Project

Installation of a MIDEA EVOX G3 central heat pump on a flat roof in Saint-Anicet, Montérégie

In Saint-Anicet, AirGreen installs a MIDEA EVOX G3 central heat pump on a flat roof, with an elevated support designed for snow, defrosting, service access, and Quebec's winter conditions.

By AirGreen Climatisation & Chauffage Admin16 min read
Installation of a MIDEA EVOX G3 central heat pump on a flat roof in Saint-Anicet, Montérégie
Installation of a MIDEA EVOX G3 central heat pump on a flat roof in Saint-Anicet, Montérégie
Generic diagram: central heat pump, indoor module and ducts

In summer, the outdoor unit rejects the house's heat outside.

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.

  2. The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.

  3. A shut-off switch near the outdoor unit isolates it safely for service.

  4. Sitting on the indoor module, it moves heat between the house air and the refrigerant.

  5. Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.

  6. Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.

  7. It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.

  8. It runs the heat pump and the backup heat. It must be compatible with the installed system.

In Saint-Anicet, an EVOX G3 installed on the roof: a project where the support, snow, vibrations, and service access matter just as much as the BTUs

This MIDEA EVOX G3 central heat pump installation in Saint-Anicet immediately stands out because of its location. The outdoor unit is neither placed on the ground near the foundation nor mounted on wall brackets: it is installed directly on a flat roof, on a raised metal structure resting on two long bases that distribute the load across the roof.

For us at AirGreen, this type of project requires a different approach from a conventional residential installation. On a roof, we must consider the load, membrane protection, vibrations, air movement, snow accumulation, defrost water drainage, refrigerant line routing, and future access for HVAC maintenance simultaneously.

The jobsite photo shows this reality precisely. The Midea heat pump is held well above the roof surface by a four-legged support. These rest on two longitudinal bases that prevent the equipment's entire weight from being concentrated on four small points. To the right of the unit, we can also see the route of the refrigerant and electrical connections, guided toward the building along a support structure.

It is therefore not just a MIDEA EVOX G3 placed on a roof. It is a system whose outdoor environment has been designed for the actual conditions of a Quebec roof.

Why elevate a central heat pump on a flat roof

On a flat roof in Saint-Anicet, one of the most important challenges is snow.

An outdoor unit operating almost at membrane level could quickly find itself surrounded by significant accumulation after a few storms. On a roof, wind also creates snow movement and drifting patterns that differ from those observed at ground level.

By elevating the heat pump, we aim to preserve more space around the coil and beneath the unit.

This height also facilitates the management of water from defrost cycles. A central heat pump in heating mode must occasionally defrost its outdoor coil. The resulting water must be able to drain away without immediately creating a mass of ice directly beneath the condenser base.

The support visible in the photo therefore contributes to several objectives:

  • keep the unit above the immediate roof level;
  • reduce the risk of partial burial by snow;
  • leave more space for defrost water;
  • make access beneath and around the unit easier;
  • maintain good clearance for airflow;
  • make service work more practical.

The ideal height always depends on the exact roof configuration and the manufacturer's requirements. We therefore do not treat all rooftop installations identically.

A base designed to protect the roof and distribute loads more effectively

Perhaps the most interesting detail in the photo is found beneath the support's four feet.

Rather than placing each foot directly on the membrane, the installation uses two long bases beneath the metal structure. On a flat roof, this allows us to distribute the loads more effectively and avoid unnecessarily concentrating the weight in a few small areas.

This is particularly important when working with an existing roofing membrane. Supports, fasteners, protective materials, and service penetrations must be installed in a way that does not create damage that could later become a source of water infiltration.

The structure must also remain stable while the condenser is operating. The compressor and fan generate normal vibrations, and an improperly designed support could transmit more noise to the building structure.

In a rooftop project, our objective is therefore twofold: properly support the equipment while respecting the building envelope.

The EVOX G3's front air discharge is particularly important on a rooftop

The large round grille at the front of the condenser corresponds to the horizontal fan.

Midea uses a horizontal discharge design on the EVOX G3, combined with a vertical heat exchanger. According to the manufacturer's documentation, this architecture is intended to provide more uniform airflow across the heat exchanger and better efficiency as the outdoor temperature decreases.

In the photo, the front of the unit is largely unobstructed. This is exactly what we want to look for with this type of equipment.

