AirGreenUponor
Uponor · hydronic radiant floorsThe Uponor space at AirGreenThe A3100101 thermostat, sold by AirGreen in Montréal, Laval, Longueuil, the South Shore and the North Shore. Price on quotation.
The Uponor warranty
Business hours: Mon. to Thu. 8 a.m. to 6 p.m., Fri. 8 a.m. to 4 p.m.
Uponor · Sources checked on October 20, 2026

Uponor A3100101: the thermostat for one radiant floor zone

A heat-only thermostat built for hot-water radiant floors. Two wires at 24 V, a touchscreen, and three control modes: air, floor or both, with an optional slab sensor.

Uponor A3100101 touchscreen thermostat
What Uponor’s manual says
Heat-only Thermostat with Touchscreen, A3100101
Heat only, 24 VAC, Class II circuits
Two wires with power sharing (Rh and W): no C wire, no batteries
Large-number touchscreen, automatic differential and pulse width modulation (PWM)
Slab sensor A9010599 sold separately: it unlocks the floor modes
Non-programmable, no Wi-Fi
A3100101 manual (0221) and Uponor submittal, read on Oct. 20, 2026.
2 wires24 VAC, no C wire
3 modesair, floor or both
1 to 35 °Cfloor setpoint (34 to 95 °F)
1.3 Aoutput, about 6 actuators
AirGreen × UponorA3100101Heat only, 24 VTwo wires, no C wireAir, floor or bothOptional A9010599 slab sensorMontréal · Laval · Longueuil · South Shore · North Shore
01 · Call for heat

From thermostat to boiler, in five steps

Uponor’s wiring diagram shows what happens when a room cools down. Pick your setup and how far the room is below setpoint, then step through it.

The zone is opened by…
The room is below setpoint by…
  1. ThermostatA3100101
  2. Zone control moduleA3031003 / A3031004yellowred
  3. Actuators at the manifoldA3023522
  4. Pump relayA3010100
  5. Circulator and boilerrelay dry contacts
At rest
The zone is at rest
The thermostat starts a call for heat once the room drops 1 °F below setpoint. Step forward to follow the chain.

Per Uponor: CDAM design manual, 8th edition (CDAM_1023), wiring schematics 1 and 2 (p. 145 and 146), and the A3100101 manual (0221) for the call and modulation. These are Uponor’s diagrams with Uponor parts; another module, relay or boiler is checked case by case on quotation.

02 · Air or floor

Control the room, the floor, or both

Uponor’s manual offers three modes. The floor covering sets the surface temperature not to exceed. Answer three questions.

Floor covering
What matters most
Is a slab sensor already in the floor?

Uponor: a surface of 80 °F (26.7 °C) at most for hardwood, and generally 87.5 °F (30.8 °C) at most for other finished floors. Also check your flooring manufacturer’s limit.

Recommended mode
Air (operative temperature)
Possible with the A3100101
The thermostat controls the room by the temperature you feel.
  • Without a sensor, only the air mode is possible, with no floor limit.
  • A sensor wires to SEN1 and COM: to be confirmed at the estimate.
  • Hardwood: the manual presents the floor limit as protection for wood floors. It needs the sensor.
  • Surface not to exceed per Uponor: 26.7 °C (80 °F) for hardwood.

AirGreen × Uponor

Uponor’s thermostat, picked for your zone.

Uponor designs the thermostat, the control chain and the rules that go with them. AirGreen starts from your module and your floor to tell you whether the A3100101 fits, on quotation.

Uponor

What Uponor brings

  • Since 1918A Finnish company; Wirsbo PEX pipe since 1972; part of the GF group since 2023.
  • A3100101A two-wire 24 V heat-only thermostat, built for hydronic radiant heating.
  • Its wiring diagramsThermostat, module, actuators, relay, circulator: the CDAM manual describes them.
  • Its limited warrantyUponor Ltd.’s, with its conditions, as Uponor writes it.
AirGreen

What AirGreen brings

  • Sold by AirGreenIn Montréal, Laval, Longueuil, the South Shore and the North Shore.
  • Uponor’s rules, appliedBoth tools follow its documents and add nothing to them.
  • Free estimatePrice on quotation.
  • RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16; hydronic work by a partner holding subclass 15.4.

