Installation of a GREE UNIX R32 central heat pump in a horizontal configuration with electric backup in Saint-Antoine-sur-Richelieu (La Vallée-du-Richelieu RCM, Montérégie)
Basement ceiling too low for an upright unit: we installed a 3-ton GREE UNIX R32 air handler (AHRI 217120760) horizontally, on wooden sleepers. The A2L sensor was relocated, a transparent trap was installed, the drain pan slope was checked, and the electric supplemental heat was calculated.
- City
- Region
- Equipment
- Brand
- Challenges
- Published
The job on one screen

The article, chapter by chapter
When basement height determines the unit's orientation
Most articles about central heat pumps focus on performance, rebates, and tonnage. In the field, the first constraint is often much more prosaic: the distance between the slab and the underside of the joists. In Saint-Antoine-sur-Richelieu, this distance dictated the entire project.
We installed a GREE UNIX R32 air handler horizontally, on wooden supports, beneath a basement ceiling that was too low for the unit to be installed upright. This orientation is not a last-minute compromise: it changes the condensate pan drainage point, the required position of the refrigerant detection sensor, service access, and how the unit is leveled. Here is how we handled it.
Saint-Antoine-sur-Richelieu: a heritage village with basements that were not
Saint-Antoine-sur-Richelieu is part of the Association of the Most Beautiful Villages of Quebec and is located in the La Vallée-du-Richelieu RCM, on the east bank of the river, opposite Saint-Denis. The village core includes old houses, some dating to before Confederation, whose basements were never designed as habitable spaces: limited headroom, full-dimension solid-wood joists, a slab poured later over a dirt floor, and a duct network added in stages over the course of three or four generations of homeowners.
This situation is found just as often in Saint-Denis-sur-Richelieu and Saint-Marc, in Verchères, and in the old neighborhoods of the South Shore and the North Shore. It consistently creates the same problem: the 3-ton air handler is 1,224 mm high, or just over 48 inches, to which a base, a return-air plenum, a supply-air plenum, and the required service clearance above must be added. Upright, the unit does not fit. On its side, it fits—provided the work is done in the right order.
What the survey revealed before the work
Our survey established what the photo shows in part:
- Insufficient clearance for a vertical installation with plenums.
- An existing galvanized sheet-metal duct system, with a black insulated flexible duct dropping diagonally across the space.
- An existing appliance to the left of the selected location, which had to be retained and worked around.
- A sound but uneven concrete slab, with no usable floor drain nearby.
- An exposed wood frame limiting the passage width and prohibiting any appliance more than 24 inches wide at that location.
The 3-ton UNIX R32 air handler is 540 mm wide (21-17/64 in) and 540 mm deep. When laid on its side, it occupies 540 mm in height instead of 1,224 mm. This arithmetic alone made the project feasible without excavating or notching the joists.
The selected equipment: GREE UNIX R32, 3-ton configuration
We chose the air-handler option rather than the cased coil option, and we explain below why the figures support this choice.
Technical specifications for the installed configuration
| Parameter | Value |
|---|---|
| Indoor unit (air handler) | GUD36AH2/G-D(U) |
| Outdoor unit (condenser) | GUD36W2/NhE-D(U) |
| AHRI reference code | 217120760 |
| Power supply | 208-230 V / 60 Hz / 1 phase |
| Nominal cooling capacity | 34,000 BTU/h (18,000–37,000 modulation) |
| Nominal heating capacity | 34,000 BTU/h (18,000–38,000 modulation) |
| Power input (cooling / heating) | 4.6 kW / 5.6 kW |
| Rated current (cooling / heating) | 22.0 A / 25.6 A |
| SEER2 | 18,0 |
| EER2 | 12,0 |
| HSPF2 | 10,0 |
| COP at 8 °C (47 °F) | 3,20 |
| Indoor airflow | 1,700 m³/h (1,000 CFM) |
| Nominal external static pressure | 125 Pa (0.5 in. w.c.) |
| Indoor / outdoor sound pressure | 51 dB(A) / 61 dB(A) |
| MCA / MOP indoor unit | 5.3 A / 15 A |
| MCA / MOP outdoor unit | 27.7 A / 30 A |
| Cabinet dimensions (W × H × D) | 540 × 1,224 × 540 mm (21-17/64 × 48-3/16 × 21-17/64 in) |
| Net cabinet / condenser weight | 74.0 kg (163.1 lb) / 85.0 kg (187.4 lb) |
| Heating range | -30 °C to 24 °C |
| Cooling range | -15 °C to 54 °C |
| Refrigerant / charge | R32 (A2L) / 2.9 kg (102.3 oz) |
| Suction line / liquid line | ø 19 mm (3/4 in) / ø 9.52 mm (3/8 in) |
| Standard / maximum piping length | 7.5 m (24.6 ft) / 30 m (98.4 ft) |
| Maximum elevation difference | 15 m (49.2 ft) |
“36000 (36/36)”: the model name and certified capacity do not say the same thing
The GREE specification sheet identifies this configuration as 36000 (36/36). The certified capacity, however, is 34,000 BTU/h in both cooling and heating. The discrepancy is not a misprint: “36” is a nominal tonnage class—a commercial convention—whereas 34,000 BTU/h is the measured value published under AHRI code 217120760.
