Project

Installation of a GREE FLEXX R32 electric furnace in Saint-Césaire, Rouville RCM (Montérégie)

Conversion of an electric furnace to a 3-ton GREE FLEXX R32 central system in Saint-Césaire: 34,000 BTU, TRÉS2 18, CPSC2 10, electric backup heat, bypass humidifier, and measured static pressure. AirGreen HVAC expertise in Montérégie and Montréal.

By AirGreen Climatisation & Chauffage Admin14 min read
Installation of a GREE FLEXX R32 electric furnace in Saint-Césaire, Rouville RCM (Montérégie)
Installation of a GREE FLEXX R32 electric furnace in Saint-Césaire, Rouville RCM (Montérégie)
–chapters in this story
14 minreading time
–type of installation
2026year published
The tour

Take a tour of the installation

Each number is a point we check on site. Switch between summer and winter to watch air and heat move.

Generic diagram: central heat pump, indoor module and ducts

In summer, the outdoor unit rejects the house's heat outside.

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.

  2. The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.

  3. A shut-off switch near the outdoor unit isolates it safely for service.

  4. Sitting on the indoor module, it moves heat between the house air and the refrigerant.

  5. Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.

  6. Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.

  7. It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.

  8. It runs the heat pump and the backup heat. It must be compatible with the installed system.

The job

The heart of the system is in the basement, and that is where everything happens

In most installation reports, attention focuses on the outdoor unit: defrosting, snow, the pad, and noise. At Saint-Césaire, the interesting part of the project was elsewhere. All the complexity was in a small basement mechanical room, around a 74 kg gray cabinet connected to an existing ductwork network, an electric heating kit, a bypass humidifier, and a 24 VAC wall thermostat.

At AirGreen, we install central systems in Montreal, Laval, Longueuil, the North Shore, and the South Shore, and the most demanding projects are almost never the most spectacular. They are the ones where six subsystems must coexist within three square meters.

The starting point: an electrically heated home with existing ductwork

The Saint-Césaire customer had been living with a classic electric furnace: a vertical cabinet, resistance elements, a fan, and a Hydro-Québec bill that was perfectly predictable in January. The air distribution network was sound, the plenums were properly sized, and the finished basement provided acceptable clearance in front of the unit.

Their request was simple: keep the comfort of a central forced-air system, add air conditioning for Montérégie's summers, and stop paying for 100% resistance heating from October to April.

This is exactly the type of application where the GREE FLEXX R32 makes sense. The indoor unit replaces the furnace in the same space, connects to the same plenums, retains a conventional 24 VAC thermostat, and receives an integrated electric heating kit. From the living room, nothing changes. From the electric meter's perspective, almost everything changes.

The installed equipment and its certified data

The selected system is a 3-ton GREE FLEXX R32:

  • Indoor unit (air handler cabinet): GUD36AH2/G-D(U)
  • Outdoor unit: GUD36W2/NhE-D(U)
  • AHRI number : 217120760
  • Cooling capacity: 34,000 BTU/h nominal, modulation from 18,000 to 37,000 BTU/h
  • Heating capacity: 34,000 BTU/h nominal, modulation from 18,000 to 37,000 BTU/h
  • TRÉS2 (SEER2) : 18
  • CPSC2 (HSPF2) : 10
  • TRÉ2 (EER2) : 12
  • COP : 3,2
  • Refrigerant: R32, factory charge of 2.9 kg
  • Heating range: -30 °C to 24 °C
  • Cooling range: -15 °C to 54 °C
  • Power supply: 208–230 V
  • ENERGY STAR certification, including an A2L leak-detection sensor and a factory-installed Wi-Fi module

Two figures deserve emphasis because they govern actual comfort in a Saint-Césaire home. The first is the modulation range: 18,000 to 37,000 BTU/h. An inverter-driven compressor that can reduce its output to half its nominal capacity does not short-cycle in April or October, resulting in much smaller temperature differences between the basement and the upper floor. The second is the CPSC2 of 10: this is the seasonal heating index, and it—not the TRÉS2—determines what the customer will actually save in a climate where the heating season lasts seven months.

Why people still refer to it as an “electric furnace” after installation

This is the most important technical distinction in the project, and the one most often poorly explained to customers.

The installed cabinet is not a furnace in the strict sense. It is an air handler containing the system's indoor coil, blower, and an electric heating kit that serves as the former furnace. The two visible breaker blocks at the upper left of the unit supply these resistance elements.

From the building's perspective, the result is a dual-source heating system.