A heat pump that discharges air horizontally should not be placed directly facing a nearby obstruction. On a rooftop, we must therefore consider the position of parapets, other mechanical equipment, and taller walls that could promote air recirculation.

Here, the selected location provides particularly open space in front of the fan.

The refrigerant line route is part of the work, even on a roof

To the right of the unit, we can see the path of the lines connecting the condenser to the indoor system.

On a roof, it is not enough to connect the lines and leave them resting freely on the membrane. They must be protected, supported, and organized in a way that limits movement, wear, and unnecessary contact points.

A good route also facilitates future service calls. If a technician has to return for a heat pump diagnosis, an inspection, or a repair, they must be able to easily follow the circuit without having to move improvised elements.

We therefore seek to maintain a clear path between the outdoor MIDEA unit and the point where it enters the building.

The roof environment also affects maintenance work

A heat pump located on a roof is generally less accessible than equipment installed next to a house.

This means that service access must be planned from the outset.

A technician must be able to:

  • approach the equipment safely;
  • open the service panels;
  • access the refrigerant connections;
  • take electrical measurements;
  • inspect the heat exchanger;
  • clean the unit when necessary;
  • work without having to move the condenser.

That is precisely why we avoid positioning a unit in a corner that is too tight solely to gain a few more feet of available roof space.

The MIDEA EVOX G3 is designed for heating at very low temperatures

A rooftop installation like this would be much less appealing if the heat pump were intended only for air conditioning.

The MIDEA EVOX G3 is an Inverter central heat pump designed to operate year-round. Midea documentation states continuous operation down to -30 °C for Extreme Heat configurations. For the three-ton system used by Midea as a reference for the cited tests, the manufacturer also indicates up to 100% heating capacity at -25 °C, with a COP that can reach approximately 1.9 under these conditions.

Midea explains that its compressor technology uses an intermediate-temperature vapor injection during extreme cold conditions to increase the amount of compressed refrigerant and support heat production.

This feature is especially relevant in Saint-Anicet, where a heat pump must be able to operate during winter periods that are much more demanding than those in a temperate climate.

Several capacities are available in the EVOX G3 range

The name EVOX G3 does not refer to a single capacity.

The documentation presents a range of central systems covering approximately 18,000 to 54,000 BTU/h of nominal cooling capacity, with several combinations of indoor and outdoor units.

Among the combinations published by Midea, we find in particular:

  • 18,000 BTU/h;
  • 24,000 BTU/h;
  • 30,000 BTU/h;
  • 36,000 BTU/h;
  • 48,000 BTU/h;
  • 54,000 BTU/h.

Depending on the configuration, the range reaches up to 19 SEER2, 12.5 EER2, and 10.8 HSPF2.

However, the photograph from Saint-Anicet does not allow us to read the model number clearly enough to honestly assert the exact tonnage of this installation. We therefore prefer to present the range's performance and explain how it varies rather than arbitrarily assigning a capacity to the visible condenser.

An interesting example: the 30,000 BTU central configuration

To understand the importance of the exact combination, let's look at the 30,000 BTU configuration presented in the technical documentation.

Midea indicates a nominal capacity of 30,000 BTU/h in cooling, a nominal heating capacity of 33,000 BTU/h, an SEER2 of 17.2, an EER2 of 12.0, and an HSPF2 of 10.8 for this combination. At -15 °C, the technical data sheet still indicates approximately 33,200 BTU/h of heating with a COP of 1.97.

This detail is particularly interesting for homeowners who compare two systems based solely on the number of tons.

The nominal rating does not tell the whole story.

We must also consider the available capacity in cold weather, seasonal efficiency, duct system capacity, and the building's thermal profile.

A three-ton heat pump is not automatically the right solution just because the old one was

For a central replacement, one of the most common mistakes is to blindly copy the tonnage of the old system.

A property may have changed since the old equipment was installed:

  • new windows;
  • added insulation;
  • finished basement;
  • addition;
  • new ducts;
  • sealed-off duct sections;
  • major changes in occupancy habits.

We therefore prefer to size the system according to current needs.

Oversizing does not automatically provide greater comfort. It can cause shorter cooling cycles and limit the time needed for proper dehumidification. Conversely, an undersized unit may lack capacity during the most demanding periods.

The indoor duct system remains crucial

Even if the photo of this project mainly shows the exterior, a central heat pump always operates as a system.

The quality of the indoor duct system has a direct impact on comfort.