The result: a thermostat picked for your module and your floor covering, price on quotation.

03 · The A3100101

One thermostat, and the parts Uponor puts around it

We sell the thermostat. The manual also names the Uponor parts that go with it in a zone; they are not in our shop.

Uponor A3100101 radiant floor thermostat

Uponor A3100101

Heat-only touchscreen thermostat for hydronic radiant floors.

  • Air setpoint from 1 to 30 °C (34 to 86 °F)
  • Floor setpoint from 1 to 35 °C (34 to 95 °F)
  • Maximum floor limit adjustable up to 35 °C (95 °F)
  • Freeze protection at 3 °C (37 °F) in Off mode
  • 136.9 × 81.8 × 16 mm (5.39 × 3.22 × 0.63 in) per the manual; the submittal gives 0.801 in deep
View the product
A901059910k slab sensor, 10 ft lead extendable to 250 ft (18 AWG)
A3031003 · A3031004Zone control modules, 3 or 4 zones
A3010100Single-zone pump relay
A3011075Zone valve
A305005024 VAC transformer
10 kΩ resistorIncluded, for some other-brand relays, valves or boilers

Parts named in the A3100101 manual; A9010599, A3031003 and A3031004 shown as “Active” on Uponor’s Canadian site on Oct. 20, 2026.

04 · Before you order

Four checks before you replace a thermostat

Taken from Uponor’s manual and submittal. They help you avoid ordering a thermostat that does not fit the system in place.

1

A hot-water floor

The A3100101 is a 24 V thermostat for hydronic radiant heating. Uponor’s documents mention no electric floor.

2

The module in place

With an Uponor A3031003 or A3031004 module, Rh and W go to terminals 2 and 3. With another relay, the 10 kΩ resistor may be needed.

3

The load

Output of 1.3 A at 24 VAC, which is about six actuators per thermostat according to the manual.

4

The location

Interior wall, about 5 ft (1.5 m) above the floor, away from heat sources and drafts.

What AirGreen does

We sell the thermostat and advise you on the mode, the sensor and the parts, based on Uponor’s documents.

Who does the work

A partner holding RBQ subclass 15.4 does the hydronic work. The manual reserves installation for professionals familiar with low-voltage wiring.

AirGreen × UponorUponor Ltd. limited warrantyUponor Ltd., MississaugaPrice on quotationRBQ 5645-9605-01Free estimateMontréal · Laval · Longueuil · South Shore · North Shore
05 · Warranty and grants

Uponor’s warranty, and the grants checked as of October 20, 2026

What Uponor Ltd.’s limited warranty and the programs themselves say.

Uponor Ltd. limited warranty

For installations made after May 12, 2026 (document 051226).

  • Controls and thermostats are not named in it: we show no term.
  • Installation by a certified, licensed plumbing contractor recognized by Uponor, per Uponor’s instructions
  • It starts on the installation date; refund, repair or replacement, at Uponor’s option
  • Labour excluded
  • Ask whether the contractor you choose is recognized by Uponor.

Read Uponor’s warranty (PDF)

ENERGY STARNot listed

No Uponor on the list of certified smart thermostats.

ÉnergirNot eligible

The grant targets a Wi-Fi thermostat on its ENERGY STAR list: the A3100101 is not on it.

LogisVertNot eligible

LogisVert has no thermostat measure.

HiloNot applicable

Its floor thermostat is for electric floors, not water-based systems.

Uponor in brief. Founded in 1918 in Lahti, Finland. Wirsbo, which has made PEX pipe since 1972, joined it in the late 1980s. Uponor has been part of the GF group since the successful offer of November 2023; in April 2024, GF renamed the division GF Building Flow Solutions and kept the Uponor brand. In Canada: Uponor Ltd., in Mississauga, Ontario.
06 · FAQ

Common questions about the Uponor thermostat

Does this thermostat work with an electric floor heating mat?

No. The A3100101 is a 24 V thermostat for hydronic radiant floors, wired to a zone module, a relay or a valve. Uponor’s documents mention no electric floor. For an electric floor, see our other thermostats.

Is a C wire needed?

No. It runs on two wires with power sharing, on terminals Rh (R) and W, with no polarity. It has no batteries. The floor sensor wires separately, to SEN1 and COM.