The exact role of the electric elements

In winter, the heat pump provides heat as long as it is capable of doing so and as long as it is economically advantageous. The electric elements intervene in only three cases:

  1. Below the balance point — the outdoor temperature at which the heat pump's capacity intersects the home's heat loss. On this project, with a nominal capacity of 34,000 BTU/h and a modestly sized home, this point is fairly low on the temperature scale, leaving the heat pump in sole control for the vast majority of the winter.
  2. During defrost — the reverse cycle momentarily cools the supply air, and some of the elements compensate so no one feels a cold draft coming from the vents.
  3. In emergency heat — if the outdoor unit is out of service, the house remains fully heated by the elements, exactly as before.
Wiring for a conventional 24 VAC thermostat

The FLEXX accepts a conventional 24 VAC thermostat, which is a real advantage: no proprietary controls, no dependence on an app, and replacement in ten years with any heat-pump thermostat on the market.

It still has to be configured correctly. Three settings must be made during commissioning, and these are the ones we most often see overlooked:

  • The thermostat configuration in heat pump with electric auxiliary heat mode, rather than conventional two-stage heating mode.
  • The reversing-valve polarity (O or B, depending on the manufacturer). An error here results in a system that cools when heating is requested.
  • The auxiliary lockout and time delay, so that the elements do not engage as soon as the thermostat is raised by two degrees. This is the setting that makes the difference between an electricity bill that goes down and one that does not.

The electrical side: what the heating kit changes in the panel

The air handler alone has very modest power consumption: MCA of 5.3 A and MOCP of 15 A for the 3-ton model. However, this figure is only part of the story, because the electric heating kit is sized and powered separately.

The panel load calculation must therefore account for the air handler, the heating kit, and the outdoor unit, whose MCA is 27.7 A and MOCP is 30 A on this model. On a replacement project like the one in Saint-Césaire, the good news is that the old electric furnace left behind a circuit already sized for full resistive heating. The bad news, in older homes in the area, is that space sometimes has to be added to the panel for the outdoor-unit circuit.

We systematically verify three things before ordering the equipment: the panel capacity, the available breaker space, and the rating of the existing conductors. A grant-eligible central system that cannot be powered is a project that comes to a halt halfway through.

The air-distribution connection: the filter base and static pressure

Under the unit, there is a galvanized sheet-metal filter base marked “Air Flow” with a marker, with an upward-pointing arrow. This detail is not decorative. It indicates the direction of airflow and reminds anyone who opens this cabinet eight years from now which way the filter should be slid in.

The decisive technical factor here is external static pressure. The air handler cabinet is designed to deliver its rated airflow at approximately 125 Pa, or 0.5 in. of water column. A ductwork system originally designed for an electric furnace generally handles this constraint well because the furnace itself offered little resistance. But once a high-density pleated filter, a bypass humidifier, and a poorly flared transition are added, this value can be exceeded without realizing it.

We measure static pressure during commissioning, on both sides of the unit. It is a ten-minute procedure that immediately reveals whether the duct system is restricting the blower. On this job, it guided the choice of thickness and density of the inner filter: a thicker media, and therefore a larger surface area, means less resistance at the same airflow while maintaining good capture.

The bypass humidifier: where most installations go wrong

The white unit mounted on the return plenum is a Honeywell Home bypass humidifier, connected to the supply plenum by the insulated flexible duct running above the unit. The red PEX line rising along the wall is its water supply.

A humidifier paired with a central heat pump requires special attention for one simple physical reason: air delivered by a heat pump is significantly cooler than air from a furnace. An evaporative humidifier that relied on 50 °C air to vaporize its water is instead supplied with air at 32 or 35 °C. Its performance drops.

What we do to ensure the system actually works:

  • Orient the bypass in the right direction: air must be drawn from the supply plenum and returned to the return plenum, never the other way around. A reversed connection sends cold air through the humidifier, and it produces almost nothing.
  • Provide a proper water supply: a compliant shutoff valve with a dedicated fitting, not a saddle valve pierced into a copper pipe. A saddle valve is a leak waiting to happen in a finished basement.
  • Close the bypass damper in summer. If left open, it short-circuits some of the conditioned air directly back to the return, reducing cooling capacity and increasing energy use. This is the only seasonal maintenance action required from the customer, and we leave a written note about it.
  • Adjust the humidistat according to the outdoor temperature. At -25 °C, an indoor humidity level of 45% causes condensation to run down the windows and eventually damages the frames. We lower the setting to between 30% and 35% during severe cold.
  • Replace the evaporative pad every year. Water in the Montérégie region is mineral-rich, and a scaled-up pad barely humidifies at all.

Condensate, slope, and cleaning openings

The PVC condensate connection exits from the bottom of the unit with a trap and a red cleaning plug. During the cooling season, the indoor coil produces a considerable amount of water, making this drain the most critical component in the entire system: when it becomes blocked, it causes water damage.

Our rules on this matter are firm:

  1. A trap sized according to the fan pressure; otherwise, it may empty or back up.
  2. A continuous slope toward the discharge point, with no concealed back-pitch behind a stud.
  3. Accessible cleaning openings, not buried behind the cabinet.
  4. Discharge into a suitable drain, never into a collection pan shared with a water heater.

