this unit’s exact capacity with certainty. We therefore deliberately do not assign it an unconfirmed BTU rating.

The A2L symbol visible on the nameplate: the arrival of R454B

On the unit installed in Acton Vale, the symbol A2L is clearly visible.

Midea’s documentation indicates that the R454B was selected for the EVOX lineup and specifies a global warming potential, or GWP, of 466.

This refrigerant change affects work methods.

R454B is classified as A2L, meaning it has low but non-zero flammability. Installation and servicing therefore require procedures adapted to this new generation.

For a homeowner replacing an old R410A central heat pump, the type of refrigerant is now an item to note in the documentation for the new equipment.

Filtration: MERV 13 is possible, but only if the system can breathe properly

Midea documentation provides for filtration modules compatible with 1-, 2-, or 4-inch filters, including MERV 13 depending on the configuration.

Better filtration can help capture more:

  • dust;
  • pollen;
  • fine particles;
  • pet hair.

It can also help keep the indoor coil cleaner.

But a high MERV rating should never be considered in isolation.

If the filter becomes too restrictive for the available surface area, it increases static pressure and can reduce airflow. We therefore seek a balance between filtration quality and airflow.

A filter in an attic must above all remain accessible

Accessibility is even more important on this job.

A filter that should theoretically be replaced regularly should not require dismantling a duct or moving a structural component every time it needs to be reached.

During planning, we must therefore ask ourselves where the technician or homeowner will actually be when maintenance is required.

The photo clearly illustrates this reality: between the framing, large ducts, and insulation, no movement is as simple as it would be in a conventional mechanical room.

Communicating control or 24 V thermostat

The EVOX G3 platform can use several control strategies.

The documentation specifies compatibility with the Midea 485 system as well as with certain configurations using a conventional 24 V thermostat.

With the corresponding communicating components, Midea also offers programming, comfort monitoring, energy-use tracking, and diagnostics through the SmartHome app.

This flexibility can be valuable when replacing equipment in an existing home, where running a new thermostat cable would otherwise require opening finished walls or ceilings.

Mistakes we seek to avoid when installing a furnace in an attic

Position the unit solely according to the available space

Drainage, maintenance, and ductwork must also be considered.

Use flexible ducts to “make room”

Compressing them can significantly reduce their effective cross-sectional area.

Forgetting to check the level

A horizontal configuration requires precise positioning in accordance with the system requirements.

Blocking a panel behind a structural component

We must always anticipate future service work.

Compressing the insulation around the unit

An HVAC installation should not unnecessarily degrade the thermal envelope.

Choosing the tonnage solely based on the old unit

An old installation may itself have been oversized.

Using the lineup's maximum efficiency as the efficiency of the installed model

Values reaching 19 SEER2 or 10.8 HSPF2 apply to certain specific combinations, not to all EVOX G3 units.

What about subsidies?

The Midea brochure provided with the equipment contains examples of financial assistance programs, but these mainly concern U.S. programs.

It therefore does not constitute confirmation that a system installed in Acton Vale qualifies for a Quebec subsidy.

For a central heat pump in Quebec, you must always verify the exact combination of indoor and outdoor models, the applicable certification, and the rules of the program in effect at the time of installation.

We therefore avoid promising financial assistance solely because a unit belongs to the MIDEA EVOX G3 lineup.

This Acton Vale project shows what really makes the difference in an HVAC installation

At first glance, the photo shows a MIDEA EVOX G3 lying horizontally in an attic.

In reality, it shows much more comprehensive integration work.

We have to work around:

  • a structural frame that cannot be moved;
  • a low roof;
  • an existing duct network;
  • insulation covering the entire work area;
  • limited access;
  • a unit that must be positioned precisely;
  • an R454B A2L system;
  • future maintenance to anticipate even before startup.

This type of project explains why we never consider an electric furnace or central heat pump installation to be a simple box replacement.

At AirGreen, we apply the same level of care to installations carried out in Acton Vale, Longueuil, on the South Shore, in Montreal, Laval, and on the North Shore: the system must be properly sized, correctly connected to the ductwork, and above all adapted to the building around it.

An EVOX G3 offers interesting technology, but it is the quality of the integration that will allow this technology to genuinely support occupant comfort in the years to come.

The steps

The big day, step by step

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.

  1. The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
  2. The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
  3. Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
  4. The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
  5. The outdoor unitOn a level base, raised above the snow, with free space all around.
  6. The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
  7. Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
  8. Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
  9. The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
Your numbers

What would it look like at your place?

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Size checkYour electric furnace, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    Mistakes avoided

    Four mistakes we do not make

    Flip each card to see what we do instead.

    Going further

    Your own project, step by step

    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Check the indoor module's filter.
    • Clear winter debris from the outdoor unit.
    • Test cooling before the heat arrives.
    At your place

    Is your home ready?

    Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.

    0 / 6 checked
    True or false

    Four statements: true or false?

    It all comes down to details you have just seen.

    1. A central heat pump uses the house's ducts.

    2. In extreme cold, electric backup heat can take over.

    3. The filter only gets changed when the unit breaks down.

    4. You can reuse the old unit's size without checking.

    Frequently asked questions

    What people ask us about this kind of work

    11 questions
    Can I keep my current ducts?
    Often, yes: the central heat pump connects to the existing ducts. We check their condition and size during the estimate.
    What happens in extreme cold?
    The indoor module (furnace or air handler) works with the central heat pump and takes over in extreme cold.
    Furnace, air handler, ducted: what is the difference?
    The furnace or air handler is the indoor module of the central system. A ducted system hides in the ceiling: all you see are small supply grilles.
    Are there grants?
    Depending on the equipment and your situation, assistance programs may apply. AirGreen checks the exact combination before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city. See permits and by-laws, and we check for your address.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Will my current thermostat work?
    Not always: the thermostat has to run the heat pump and the backup heat. We check compatibility during the estimate.
    Central or wall units: which one?
    If the house has ducts in good shape, a central system heats and cools every room at once. Without ducts, wall units or a multi-zone are often simpler. We compare on site.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    Every house has its constraints. We see them before we install.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment