Installation of a 5-head GREE FreeMatch R32 multi-zone heat pump (GWHD(42)ND6MO) in Pointe-des-Cascades, Vaudreuil-Soulanges RCM

Five GREE FreeMatch R32 indoor units connected to a GWHD(42)ND6MO in a Pointe-des-Cascades grocery store: why the refrigerated display cases and the hood determine the sizing, why air is never blown into a food-preparation room, and the suspended-ceiling trap.

By AirGreen Climatisation & Chauffage Admin16 min read
Installation of a 5-head GREE FreeMatch R32 multi-zone heat pump (GWHD(42)ND6MO) in Pointe-des-Cascades, Vaudreuil-Soulanges RCM
Installation of a 5-head GREE FreeMatch R32 multi-zone heat pump (GWHD(42)ND6MO) in Pointe-des-Cascades, Vaudreuil-Soulanges RCM
–chapters in this story
16 minreading time
–type of installation
2026year published
The tour

Take a tour of the installation

Each number is a point we check on site. Switch between summer and winter to watch air and heat move.

Generic diagram: wall-mounted heat pump, indoor and outdoor units

In summer, the outdoor unit rejects the house's heat outside.

Generic illustration of this type of installation, not a survey of this job site. Tap a number.

  1. Mounted level on a wall plate, high enough for the air to reach the whole room, with enough space around it to slide the filters out easily.

  2. The refrigerant lines, the communication cable and the drain go through the wall in a single opening, sealed against water, cold air and insects.

  3. Two insulated copper pipes connect the two units. Outside, a line cover can protect them from sun, knocks and weather.

  4. A shut-off switch near the outdoor unit isolates it safely for service. It must stay accessible at all times.

  5. The compressor and the fan. In heating mode it captures heat from the outdoor air, even in winter, and moves it inside.

  6. On the ground or on the wall, it keeps the unit above accumulated snow. The unit stays clear and defrost water can drain away.

  7. The fan needs to blow freely. Storage, a fence or a wall too close, and efficiency drops while noise goes up.

The job

Cooling a food-service premises: five zones at the entrance to the Soulanges Canal

This Pointe-des-Cascades project is not a house. The photo says so in three details: a suspended ceiling with exposed framing and round recessed lights, a white raceway running along the wall to the GREE wall-mounted head, and, at the bottom of the frame, a stack of disposable cups in front of a glass-front refrigerated display case.

This is a food-service commercial premises, near the entrance to the Soulanges Canal and Parc des Ancres, in a village where a large share of traffic is concentrated between June and September. This combination—cooking, refrigeration, seasonal customers, and hygiene requirements—overturns several of the rules we apply in residential settings.

This is the fourth non-residential project in this series, after an office in Sainte-Julie, a community building in L'Île-Perrot, and a service business in Pointe-Fortune, and the first in food service.

The load of a food-service premises does not come from the building envelope

In a house, the cooling load comes from the sun, windows, and insulation. In a food-service premises, it comes from inside, and it never stops.

Three sources dominate, and none appears on an architect's plan:

  • Refrigeration releases its heat into the room. Every refrigerated display case, chest freezer, and ice machine has a condenser, and that condenser releases into the premises exactly the heat it removes from its contents, plus the heat from its own motor. A business that adds a second display case adds a permanent cooling load, twelve months a year.
  • Customers. A food-service operation concentrates occupants in a small area, with rapid turnover, each person contributing sensible heat and moisture.
  • Lighting and countertop appliances — toasters, countertop ovens, warming plates, coffee makers.

The consequence is counterintuitive for a business owner: the premises may call for cooling in November, while the house next door is being heated. This is also what makes a modulating multi-zone system particularly well suited here, since it can handle a small cooling load during the cold season—something a fixed-speed unit does very poorly.

We had published similar reasoning for an office in Sainte-Julie. The difference in food service lies in the refrigeration, which is absent from an office and turns an intermittent occupancy load into a permanent load.

The kitchen hood puts the room under negative pressure

This is the point most often overlooked in commercial air-conditioning quotes, and it alone can cause a perfectly sized system to fail.