The humidifier also has a purge drain, and it operates in winter, that is, outside the condensation season. Both drains must be checked at different times of the year.

The A2L leak detection sensor in an enclosed mechanical room

R32 is an A2L-class refrigerant and is slightly flammable. The FLEXX has a factory-installed A2L leak detection sensor and the associated safety logic: when a leak is detected, the indoor fan starts to dilute and disperse the refrigerant.

In a basement in Saint-Césaire where the unit is installed in a relatively enclosed room, two checks are essential. First, calculate the minimum room volume based on the refrigerant charge, as indicated in the notice affixed to the cabinet. Then ensure that the fan can actually circulate the air: a sensor controlling a fan whose grilles are blocked by storage boxes is useless. We always keep the service clearances unobstructed and explain this to the customer before leaving.

Mistakes to avoid with this type of conversion

  1. Keeping the old thermostat without reconfiguring it. A thermostat set to furnace mode will run the electric elements continuously and eliminate the heat pump's economic advantage.
  2. Neglecting the building load calculation. Simply reusing the old furnace's capacity almost always leads to oversizing, which causes short cycling and, consequently, poor humidity control in summer.
  3. Installing an overly restrictive filter because it promises better air quality. Without measuring static pressure, this guarantees a loss of airflow.
  4. Leaving the humidifier bypass damper open all year.
  5. Forgetting to weigh the refrigerant charge when the line length exceeds the 7.5 m factory charge length. The additional charge for this model is 30 g per additional metre, and the maximum distance between the units is 30 m with a maximum elevation difference of 15 m.
  6. Failing to document commissioning. Without initial readings, no technician will be able to diagnose a deviation three years from now.

Rebates and eligibility

The FLEXX is ENERGY STAR certified and has a specific AHRI number for each configuration: 217120760 for the unit installed in Saint-Césaire. These two elements are what government programs and distributors require to validate eligibility for applicable rebates.

Program criteria and amounts change depending on the period and level of government. We verify the eligibility of the exact configuration before signing, never afterward, and provide the customer with the corresponding AHRI certificate along with the invoice. This is the only way to avoid having an application rejected because a model number does not match the installed pair.

What this Montérégie project illustrates

Converting an electric furnace to a central heat pump system is not an appliance swap. It is the coordination of a ductwork network, an electrical panel, a thermostat, a humidifier, a condensate drain, and control logic for two heat sources. Each of these six elements can, on its own, undermine the system's performance.

At AirGreen, we provide HVAC installation and HVAC maintenance for central systems in Saint-Césaire, throughout the Rouville RCM and Montérégie, as well as in Montréal, Laval, Longueuil, on the North Shore and the South Shore. Our technicians measure static pressure, weigh the refrigerant charge, configure the auxiliary heat lockout, and provide written commissioning readings.

For an assessment of your home and a detailed quote for a GREE FLEXX R32 central system, contact our team. We come to your home, take measurements, and explain exactly what will be done before anything is disconnected.

The steps

The big day, step by step

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.

  1. The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
  2. The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
  3. Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
  4. The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
  5. The outdoor unitOn a level base, raised above the snow, with free space all around.
  6. The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
  7. Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
  8. Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
  9. The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
Your numbers

What would it look like at your place?

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Size checkYour electric furnace, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    Mistakes avoided

    Four mistakes we do not make

    Flip each card to see what we do instead.

    Going further

    Your own project, step by step

    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Check the indoor module's filter.
    • Clear winter debris from the outdoor unit.
    • Test cooling before the heat arrives.
    At your place

    Is your home ready?

    Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.

    0 / 6 checked
    True or false

    Four statements: true or false?

    It all comes down to details you have just seen.

    1. A central heat pump uses the house's ducts.

    2. In extreme cold, electric backup heat can take over.

    3. The filter only gets changed when the unit breaks down.

    4. You can reuse the old unit's size without checking.

    Frequently asked questions

    What people ask us about this kind of work

    11 questions
    Can I keep my current ducts?
    Often, yes: the central heat pump connects to the existing ducts. We check their condition and size during the estimate.
    What happens in extreme cold?
    The indoor module (furnace or air handler) works with the central heat pump and takes over in extreme cold.
    Furnace, air handler, ducted: what is the difference?
    The furnace or air handler is the indoor module of the central system. A ducted system hides in the ceiling: all you see are small supply grilles.
    Are there grants?
    Depending on the equipment and your situation, assistance programs may apply. AirGreen checks the exact combination before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city. See permits and by-laws, and we check for your address.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Will my current thermostat work?
    Not always: the thermostat has to run the heat pump and the backup heat. We check compatibility during the estimate.
    Central or wall units: which one?
    If the house has ducts in good shape, a central system heats and cools every room at once. Without ducts, wall units or a multi-zone are often simpler. We compare on site.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    Every house has its constraints. We see them before we install.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment