How to read a NEEP record and an AHRI certificate

Home / Comparisons / Guides: reading the records

Guide · Reading the records · NEEP record and AHRI certificate

How to read a NEEP record and an AHRI certificate

The numbers on our comparison pages come from two documents few people have ever opened: a unit’s AHRI certificate and its record on the NEEP list. This guide opens a real record, for a wall-mounted heat pump sold by AirGreen, and explains every field: what it measures, at what temperature, and who stands behind it.

NEEP record no. 392122 AHRI certificate no. 214888802 Record consulted on November 9, 2026
FUJITSU AIRSTAGE ORION XLTH 12,000 BTU (AirGreen image)
The example unitFUJITSU AIRSTAGE

ORION XLTH · 12,000 BTU

ASUH12KZAS / AOUH12KZAH1 · AHRI 214888802

See the product page
+++
Its NEEP recordDiagram. The real record is reproduced below, field by field.
Season cost

Two fields of the record feed the season cost estimate

On our comparison pages, the cost estimate starts from two values of this record: Region V HSPF2 for winter and SEER2 for summer. This guide shows no dollar amount; it shows where these two fields are and what is done with them. The pages below run the calculation in dollars for this unit.

HSPF2 (Region V)Field of the record, without the ⁺ sign
heat to deliver × 3.412 ÷ Region V HSPF2The 3.412 factor converts kilowatt-hours into thousands of BTU.
WinterkWh of electricity for heatingAn electric baseboard needs as many as the heat to deliver.
SEER2+Field marked ⁺: AHRI certified and verified
12,000 BTU/h ÷ SEER2 × hours × days ÷ 1,000The method of Hydro-Québec’s air-conditioning calculator, with SEER2.
SummerkWh of electricity for coolingThe number of hours and days is a scenario the reader sets.

The higher the HSPF2 or SEER2, the less electricity it takes for the same heat or the same cooling. The price per kilowatt-hour, the hours of use and the full method are shown on every page that gives an amount.

The annotated record

NEEP record no. 392122, field by field

Here are the fields of the record as NEEP displayed it on November 9, 2026, with their original labels. Tap a field: the panel says what it measures, who stands behind it and how our pages use it.

+Field marked ⁺ on the record: AHRI certified and verified FManufacturer reported =Calculated ·No verification mention on the record

This sorting follows the note NEEP places at the bottom of the record: fields marked ⁺ are AHRI certified and verified information; so is rated capacity; input power is “manufacturer reported” and COP is calculated. Source of the ⁺ fields according to NEEP: ahridirectory.org.

Who certifies what

From the lab to our pages: the path of a number

AHRI and NEEP do different jobs. AHRI runs a certification program: units are tested by an independent laboratory under AHRI Standard 210/240. NEEP keeps a list of cold-climate heat pumps that carries those values and adds others.

1The manufacturer

It declares the performance of each outdoor and indoor unit combination.

2Independent testing

A third-party laboratory under contract to AHRI tests units to AHRI Standard 210/240.

3The AHRI certificate

The combination gets a reference number in the AHRI directory: here, 214888802.

4The NEEP record

NEEP receives the data through AHRI, carries the certificate number and publishes additional fields.

5Our pages

Each value we use carries its certificate number, its record number and the verification date.

What AHRI certifies

  • A voluntary program, run by AHRI, which checks that products perform according to their manufacturer’s published values.
  • Third-party testing: an ISO 17025-accredited laboratory under contract to AHRI. AHRI writes that certified products are tested every year.
  • The program’s ratings for a heat pump: cooling capacity, EER2, SEER2, high-temperature heating capacity (47 °F) and Region IV HSPF2.
  • A mark: only products that have passed this testing may display the AHRI Certified mark. AHRI also reports its data to Natural Resources Canada.
Source: AHRI, “Unitary Heat Pump and Air Conditioner Equipment (USE)” certification program sheet and AHRI Standard 210/240.

What NEEP adds

  • A list, with entry conditions: the cold-climate specification (Version 4.0, in effect since January 1, 2023) covers variable-capacity heat pumps. For a non-ducted unit: HSPF2 of at least 8.5, SEER2 of at least 15 and COP of at least 1.75 at 5 °F, at maximum capacity.
  • Extended data: capacity, input power and COP at minimum, rated and maximum, at 47, 17 and 5 °F, then at the lowest temperature cataloged by the manufacturer.
  • Region V HSPF2, which our cost estimates use. On the record, this field does not carry the ⁺ sign.
  • Its own reading note, at the bottom of each record, which says what is AHRI certified and verified, what the manufacturer reports and what is calculated.
Source: NEEP, “Cold Climate Air Source Heat Pump Specification (Version 4.0)”, the list’s page and record no. 392122.

Worth keeping in mind when reading our pages. When one of our pages cites an “AHRI” or “NEEP” value, it was read from these documents on the date shown. The ⁺ sign on the record marks what AHRI certifies and verifies; minimum and maximum capacities, power and COP come from the manufacturer or from a calculation, as NEEP itself writes.

Min, Rated, Max

Three columns for a unit that modulates

A variable-capacity heat pump does not deliver a single output: it slows down and speeds up. The record therefore gives three values at each test temperature. Pick a row of the table.

According to the NEEP specification, minimum, rated and maximum values are levels the unit holds continuously, without cycling or a time-limited “boost” mode. The rated value must match the AHRI certificate value; it may equal the maximum.

COP

COP can be recalculated from two cells of the record

COP says how much heat comes out of the unit for each unit of electricity going in. NEEP states that this number is calculated. You get it by dividing capacity by input power, once BTU/h are converted into kilowatts.

A COP on the record holds for one temperature and one operating level. It counts neither defrost nor the base pan heater: the NEEP specification excludes their power from the tables. For a whole season, read the seasonal ratings instead, SEER2 and HSPF2.

Its limits

What the record does not say

A NEEP record describes laboratory tests. For the rest, our pages go to the manufacturer’s documents, and say so.

Sound, dimensions, weight

None of this is on the record. Our pages take it from the manufacturer’s brochure and manuals, labelled “per the manufacturer”.

The trade name

The example’s record says “AIRSTAGE H-Series”; the name ORION XLTH is not on it. A unit is found by its model numbers or its AHRI number.

The operating limit

The last row of the table is the lowest temperature for which the manufacturer publishes data. The example’s record shows no shutoff temperature.

What happens between two rows

The table gives test points: 47, 17, 5 and −15 °F for this unit. The record’s chart joins these points with straight lines; our pages stick to the published points.

Units missing from the list

The list covers variable-capacity air-to-air heat pumps. Air-to-water and ground-source heat pumps are not on it, and NEEP notes that some eligible products remain to be listed since its April 1 change in data collection.

Your home

Tests are run at fixed temperatures: 21.1 °C indoors in heating, 26.7 °C in cooling. The pipe length, location and settings of a real installation are not part of them.

Frequently asked questions

The questions we get about these two documents

Are the NEEP record and the AHRI certificate the same document?

No. The AHRI certificate belongs to AHRI’s certification program and carries a reference number specific to one combination of units. The NEEP record is a page of NEEP’s cold-climate heat pump list; it carries that number and adds fields the certificate does not show, such as minimum and maximum capacities.

What does the ⁺ sign on the record mean?

NEEP explains it at the bottom of each record: the ⁺ sign marks AHRI certified and verified information, sourced from the AHRI directory. The same note states that rated capacity is AHRI certified and verified, that input power is manufacturer reported and that COP is calculated.

Why are rated and maximum capacity identical at −15 °C?

On the example’s record, both columns show 16,600 BTU/h at 5 °F, or −15 °C. The NEEP specification provides for it: when a unit is rated under the Appendix M1 H4 test, run at 5 °F, the value obtained is reported in both the rated and the maximum columns.

Why is there no rated value at −26.1 °C?

This row is the “lowest cataloged temperature”: the coldest one for which the manufacturer publishes performance data. The NEEP specification ties rated values to the AHRI certificate at 47 and 17 °F in heating and 95 °F in cooling. At −15 °F, the record therefore gives only the smallest and the largest capacity.

Is a heat pump missing from the NEEP list left out of your pages?

No. Listing is voluntary and the list has its own entry conditions. When a unit is not on it, our pages say so and name the source used instead. The absence of a record says nothing, by itself, about a unit’s performance.

Why do your pages quote 8.3 °C, −8.3 °C and −15 °C?

The tests are defined in degrees Fahrenheit: 47, 17 and 5 °F. Our pages convert these temperatures into degrees Celsius, which gives 8.3 °C, −8.3 °C and −15 °C. Likewise, 95 °F becomes 35 °C and −15 °F becomes −26.1 °C.

Can a record change?

Yes. The example’s record shows a creation date, March 31, 2026, and an update date, November 6, 2026. The NEEP specification also provides a field for an old AHRI reference number. This is why each of our pages carries a “Data verified on” line with its date.