A commercial hood exhausts a substantial volume of air. That air must be replaced. If there is no dedicated make-up air supply, or if it is insufficient, the room goes into negative pressure and draws air through every available air leak: under the doors, through the entrance door that opens for each customer, and around pipe penetrations.

What this does to a wall-mounted heat pump:

  1. It is constantly fighting untreated outdoor air — 30 °C and humid in July, -15 °C in January.
  2. The actual load becomes much higher than the load calculated from the building envelope, and the head appears undersized even though it is not.
  3. Cold drafts appear at floor level, near the doors, exactly where customers are seated.

Our position on this type of project: the make-up air supply must be validated before sizing the heads, together with the ventilation contractor and the owner. An air-conditioning unit does not replace a ventilation system, and a wall-mounted heat pump introduces no outdoor air — it recirculates the room air through a coil. We stated this principle in a residential context in our Beauharnois article; in food service, it is no longer merely a comfort consideration, but a condition for proper operation.

This is also why the cooking area beneath the hood did not receive a head. A comfort appliance installed within the field of a commercial hood, in air laden with greasy aerosols and subject to constant negative pressure, quickly becomes dirty and operates poorly.

Sizing: refrigeration decides, not floor area

A business in which all zones are occupied at the same time is not sized like a house. We developed this reasoning — the diversity factor collapses as soon as simultaneity is complete — in our Pointe-Fortune article, for a service business in the same regional county municipality. The principle applies fully here: at noon, all five zones call for heating or cooling together.

The installed allocation therefore totals 36,000 BTU/h, or 86% of the nominal cooling capacity of the GWHD(42)ND6MO and approximately 81% of its maximum modulating capacity of 44,300 BTU/h. This is the lowest ratio we have published in this series, and it means one simple thing: the compressor can supply all five heads at full capacity simultaneously, with room to spare.

What is specific to this project is how the capacities are distributed among the zones. It was not the floor area that decided the matter, but the location of the refrigeration equipment:

Zone Capacity What determined the capacity
Service counter and refrigerated display cases 9,000 BTU/h Heat rejected by condensers + staff
Front room, entrance and window side 9,000 BTU/h Customers, solar gain, door openings
Back room 6,000 BTU/h Customers only
Cold-preparation room, no cooking 6,000 BTU/h Small space, limited occupancy
Office and storage room 6,000 BTU/h Intermittent occupancy

The counter area occupies a modest floor space yet receives the same capacity as the front room, which is twice as large. A calculation based on square footage would have produced the opposite result, and the person working eight hours behind that counter would have paid the price.

The trade-off must be acknowledged. A closed premises on a Tuesday in November requires very little, and a single small zone calling for cooling on its own can drop below the system's modulation floor, 8,870 BTU/h, resulting in short-cycling—the mechanism discussed in our Saint-Chrysostome article. The free solution: during the off-season, leave two zones running instead of just one.

The opposite approach—installing five 12,000 BTU/h units “just to be sure”—would have produced five oversized appliances that short-cycle outside peak hours, dehumidify poorly, and make noise in a room where people talk.

Where not to blow air in a food-service area

Positioning a unit in a space where food is handled involves constraints that exist nowhere else.

  • Never blow air directly onto a preparation surface, uncovered food, or a handwashing station. An air stream moves particles, and a comfort appliance is not filtration equipment.
  • The condensate drain must never run above a work surface, preparation counter, or open piece of equipment. An overflow above a food counter is not a stain on the wall; it is a health incident.
  • Everything we install must remain cleanable and accessible. A wall-mounted unit and its line-hide form a horizontal surface high up that collects dust and aerosols. It must be possible to wipe it down without dismantling anything.
  • The maintenance frequency is not the same as in a residence. Here, we recommend cleaning the filters much more frequently than at home, along with thorough coil cleaning by a technician at short intervals. Greasy aerosol buildup also occurs in the dining area, not just in the kitchen—we developed this point in our Saint-Stanislas-de-Kostka article, for an open residential kitchen.