The distinction has concrete consequences. A load calculation concluding that 35,000 BTU/h is needed at the design temperature is not covered by a “3-ton” unit in this range, despite its name. In that case, you must move to the 4-ton configuration (48,000 BTU/h certified) or accept that the electric backup heat will operate more often. We prefer to have this conversation before signing rather than on January 1.
Conversely, the 18,000 to 38,000 BTU/h heating modulation range gives the unit genuine latitude: it is not condemned to short-cycle in a home that needs only 15,000 BTU/h in October.
Ventilation cabinet or cased coil: the 3-ton figures
GREE offers two ways to build a central UNIX R32 system. The difference in certified performance is not marginal:
| 3-ton configuration | Ventilation cabinet GUD36AH2 | Cased coil GCAC36F/NhA |
|---|---|---|
| AHRI code | 217120760 | 216765692 |
| Cooling capacity | 34,000 BTU/h | 32,000 BTU/h |
| Heating capacity | 34,000 BTU/h | 35,000 BTU/h |
| SEER2 | 18,0 | 16,0 |
| EER2 | 12,0 | 11,0 |
| HSPF2 | 10,0 | 8,5 |
| COP at 8 °C | 3,20 | 3,20 |
The cased coil still has a legitimate use: it connects to an existing furnace and reduces the cost of a retrofit project, which GREE explicitly identifies as option B for installation flexibility. But it costs 2 points of SEER2 and 1.5 points of HSPF2. In an electrically heated home in the Richelieu Valley, that HSPF2 gap translates into kilowatt-hours every winter, not just on paper. The complete cabinet, with its factory-matched fan and heat exchanger, is the route we recommend when the room's geometry allows it—and here, it did, provided the unit was laid on its side.
A note for contractors consulting the same data sheet: the cased coil table published by GREE contains cells that are clearly incomplete or carried over from one column to another—notably the airflow and dehumidification capacity for the 36,000 column, and identical power entries for the 24,000 and 32,000 BTU/h columns. We systematically validate these values with the manufacturer rather than copying them into a quote.
Laying a ventilation cabinet on its side: what the orientation really changes
This is the heart of the project. A cabinet laid on its side is not an upright cabinet simply placed differently.
The factory label you must not ignore: the A2L sensor relocates
On the face of the cabinet, GREE affixes a bilingual label that reads as follows: if the unit discharges air from the side, as shown in the illustration printed on the label, the refrigerant leak sensor must be placed in the indicated location. In other words, the manufacturer anticipates side-discharge installation and requires a sensor position different from the factory position.
The reason is physical. R32 is denser than air. The detection sensor with which all GREE Canada indoor units come standard is valuable only if it is located where the refrigerant would actually accumulate in the event of a leak. When the cabinet is rotated 90 degrees, the lowest point of the unit is no longer the same: a sensor left in its factory position ends up at the top of the volume, where an R32 leak will never pass.
This is the kind of detail that no commercial brochure mentions and that can only be found in the installation manual and on the label affixed to the unit. An HVAC installation that overlooks this relocation delivers a unit whose A2L safety device is functional on paper but ineffective in practice. We check this point on every horizontal cabinet and record it on the commissioning sheet.
The condensate pan no longer has the same low point
A vertical cabinet drains by gravity toward the bottom of the coil. When laid horizontally, that same coil causes its primary pan to tilt: the drain connection to use is no longer the original one, and the pan must drain toward what has become its actual lowest point.
Two rules govern what follows:
- Leveling is transverse; slope is longitudinal. The unit must be level along the axis perpendicular to the drainage flow and slightly inclined toward the drain connection. A cabinet that is “more or less level” retains a few millimeters of water in its pan permanently: that is how odors, biological deposits, and, two years later, an overflow are created.
- The secondary pan is only mandatory in certain situations. When a horizontal unit is suspended above a finished area — a living-room ceiling or an attic space above a bedroom — a secondary drip pan with an independent drain or safety switch is required. On this job, the unit rests on the basement slab: there is no finished space below it, so the secondary pan was not required. We mention this because the opposite — omitting the secondary pan on a suspended unit — is the most costly mistake in the trade.
The condensate trap in horizontal configuration: depth, clearance, and access panels
The cabinet's fan draws air through the coil, placing the condensate pan under negative pressure. Without a sufficiently deep trap, this negative pressure holds the water back instead of letting it drain, and the pan overflows even when the piping is completely clear.
The rule we apply: the trap's water column must comfortably exceed the unit's static pressure. On a cabinet rated at 125 Pa (0.5 in. of water column), a trap with less than 25 mm of water seal is a trap that will not do its job. We systematically aim for twice that.
On this installation, three choices are worth noting:
- A clear-bodied trap, which makes it possible to check at a glance that the water seal is present, without taking anything apart. A trap that has lost its seal in winter—the water evaporates when the unit does not cool for six months—allows basement air into the pan.
- Two cleanouts with caps, placed on either side of the trap, so that future HVAC maintenance can flush and brush the line without cutting the PVC.
- A short route, inside the heated space, never against a foundation wall exposed to the north.
The wooden sleepers are not there for looks
The unit rests on pieces of wood laid on the slab. Three reasons, in order of importance:
- Adjusting the slope. A basement slab in an older house is never level. The sleepers allow the unit to be set to the desired slope toward the drain, which would be impossible if it were placed flat on the concrete.
- Breaking contact with the concrete. The fan transmits low-frequency vibrations that the slab spreads throughout the structure. Wood, with a damping material beneath the unit, interrupts this path.
- Height. Even a modest clearance beneath the unit keeps the sheet metal away from slab moisture and allows the electrical line and drain to pass without being crushed.
We never use untreated wood in direct, prolonged contact with a damp slab, and we never place a 74 kg cabinet on improvised shims: the supports must be continuous beneath the chassis rails, not isolated points under the center of a sheet-metal panel.
Service access: the panel that must be removable ten years from now
In the photo, the side panel has been removed, revealing the fan compartment, coil, and wiring. This is exactly the access a technician will need in five or ten years to replace a motor, clean a coil, or replace a control board.
A cabinet placed against a wall, with its access panel facing the masonry, becomes a unit that must be removed for servicing. We therefore position the unit based on two simultaneous clearances: the service-panel clearance and the filter clearance. In a system that must move 1,000 CFM at 125 Pa, the filter is not an accessory—it is part of the static-pressure budget and must be replaceable without tools.
The refrigerant connection: two insulated lines, not one
The lines visible in the photo are individually insulated along their entire length, including the joints, with sealing tape at the connections. This is a distinction between an air conditioner and a heat pump that many installations miss.
In an air conditioner, only the suction line is cold: it is insulated, while the liquid line remains bare. In a central heat pump, the cycle reverses in heating mode: the larger line becomes a hot-gas line, and the smaller line also operates at temperatures that justify insulation. Leaving the 3/8 in. line bare in a cold basement means losing energy six months of the year and creating condensation during the other six.
The diameters are specified: ø 19 mm (3/4 in.) for the suction line, ø 9.52 mm (3/8 in.) for the liquid line. The standard length is 7.5 m, the maximum length is 30 m, and the maximum elevation difference is 15 m. Beyond the standard length, the charge must be adjusted—and this adjustment must be documented somewhere, not left to the technician's memory.