A high-performance outdoor unit cannot fully compensate for:

  • an undersized return air duct;
  • undersized ducts;
  • a highly restrictive duct system;
  • poorly balanced dampers;
  • an overly restrictive filter;
  • poorly insulated ducts in certain areas.

This is precisely the part of the system where the EVOX G3 platform offers an interesting feature.

Beyond the rooftop outdoor unit: the EVOX G3 indoor unit and the real quality of the central system

The MIDEA EVOX G3 was designed as a modernization platform for a complete central system. The outdoor unit visible in Saint-Anicet is therefore only one element of an installation that also includes the air handler, duct system, filtration, controls and, potentially, auxiliary electric heating.

Computational Constant Airflow 2.0: adapting the fan to the duct system

Midea integrates a technology called Computational Constant Airflow 2.0 into the EVOX G3.

The documentation states that the system can adjust fan capacity to adapt to different duct and filtration conditions, with static pressure management of up to 1.2 in. of water column under the conditions presented by the manufacturer.

The airflow can also be customized across up to 60 levels, providing greater latitude during commissioning.

For us, this flexibility is useful when replacing an old central system.

But it should not become an excuse to ignore a poorly designed duct system. Advanced fan technology does not turn a severely undersized duct into a good duct.

A modular indoor unit for challenging mechanical rooms

The EVOX G3 system also uses a modular design called Block N Lock.

The documentation presents six installation configurations, including upflow, downflow, right horizontal, left horizontal and low-boy configurations.

This can help us in buildings where interior space is limited.

The mechanical rooms in Montréal, Laval, Longueuil, the North Shore and the South Shore present very different realities: old basements, low ceilings, existing ducts that are difficult to relocate, or spaces arranged around the mechanical equipment.

The modularity of the indoor unit can therefore limit certain modifications.

A width suited to several furnace replacements

Midea also presents the EVOX G3 as a solution designed to facilitate certain furnace replacements.

The announced indoor units have approximate widths of 14.5 to 21.5 inches, similar in size to several common central furnace formats.

This can make it possible to preserve part of the existing plenum geometry when the dimensions are compatible.

We must of course assess each project individually, because ducts, height, return air and metal transitions are never identical from one house to another.

Auxiliary heating up to 25 kW

A Quebec central heat pump is often paired with auxiliary electric heating.

For the EVOX G3, Midea provides three-stage auxiliary kits reaching 25 kW, with activation and adjustment based on temperature changes.

However, this component must be carefully sized.

We must check the electrical panel capacity, the property's heating needs and the system's control strategy. Automatically adding the largest available component is not a good design method.

485 communication, 24 V and retrofit possibilities

The EVOX G3 is compatible with several control strategies.

The documentation indicates compatibility with 485 communication as well as 24 V control systems, including third-party thermostats. Midea also specifies that the equipment can automatically identify the control mode being used.

Sub-1 GHz communication modules can also, in some configurations, reduce the need for a new communication wire between the indoor unit, heat pump and thermostat.

This flexibility can be particularly useful when replacing equipment in an already finished property, where running new cables would require opening up several surfaces.

R-454B: the next generation of refrigerant

The EVOX central system lineup in question uses R-454B refrigerant, classified as A2L.

Midea indicates a GWP of 466 for this refrigerant and states that it has adopted it for its new central system lineup.

For us, installers, this means that work methods, tools and commissioning procedures must be adapted to the refrigerant actually being used.

The refrigerant change is therefore not merely a line in a technical brochure.

MERV 13 filtration up to four inches

Midea also provides a filtration module compatible with 1-, 2- or 4-inch MERV 13 filters. The documentation indicates that this filtration is intended to capture more dust, pollen, particles, as well as some pet hair and dander, while helping keep the indoor coil cleaner.

However, we must always consider the filter's pressure drop.

Better filtration must be integrated into the system, not simply added without measuring its impact on airflow.

The mistakes this rooftop installation helps us avoid

This Saint-Anicet project is an excellent opportunity to highlight some common mistakes with central heat pumps installed on a roof:

  • place the unit too close to the membrane and snow;
  • concentrate all the weight on small support points;
  • leave the refrigerant lines loose on the roof;
  • point the fan toward an obstacle that is too close;
  • neglect defrost water;
  • place the condenser where no technician can easily service it;
  • size the unit solely according to the old tonnage;
  • forget that system performance also depends on the indoor unit and the ducts;
  • announce the maximum values for the range as if they applied to all capacities.

A good HVAC installation consists precisely in anticipating these details before they become problems.