Blowing on a refrigerated display case

The glass-fronted display case visible at the bottom of the photo deserves its own rule. A comfort-air jet directed toward a refrigerated display case produces two effects, both undesirable:

  • The display case load increases. Air moving against its walls and air curtain accelerates its heat exchange with the room, its compressor runs more often, and it rejects even more heat into the space—the snake biting its own tail.
  • Condensation appears on the glazing when warm, humid air is actively pushed against a cold surface.

The unit was therefore oriented to sweep across the room without aiming at the display case, and the air-discharge louvers were adjusted accordingly during commissioning.

Everything is visible, everything must be cleaned: exposed conduit and suspended ceiling

The second lesson from this project is evident in what the photo shows without saying: nothing is hidden. The conduit is exposed, it meets the suspended ceiling, and a white pipe runs upward to the right of the unit.

Why we did not hide the piping in the ceiling void

A suspended ceiling offers a tempting service space, and we use it regularly—that is exactly what we did in the Sainte-Julie office. In a food-service space, the reasoning is reversed for three reasons:

  1. A ceiling void is an inaccessible space. Anything that gets dirty in it cannot be cleaned, and anything that leaks there cannot be seen. Surface-mounted conduit can be wiped with a cloth and removed with a screwdriver.
  2. Inspection is immediate. A trace of moisture on exposed conduit is spotted in passing; the same trace above the ceiling tiles is discovered when a tile becomes stained—which is too late.
  3. A suspended ceiling grid is not a load-bearing structure. Any piping that passes through this space must be supported independently of the grid, from the slab or structural framework, and never suspended from the T-grid.

The choice of exposed conduit is therefore an operational decision, not an aesthetic compromise. We announce it before the work begins, because visible conduit is always a surprise when it has not been mentioned.

The point that almost no one checks: is the ceiling void a return-air plenum?

In many commercial buildings, the space above the ceiling tiles is not just used to hide pipes: it serves as a return-air plenum for the ventilation system. Air from the room rises into it, circulates, and returns to the air-handling unit.

This completely changes the status of what is installed there. In a return-air plenum, exposed materials are subject to requirements for flame spread and smoke developed—which is why communication cables sold for these spaces carry a specific designation.

However, a refrigerant line set is insulated with combustible elastomeric foam. Running a set of insulated lines through a return-air plenum without verifying its status is a silent error: it is not apparent during commissioning or the first winter, but it emerges during an inspection or insurance renewal.

Our method:

  • Ask the owner and the ventilation contractor before choosing the route: is this void a return-air plenum, or simply a service void?
  • If it is a plenum, favor a surface-mounted route in a cable tray beneath the ceiling—which is exactly what was done here—or use materials rated for this application.
  • Never solve the problem by cutting the insulation where it passes through. An uninsulated suction line in an air-conditioning system will condense and cause water to drip where no one can see it. We documented this mechanism in our articles on Saint-Étienne-de-Beauharnois and Saint-Louis-de-Gonzague.

The rising drain

The white pipe running upward on the right side of the unit indicates that gravity drainage was not available and that a condensate pump was installed to reach a higher drain point—a common situation in commercial premises, where the drain connects to an existing network at ceiling level.

We covered the drain design of a five-zone system in detail in our Cèdres article, so we will not revisit it here. However, two requirements specific to food-service environments apply:

  • The float safety switch is non-negotiable and must stop the associated head, not merely trigger an alarm. In a food-service business, an overflow above a counter can interrupt service.
  • The pump reservoir belongs on the maintenance schedule. This is exactly where biofilm forms, and in a food-service space, this buildup manifests as an odor well before it causes a breakdown.

Mistakes to avoid when air-conditioning a commercial food-service space

  • Size by floor area. Two identical premises do not have the same load if one has three refrigerated display cases and the other has none.
  • Apply a residential diversity factor to a business where all areas are occupied at the same time.
  • Ignore the hood and makeup air. This is the leading cause of commercial systems being deemed “undersized” when they are actually adequate.
  • Place a head within the field of a cooking hood.
  • Direct the supply air toward a refrigerated display case or a food-preparation surface.
  • Run insulated lines through a return-air plenum without verifying the status of that space.
  • Apply a residential maintenance schedule to a unit operating twelve hours a day in heavily polluted air.
  • Schedule the work during the busy season. Installation takes place outside peak periods, and commissioning is performed with the premises empty.

The figures that drove the decisions

Data (GWHD(42)ND6MO) Value
Connectable indoor units 2 to 5
Rated cooling capacity 42,000 BTU/h
Maximum modulated cooling capacity 44,300 BTU/h
Modulation floor 8,870 BTU/h
SEER2 / HSPF2 / EER2 21 / 10 / 12
MCA / maximum protection 30 A / 45 A
Precharged / maximum total length 50 m / 100 m
Additional charge 20 g/m
Refrigerant R32, 2,700 g
AHRI codes (ductless / ducted / mixed) 214931590 / 214931596 / 214931600
Warranty 10 years, 12 years upon registration with the distributor

The GWHD(42)ND6MO is the only unit in the FreeMatch R32 range that accepts five indoor units; the model was therefore determined before any calculations, as we explained in our Sainte-Martine article. The ratio between the modulation floor and maximum capacity is the decisive figure here because it precisely defines the difference between a November Tuesday and a July Saturday.

Financial assistance: the commercial program is not the residential program

LogisVert, Rénoclimat, and Chauffez vert are intended for the residential sector. A business does not qualify simply because a residential unit has been installed in a commercial space.

For a commercial building, financing generally goes through Hydro-Québec's energy-efficiency programs for businesses and government programs such as ÉcoPerformance, whose criteria and terms differ completely from those for residential properties—the same approach used for the Sainte-Julie office and the L'Île-Perrot community building. We assess eligibility on a case-by-case basis, supported by detailed invoices and the AHRI certification for the actual combination installed, before promising anything to a business customer.

AirGreen in Pointe-des-Cascades, Vaudreuil-Soulanges, and Montreal

Pointe-des-Cascades occupies the point where the Ottawa River meets the St. Lawrence River, at the entrance to the Soulanges Canal, in the Vaudreuil-Soulanges RCM, about thirty minutes west of Montreal. We regularly serve this area: Les Cèdres, Les Coteaux, Coteau-du-Lac, Vaudreuil-Dorion, and L'Île-Perrot.

At AirGreen, we install wall-mounted heat pumps, central heat pumps, air conditioners, and air exchangers for homeowners and businesses in Montreal, Laval, Longueuil, the North Shore, and the South Shore. A commercial space is assessed on-site, appliance by appliance, including the hood, before a model is recommended.

The steps

The big day, step by step

The main steps of this kind of job at AirGreen. Every house has its quirks: the estimate brings them out.

Step 1 of 9The on-site estimate

We look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.

  1. The on-site estimateWe look at the room, the outside wall, the line route and where the outdoor unit will go. That is where the capacity gets chosen.
  2. The quoteModel, capacity and price, in writing. We also check whether the model qualifies for assistance programs.
  3. Getting readyFloors and furniture protected, wall plate position marked level, wall opening located.
  4. The wall openingA single opening, with the slope the drain needs to flow outside.
  5. The outdoor unitSet on a stand raised above the snow, with the clearances the manufacturer requires.
  6. Lines, cable and drainConnected, insulated and protected. The opening is then sealed against water, cold air and insects.
  7. The electrical workA dedicated circuit and an accessible disconnect near the outdoor unit.
  8. Tests and start-upLeak test, vacuum, then start-up and a check of heating and cooling.
  9. The walkthroughRemote, modes, filters: we show you the essentials before we leave.
Your numbers

What would it look like at your place?

Two quick checks with real numbers: what heat costs, and what your current heaters add up to in BTU/h.

Size checkYour baseboards, in BTU/h
–BTU/h of installed electric heat

    Conversion: 1 W = 3.412 BTU/h. An indication, not a load calculation: baseboards and furnaces are often stronger than the real need, and they can stay as backup. AirGreen confirms the capacity on site.

    Mistakes avoided

    Four mistakes we do not make

    Flip each card to see what we do instead.

    Going further

    Your own project, step by step

    Through the seasons

    What to do, season by season

    Three habits per season for this unit. They take a few minutes and prevent many calls.

    • Clean the indoor unit's filters.
    • Clear leaves and debris left on the outdoor unit by winter.
    • Test cooling before the first hot days.
    At your place

    Is your home ready?

    Check what applies at your place. A "no" is not a refusal: it is what we sort out during the estimate.

    0 / 6 checked
    True or false

    Four statements: true or false?

    It all comes down to details you have just seen.

    1. In heating mode, the outdoor unit can produce water.

    2. You pick the capacity with a simple square-footage rule.

    3. A multi-zone connects several indoor heads to a single condenser.

    4. The disconnect can sit behind the patio furniture.

    Frequently asked questions

    What people ask us about this kind of work

    12 questions
    Does a wall-mounted heat pump heat in winter?
    Yes, it heats and cools. Its capacity drops in very cold weather; the operating range depends on the model and is listed on its spec sheet.
    Wall-mounted or multi-zone: how do I choose?
    One wall head and one condenser outside: the direct solution for a room or an open area. For two to five rooms, a multi-zone puts one head in each room on a single condenser.
    Where does the outdoor unit go?
    Where it stays above the snow, clear and accessible, away from walkways. We decide it with you during the estimate.
    Are there grants?
    Depending on the model and your situation, assistance programs may apply, including Hydro-Québec's LogisVert. AirGreen checks the model number before quoting an amount. See the grants.
    Do I need a permit?
    Rules vary from city to city: location, distances, noise. See permits and by-laws, and we check for your address.
    How cold can it heat?
    It depends on the model. According to Hydro-Québec, newer models work down to a temperature between −15 °C and −25 °C, and some cold-climate models are certified lower. The minimum temperature is on each unit's spec sheet.
    How much can I save?
    Hydro-Québec says a heat pump can be up to three times more efficient than baseboards for heating in the colder months. The result depends on the house, the climate and how it is used.
    How is the LogisVert assistance calculated?
    For ENERGY STAR cold-climate certified heat pumps, Hydro-Québec lists assistance of $120 per 1,000 BTU/h of heating capacity at −8 °C. AirGreen checks the exact model before quoting an amount; only Hydro-Québec confirms the assistance granted. See the grants.
    Is it noisy?
    The sound level depends on the model and is listed in decibels on each unit's spec sheet. Location matters too: when possible, we avoid putting the outdoor unit under a bedroom window.
    The outdoor unit is covered in ice: is that normal?
    Some frost is: the unit runs defrost cycles. Never hit the ice. If the unit stays iced up or stops heating, call us.
    Does AirGreen hold the required licences?
    Yes. AirGreen holds RBQ licence 5645-9605-01, subclasses 15.8 Ventilation, 15.10 Refrigeration and 16 Electricity.
    Is the estimate free?
    Yes. The on-site estimate is free and the quote follows within 24 hours. Book my free estimate.

    Could this job help a neighbour?

    Share
    Similar projects

    More jobs to see, near you

    By town, by equipment or by region: browse more than 4,700 published projects.

    Each dot: a town where AirGreen has published projects. The glowing dot: this job.

    All our projects

    Your project

    Every house has its constraints. We see them before we install.

    The on-site estimate is free and the quote follows within 24 hours.

    • RBQ licence5645-9605-01 · 15.8, 15.10, 16
    • EstimateOn site, free
    • QuoteWithin 24 hours

    Text and photo: a real AirGreen Climatisation & Chauffage job. The diagrams are generic illustrations of the type of installation, not a survey of this job site. Sources of the added figures: airgreen.ca product pages (NEEP / AHRI performance), Hydro-Québec (Heat pumps page, LogisVert, read on 13 October 2026), Régie de l’énergie (rate D as of 1 April 2026).

    Leave a comment