Electric supplemental heating and the distribution panel
The MCA 5.3 A and MOP 15 A values in the table above apply to the cabinet without a heating element. GREE specifies this in a footnote: as soon as an electric supplemental heater is added, these values change and must be recalculated by a certified technician.
In the village core of Saint-Antoine-sur-Richelieu, as in many older municipalities on the South Shore, a 100 A electrical service remains common. The panel load calculation, performed before the work, determines three things at once: the rating of the supplemental heater that can be installed, whether or not a service upgrade is required, and the rating of the conductors to the outdoor unit (MCA 27.7 A, MOP 30 A).
Backup heat is not a disguised primary heating system. With stable operation advertised down to -30 °C and 100% heating capacity at -20 °C, the heat pump carries the season. The electric element handles peak demand, tempers the supply air during defrost cycles, and serves as a backup. An oversized backup system is expensive to install and even more expensive to operate because a poorly configured thermostat will always call for it too early.
The Errors We Most Often Correct on Horizontally Installed Cabinets
We regularly take over horizontal installations completed by others in Montreal, Laval, Longueuil, and the municipalities of the Richelieu Valley. The same defects keep recurring:
- The A2L detection sensor left in its factory position even though the unit was laid on its side. The device is present, powered, and will never detect an R32 leak.
- The unit installed level in both directions, without a slope toward the drain, leaving a permanent layer of water in the primary pan.
- A trap that is too short, or worse, no trap at all, on a pan placed under negative pressure by the blower.
- No cleanout access on the condensate line, turning the first maintenance visit into plumbing work.
- No secondary drain pan beneath a suspended unit installed above a finished area.
- The uninsulated liquid line, a habit inherited from air-conditioning work.
- The service panel facing a wall, a duct, or a column.
- The original duct network reused without measuring static pressure: a cabinet certified at 125 Pa that must deliver 1,000 CFM through an older home's ductwork that has been expanded three times loses airflow, then capacity, and therefore the certified performance under which it was sold.
- The condensate drain connected without a backflow preventer to a sewer drain, causing odors to return to the basement as soon as the trap dries out.
Subsidies, AHRI Code, and Administrative Pitfalls
A central heat pump with this level of performance is generally eligible for the financial assistance programs offered in Quebec, subject to the criteria in effect at the time of application. The determining factor remains the AHRI reference code for the exact installed combination — here, 217120760 — not the model number of the outdoor unit alone.
This point deserves particular emphasis on this project: the GUD36W2/NhE-D(U) condenser serves both the 2-ton and 3-ton configurations, and it also appears in combinations with a cased coil, whose AHRI codes and performance ratings are different. A rebate application prepared using only the outdoor unit number is incomplete. We provide the complete combination, its AHRI code, and the commissioning sheet, and we recommend validating the current criteria before signing the contract.
What the customer received at the end of the work
- The exact installed combination, with its AHRI code and certified performance ratings.
- Written confirmation of the relocated position of the refrigerant detection sensor, specific to the horizontal installation.
- The measured slope of the unit and the trap's water seal.
- The measured piping length and details of any charge adjustment.
- Commissioning readings: pressures, entering and leaving air temperatures, amperage draw, and measured external static pressure of the duct system.
- The rating of the installed auxiliary heating element and the recalculated MCA and MOP values.
- The procedure for maintaining the filter, trap, and cleanout openings.
AirGreen in the Vallée-du-Richelieu and Greater Montréal
Horizontal installations, low basements, older homes, and duct networks built up over time make up a significant portion of our work in Montérégie. We serve Saint-Antoine-sur-Richelieu and the entire MRC de La Vallée-du-Richelieu, as well as Montréal, Laval, Longueuil, the North Shore, and the South Shore, for both HVAC installation and HVAC maintenance of existing systems.
If you are considering a central heat pump, a wall-mounted air conditioner, a mini-split, or replacing a central system in a home where basement height is an issue, our team assesses the space, ductwork, and electrical capacity before recommending a unit. A properly completed assessment takes an hour. Installing a cabinet in an unsuitable orientation costs much more.
The job tools
Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.
Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.
How the job unfolds
The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.
We look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
The equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
Access protected, old unit disconnected and removed when it is being replaced.
Electric furnace or air handler, with its coil, connected to the supply and return ducts.
On a level base, raised above the snow, with free space all around.
Insulated, they enter through a sealed opening and run to the indoor coil.
Dedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
Leak test, vacuum, start-up, airflow check and a test of both modes.
Filter, thermostat, backup heat in extreme cold: what to know before winter.
- The on-site estimateWe look at the ducts, the current indoor module, the electrical panel and the planned spot for the outdoor unit.
- The quoteThe equipment combination, capacity and price, in writing. We check whether the combination qualifies for assistance programs.
- Getting readyAccess protected, old unit disconnected and removed when it is being replaced.
- The indoor moduleElectric furnace or air handler, with its coil, connected to the supply and return ducts.
- The outdoor unitOn a level base, raised above the snow, with free space all around.
- The refrigerant linesInsulated, they enter through a sealed opening and run to the indoor coil.
- Electrical and thermostatDedicated circuits, accessible disconnect, a thermostat that works with the heat pump and the backup heat.
- Tests and start-upLeak test, vacuum, start-up, airflow check and a test of both modes.
- The walkthroughFilter, thermostat, backup heat in extreme cold: what to know before winter.
What we check on a job like this one
Each number is a point we check on site. Switch between summer and winter to watch air and heat move.
In summer, the outdoor unit rejects the house's heat outside.
Generic illustration of this type of installation, not a survey of this job site. Tap a number.
It captures or rejects heat outside. It sits on a level base, above the snow, with free space all around.
The insulated refrigerant lines enter the house through a sealed opening and run to the indoor coil.
A shut-off switch near the outdoor unit isolates it safely for service.
Sitting on the indoor module, it moves heat between the house air and the refrigerant.
Electric furnace or air handler: its fan pushes air through the ducts. The electric backup takes over in extreme cold.
Supply ducts bring air to the rooms; returns bring it back to the unit. Their condition matters as much as the unit's.
It protects the coil and the fan. A dirty filter cuts airflow, so it gets checked regularly.
It runs the heat pump and the backup heat. It must be compatible with the installed system.
Is your home ready?
Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.
Good habits, once the unit is in place
Six simple habits that keep the unit going. Your list stays on this device.
What to do, season by season
Three habits per season for this unit. They take a few minutes and prevent many calls.
- Check the indoor module's filter.
- Clear winter debris from the outdoor unit.
- Test cooling before the heat arrives.
- Check the filter more often in peak season.
- Keep registers and returns clear.
- Watch condensate drainage near the coil.
- Change or clean the filter.
- Test heating and backup heat before the cold.
- Book periodic maintenance.
- Clear snow around the outdoor unit.
- Store nothing in front of the indoor module.
- Note any unusual noise or smell and call us.
The right pages, at the right time
Four statements: true or false?
It all comes down to details you have just seen.
1. A central heat pump uses the house's ducts.
It connects to the existing ducts to heat and cool everywhere.
2. In extreme cold, electric backup heat can take over.
The indoor module (furnace or air handler) works with the heat pump and takes over in extreme cold.
3. The filter only gets changed when the unit breaks down.
A dirty filter cuts airflow. It gets checked regularly.
4. You can reuse the old unit's size without checking.
The house may have changed: insulation, windows, added rooms. Capacity is confirmed on site.
0 / 4 right answers
What people ask us about this kind of work
Can I keep my current ducts?
What happens in extreme cold?
Furnace, air handler, ducted: what is the difference?
Are there grants?
Do I need a permit?
How much can I save?
How is the LogisVert assistance calculated?
Will my current thermostat work?
Central or wall units: which one?
Does AirGreen hold the required licences?
Is the estimate free?
No question matches. Write to us: we answer.
More jobs to see, near you
By town, by equipment or by region: browse more than 4,700 published projects.
Each dot: a town where AirGreen has published projects. The glowing dot: this job.
An on-site estimate, the right capacity, the right equipment.
The on-site estimate is free and the quote follows within 24 hours.
Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).