Is it programmable?

No. Uponor’s submittal calls it non-programmable: you set the temperature and it holds it. The manual has no schedule.

Does it have Wi-Fi?

No. No wireless connection and no app.

Is the floor sensor included?

No. The A9010599 slab sensor (10k) is sold separately. Its 10 ft lead extends up to 250 ft in 18 AWG. Without it, only the air mode is possible.

What floor temperature for hardwood?

Uponor’s design manual sets 80 °F (26.7 °C) at most at the surface for hardwood, and generally 87.5 °F (30.8 °C) for other finished floors. With the slab sensor, the A3100101 applies a maximum floor limit adjustable up to 35 °C (95 °F).

Does it work with another brand’s module?

The manual allows other makers’ relays, valves or boilers, sometimes with the included 10 kΩ resistor. Each setup is checked on quotation.

How many actuators per thermostat?

The output is 1.3 A at 24 VAC, which is about six actuators according to Uponor’s manual.

Why doesn’t the circulator start right away?

In Uponor’s diagram, the module waits until the actuator or valve is open: the end switch closes, then the ES-ES contact powers the pump relay.

What happens if a sensor fails?

Per the manual, the thermostat falls back to an 18 °C (65 °F) air setpoint. In Off mode, freeze protection holds 3 °C (37 °F).

What is the warranty?

Uponor Ltd.’s, for installations made after May 12, 2026. Thermostats are not named in it, so we show no term. It requires a contractor recognized by Uponor and excludes labour.

Is there a grant for this thermostat?

None among the programs checked as of October 20, 2026. It is not ENERGY STAR listed, it is not on Énergir’s list, LogisVert does not cover thermostats and Hilo is for electric floors.

Who does the work?

AirGreen sells and advises. A partner holding RBQ subclass 15.4 does the hydronic work.

Who is Uponor?

A company founded in 1918 in Finland, known for Wirsbo PEX pipe. It has been part of the GF group since 2023; the Uponor brand is kept. In Canada, Uponor Ltd. is in Mississauga.

AirGreen · Montréal, Laval, Longueuil, South Shore and North Shore

Tell us how your floor is wired and we’ll tell you whether the A3100101 fits

Free estimate and sale of the Uponor A3100101 thermostat across Greater Montréal. Price on quotation.

Showroom1370 Joliot-Curie Street, Unit 712, Boucherville
HoursMon. to Thu. 8 a.m. to 6 p.m. · Fri. 8 a.m. to 4 p.m.
RBQ 5645-9605-01Subclasses 15.8, 15.10 and 16

Sources checked on October 20, 2026

  1. Uponor Canada — Heat-only thermostats with touchscreen (A3100101 and A9010599, status Active), read Oct. 20, 2026
  2. Uponor — A3100101 installation and operation manual (A3100101_Heat-onlyThermostat_Manual_0221, © 2021)
  3. Uponor — A3100101 submittal (© 2026 Uponor North America), read Oct. 20, 2026
  4. Uponor — Complete Design Assistance Manual, 8th ed. (CDAM_1023, © 2023): ch. 2, 11, 12, 16 and schematics p. 145-146
  5. Uponor — zone control module instruction sheet (ZoneCtrlMdl_IS_H300_0113, © 2013)
  6. Uponor Ltd. — Limited warranty, installations after May 12, 2026 (051226)
  7. Uponor — company history, read Oct. 20, 2026
  8. GF — “GF Uponor becomes GF Building Flow Solutions”, April 29, 2024; tender offer result, Nov. 6, 2023
  9. ENERGY STAR — certified smart thermostats (dataset 7p2p-wkbf, updated Oct. 18, 2026)
  10. Énergir — smart thermostat grant and eligible list PE204 (April 1, 2026)
  11. Hydro-Québec — LogisVert eligible measures, read Oct. 20, 2026; Hilo floor thermostat compatibility

Uponor and Wirsbo are trademarks of their owners. AirGreen sells this thermostat; the warranty is the manufacturer’s.

Price on quotation · free estimate. The Uponor thermostat below.

The Uponor shop

The A3100101 thermostat, right below.

Open the product page. Price on quotation.

Uponor