Table

The example’s record, row by row

The values are those of NEEP record no. 392122 on November 9, 2026, converted to degrees Celsius. The third column reports what NEEP writes about each kind of field. Nothing is highlighted: a single heat pump appears in this table.

FieldORION XLTH 12,000 BTU, on its recordWho stands behind it, per NEEP
Identity
AHRI certificate · NEEP record214888802 · 392122Certificate number: field marked ⁺
Outdoor and indoor model numbersAOUH12KZAH1 · ASUH12KZASFields marked ⁺
RefrigerantR-32No ⁺ sign
Sold in the USA or CanadaSold InUSA and CanadaField marked ⁺
Seasonal ratings
SEER230.5Field marked ⁺: AHRI certified and verified
EER2At 35 °C outdoors16Field marked ⁺
HSPF2 Region IV12.7Field marked ⁺
HSPF2 Region V10.1No ⁺ sign on the record
Heating: capacity in BTU/h
Capacity at 8.3 °C: min. / rated / max.47 °F3,500 / 16,000 / 23,600Rated: AHRI certified and verified. Min. and max.: no mention.
Capacity at −8.3 °C: min. / rated / max.17 °F2,200 / 10,000 / 18,700Rated: AHRI certified and verified. Min. and max.: no mention.
Capacity at −15 °C: min. / rated / max.5 °F, H4 test1,950 / 16,600 / 16,600Rated: AHRI certified and verified, also reported in the Max column.
Capacity at −26.1 °C: min. and max.−15 °F, lowest cataloged temperature1,400 and 12,200Manufacturer data; no rated value at this temperature
Power and efficiency at 8.3 °C
Input power, in kWMin · Rated · Max0.20 · 1.01 · 2.25Manufacturer reported
COPMin · Rated · Max5.13 · 4.64 · 3.07Calculated
Other fields
ENERGY STAR cold climateENERGY STAR V6.1 Cold ClimateYesNo ⁺ sign; also in the ENERGY STAR directory
Capacity maintenance, −8.3 °C over 8.3 °CRated 17°F / Rated 47°F62%Ratio of two rated values of the table
Base pan heaterPan Heater · Input Power150 WNo ⁺ sign; power excluded from the tables
Record created and updatedMarch 31, 2026 · November 6, 2026Dates kept by NEEP

A cooling row completes this table: at 35 °C outdoors (95 °F), rated capacity is 12,000 BTU/h, which gives the unit its “size”.

The example unit is on AirGreen’s site.

Its product page gives the model numbers; its AHRI number leads to its NEEP record. For a project, talk it over with our team: bring the area to heat, your current heating and the planned outdoor location.

Sources and documents

Where each number comes from

NEEP, Cold Climate Air Source Heat Pump Product List, record no. 392122FUJITSU AIRSTAGE ORION XLTH 12,000 BTU, AOUH12KZAH1 / ASUH12KZAS, AHRI certificate 214888802: all fields, the note on the ⁺ sign and the April 1 notice · created March 31, 2026, updated November 6, 2026 · consulted November 9, 2026 NEEP, “Cold Climate Air Source Heat Pump Specification (Version 4.0)”Effective January 1, 2023: entry conditions, reporting fields, definitions of Minimum, Rated and Maximum, lowest cataloged temperature, H4 test at 5 °F, defrost and pan heater power excluded · consulted November 9, 2026 NEEP, “ccASHP Specification & Product List”Role of the list; heat pump data submitted through the AHRI submission process; Version 4.0 in effect · consulted November 9, 2026 AHRI, “Unitary Heat Pump and Air Conditioner Equipment (USE)” certification programVoluntary program, annual testing by an ISO 17025-accredited third-party laboratory, certified ratings, AHRI Certified mark, data reported to NRCan · consulted November 9, 2026 AHRI Standard 210/240-2024 (I-P), “Performance Rating of Unitary Air-conditioning and Air-source Heat Pump Equipment”Definitions of EER2 (3.2.18), HSPF2 (3.2.23) and SEER2 (3.2.53); HSPF2 varies by region · consulted November 9, 2026 U.S. Department of Energy, Appendix M1 to 10 CFR Part 430 (final rule, 82 FR 1426, January 5, 2017)Test conditions: 70 °F indoors in heating; tests at 47, 35 and 17 °F; optional H4 test at 5 °F · consulted November 9, 2026 ENERGY STAR, certified heat pump directory, AHRI reference 214888802Cold climate: yes; markets: United States and Canada; certified April 17, 2026 · consulted November 9, 2026