A central heat pump that must be considered as a complete system

In the photo, the most striking element remains the EVOX G3 condenser installed in the middle of this roof surrounded by trees.

But the actual performance of this installation depends on much more than this outdoor unit.

They depend on sizing, the duct network, airflow, the thermostat, filtration, the auxiliary heating element, the refrigerant line routing and the quality of commissioning.

In Saint-Anicet, the elevated mounting shown in the photo already addresses several constraints specific to the roof: snow, defrosting, accessibility and surface protection. MIDEA EVOX G3 technology complements this approach with a central Inverter platform designed to operate in very cold winter conditions.

At AirGreen, we apply this same logic to central heat pump projects in Montreal, Laval, Longueuil, the North Shore and the South Shore: we are not simply looking to install a machine. We aim to create an HVAC system that is consistent with the building, its duct network and Quebec's actual conditions.

In figures
The steps

How it goes, from the first call to the end

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.

  1. The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
  2. The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
  3. Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
  4. The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
  5. The outdoor unitOn a level base, raised above the snow, with free space all around.
  6. The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
  7. Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
  8. Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
  9. The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
The unit

What the unit delivers when it is cold

The range as published on airgreen.ca: pick a size to see its capacity in deep cold.

The range, size by size
SizeHeating at −8 °CHeating at −15 °CColdest certified pointCOP at −15 °CSEERHSPFIndicative LogisVert aid
Midea EVOX G3 · 1.5 tons14,70018,600−30 °C: 11,8002.1219.010.1$1,764
Midea EVOX G3 · 2 tons20,80020,600−30 °C: 12,1002.1418.610.0$2,496
Midea EVOX G3 · 2.5 tons24,00033,200−30 °C: 17,9001.9717.210.8$2,880
Midea EVOX G3 · 3 tons33,00037,400−30 °C: 27,6001.918.010.0$3,960
Midea EVOX G3 · 4 tons39,50048,000−30 °C: 27,2002.017.59.5$4,740
Midea EVOX G3 · 5 tons45,00054,000−30 °C: 37,3001.917.59.5$5,400

Data read live from the airgreen.ca page of each size (NEEP / AHRI certified performance). When the title names the installed size, it is highlighted; otherwise the whole range is shown. The aid shown is today’s, using Hydro-Québec’s rule ($120 per 1,000 BTU/h at −8 °C); amounts quoted in the article date from its publication. Only Hydro-Québec confirms the assistance granted.

Your numbers

And at your place?

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Before / afterThe cost of the same heat

Baseboards and electric furnaces turn 1 kWh of electricity into 1 kWh of heat. A heat pump delivers more: that is its COP. At Hydro-Québec’s rate D (11.142¢/kWh above 40 kWh a day, since 1 April 2026):

Before · baseboards11.142¢/kWh
After · heat pump–

Hydro-Québec: a heat pump can be up to three times more efficient than baseboards for heating in the colder months.

Estimate per kWh of heat, at the chosen temperature, using the certified COP from the product page. Taxes, access charge and backup heat not included.

Size checkYour electric furnace, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Check the indoor module's filter.
    • Clear winter debris from the outdoor unit.
    • Test cooling before the heat arrives.
    And at your place?

    Which type of equipment for your project?

    Pick what looks like your need.

    Mistakes avoided

    Four mistakes we do not make

    Flip each card to see what we do instead.

    Frequently asked questions

    What people ask us about this kind of work

    11 questions
    Can I keep my current ducts?
    Often, yes: the central heat pump connects to the existing ducts. We check their condition and size during the estimate.
    What happens in extreme cold?
    The indoor module (furnace or air handler) works with the central heat pump and takes over in extreme cold.
    Furnace, air handler, ducted: what is the difference?
    The furnace or air handler is the indoor module of the central system. A ducted system hides in the ceiling: all you see are small supply grilles.
    Are there grants?
    Depending on the equipment and your situation, assistance programs may apply. AirGreen checks the exact combination before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city. See permits and by-laws, and we check for your address.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Will my current thermostat work?
    Not always: the thermostat has to run the heat pump and the backup heat. We check compatibility during the estimate.
    Central or wall units: which one?
    If the house has ducts in good shape, a central system heats and cools every room at once. Without ducts, wall units or a multi-zone are often simpler. We compare on site.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.
    Going further

    Useful pages for what comes next

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    Tell us about your house. We come and see it for free.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment