GREE FREEMATCH R32 18,000 and SAMSUNG FJM Premium 20,000, 2 zones

Home / Comparisons / 2-zone multi-zone, 18,000 and 20,000 BTU

Comparison · Multi-zone · 2 zones · 18,000 and 20,000 BTU

GREE FREEMATCH R32 and SAMSUNG FJM Premium, two 2-zone systems that are not the same size

These two R-32 multi-zone systems serve two rooms, but they are not the same size: the FREEMATCH R32 certificate shows 18,000 BTU/h in cooling, the FJM Premium certificate, 21,000 BTU/h. The page says so up front, then compares what can be compared: the efficiencies, the capacity ranges and the extreme-cold figures, each at its own temperature.

Certified at 35 °C: 18,000 and 21,000 BTU/hSEER2 21 and 23Coldest points: −30 and −25 °C

Certified cooling capacity, BTU/h, on one scale.

GREE FREEMATCH R32, 2 zones (AirGreen image)
GREE

FREEMATCH R32 · 2 zones, 18,000 BTU

GWHD(18)ND6MO + non-ducted indoor units · AHRI 214931586

See the product page
SAMSUNG FJM Premium, 2 zones (AirGreen image)
SAMSUNG

FJM Premium · 2 zones, 20,000 BTU

AJ020DXS3CG + non-ducted indoor units · AHRI 216372795

See the product page
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 18,000 BTU/h zone in Montréal, at Hydro-Québec’s Rate D, taxes included. Both heat pumps are calculated in exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference point. Here, the zone is both rooms together: 18,000 BTU/h, the certified capacity of the FREEMATCH R32 at 35 °C. The FJM Premium, certified at 21,000 BTU/h, is calculated for this same zone, with its own efficiencies.

How this amount is calculated
  1. Heat to deliver over the winter. A zone whose heat loss reaches 18,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours per day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump as for the baseboards: this simplification does not account for recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 18,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario you can set above, from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a ceiling, since a variable-speed unit slows down once the room is at temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. Network access charges, the same with or without a heat pump, are not counted.

AirGreen method v1.1, November 9, 2026. An estimate is used to compare units under the same conditions. The actual bill depends on the house, the insulation, the settings and the use; this amount is not a promise.

Two sizes, two certificates

What each certificate shows, condition by condition

Each dial shows one system: the outer ring gives its certified capacity at the chosen condition, the inner ring its SEER2. Both dials use the same scale, so that the difference in size is visible.

up to the rated capacity from rated to maximum minimum capacityScale: 0 to 32,000 BTU/h; SEER2 from 0 to 25

AHRI certificates 214931586 and 216372795, published by NEEP, non-ducted indoor units. At −8.3 °C and −15 °C, the certified rated capacity of the FREEMATCH R32 equals its maximum; at −15 °C, the same is true of the FJM Premium.

Why the cost is calculated for 18,000 BTU/h in both cases. The operating cost compares the two systems against the same need: an 18,000 BTU/h zone, the certified capacity of the FREEMATCH R32, which the FJM Premium also covers. Each is calculated with its own certified efficiencies (SEER2 and HSPF2 Region V). Calculating the FJM Premium on 21,000 BTU/h would mean having it heat and cool a larger zone: the amounts could no longer be compared.
“20,000” on the label, 21,000 on the certificate. The model number AJ020DXS3CG suggests 20,000 BTU/h. The AHRI certificate shows a rated cooling capacity of 21,000 BTU/h. SAMSUNG’s combination table gives 18,000 BTU/h with two 9,000 heads, and 21,000 BTU/h with 9 + 12 or 12 + 12.
Extreme cold

Below −15 °C: every published number, at its exact temperature

NEEP certifies both systems at −15 °C, at the same temperature. Lower, each has a single certified point: −25 °C for the FJM Premium, −30 °C for the FREEMATCH R32. Nothing is calculated between two points.

What each manufacturer publishes below −15 °C. GREE: the NEEP point at −30 °C (10,200 BTU/h, COP 1.51), a stated heating range of −30 to 24 °C and a 72 W outdoor unit base pan heater. Neither the brochure, the submittal sheet nor the service manual of the FREEMATCH R32 gives a capacity table below −15 °C. SAMSUNG: the NEEP point at −25 °C (18,000 BTU/h, COP 1.61), a heating range of −25 to 24 °C, and a capacity table for the 9 + 9 combination that SAMSUNG presents as trend data; its two values are in the table, next to the certified points. The installation manual adds that, below −5 °C, start-up can take up to 60 minutes to protect the compressor.
Documented features

What each manufacturer writes

GREE FREEMATCH R32 brochure (X610068B), GREE Canada submittal sheet and service manual; SAMSUNG submittals for the AJ020DXS3CG and the AJ009DNADCG wall-mounted unit, FJM R32 installation manual. Each line quotes what the manufacturer writes. For the heads, features change with the model chosen.

Extreme cold

FREEMATCH R32: stated heating from −30 to 24 °C; outdoor unit base pan heater (72 W); “intelligent” defrost.

FJM Premium: heating from −25 to 24 °C; base pan heater as standard.

Cooling in cold weather

FREEMATCH R32: stated cooling range of −30 to 48 °C.

FJM Premium: from −10 to 46 °C.

Choice of heads

FREEMATCH R32: two connections; “7 indoor options”.

FJM Premium: three connections on the outdoor unit; the combination table lists 9 + 9, 9 + 12 and 12 + 12, among others.

Power supply

FREEMATCH R32: indoor units powered from the outdoor unit; automatic voltage adaptation; low-voltage start-up.

FJM Premium: 208 to 230 V, single phase; soft start; maximum current setting.

Refrigerant leak detection

FREEMATCH R32: A2L leak sensor included.

FJM Premium: A2L leak detection built into the AJ009DNADCG wall-mounted unit; leak alarm output on the outdoor unit, with an optional module.

Modes and comfort

FREEMATCH R32: quiet operation on the outdoor unit side; comfort modes depend on the head.

FJM Premium: WindFree, Comfort Humidity Control, Good’sleep, Quiet, AI Auto (AJ009DNADCG wall-mounted unit).

Wi-Fi and controls

FREEMATCH R32: depends on the head chosen; the FREEMATCH brochure does not specify it.

FJM Premium: Built-in Wi-Fi (SmartThings) on the AJ009DNADCG wall-mounted unit; energy monitoring.

Restart after a power failure

FREEMATCH R32: automatic restart (GREE Canada website).

FJM Premium: automatic restart.

Maintenance and protection

FREEMATCH R32: self-diagnosis; coil protected against corrosion by an acrylic resin (GREE Canada website).

FJM Premium: Auto Clean; washable filter accessible from the top; filter cleaning reminder.

Sound

The sound of each one, according to its manufacturer

The sound of a head depends on the model chosen. The figures compare two 9,000 BTU/h wall-mounted units: the GREE CHARMO, published in seven levels, and the SAMSUNG AJ009DNADCG, for which the manufacturer publishes two values, the lowest and the highest.

dB(A)

How to read these figures. dB(A) measures a noise level as the ear perceives it: the lower the figure, the quieter the unit. Each dot is a fan speed published by the manufacturer, from the slowest to the fastest.

Why this is not a ranking. SAMSUNG measures in an anechoic chamber, microphone at 1 m. GREE publishes neither the distance nor the measurement conditions. A gap of a few dB(A) can come from the method as much as from the unit.

Indoor unit, in the room

Cooling, published speeds, 9,000 BTU/h wall-mounted head

Outdoor unit, outside

Published values for each outdoor unit

Measurements taken by each manufacturer using its own method: read them separately, not as a ranking.

Sources: GREE CHARMO R32 service manual (GWH09ATCXB-D6DNA1C, sound pressure) and GREE Multi R32 service manual (GWHD(18)ND6MO: sound pressure 54 dB(A), sound power 64 dB(A)); SAMSUNG technical data books, FJM Standard, version 1.2 (AJ009DNADCG, p. 17 and 95) and FJM Premium, version 1.1 (AJ020DXS3CG, p. 76: sound pressure at 1 m in front of the unit).

Installation

Outside, on the wall, in the piping

Outdoor units, outlines to scale

32 3/8 × 21 11/16 in
depth 13 7/8 in · 78.3 lb

37 × 47 5/8 in
depth 13 in · 191.8 lb

Diagram: published width and height, at the same scale. The FJM Premium outdoor unit has two stacked fans; it is 25 15/16 in taller and weighs 113.5 lb more.

Indoor units to scale

GREE headCHARMO 9,000: 32 7/8 × 10 53/64 × 7 7/8 in
GREE wall-mounted head from the AirGreen product page, to scale
32.88 in
AJ009DNADCG32 5/16 × 11 3/4 × 8 7/16 in
SAMSUNG indoor unit from the AirGreen product page, to scale
32.31 in

Widths to scale. Photos: the wall-mounted heads from the AirGreen product pages. Dimensions of the 9,000 BTU/h CHARMO (GREE Canada service manual) and of the AJ009DNADCG (SAMSUNG submittal).

Two rooms far apart: the total piping length

60 ft

Dark: length covered by the factory charge. Light: length allowed with added refrigerant. GREE brochure X610068B and GREE Canada submittal sheet; SAMSUNG submittal for the AJ020DXS3CG and FJM R32 installation manual (p. 23 and 29). Each line also has its own limit: 65.6 ft to the last indoor unit for the FREEMATCH R32 (equivalent length), 10 to 82 ft per room for the FJM Premium.

Installation FREEMATCH R32 FJM Premium
Maximum piping lengthTotal of the lines 131 ft 230 ft
Piping length per indoor unit 65.6 ftEquivalent length to the last indoor unit (submittal sheet and service manual). 82 ftMinimum of 10 ft per line.
Precharged length 33 ftThen 0.2 oz per foot. 230 ftFactory charge of 109.3 oz for the whole permitted length; the installation manual prohibits adding any.
Maximum height difference 49 ftSame value between two indoor units. 49 ft25 ft between two indoor units.
Liquid – gas diametersPer indoor unit 1/4 – 3/8 in 1/4 – 3/8 inThree connections; 3/8 to 1/2 in adapter supplied for the gas line.
Outdoor unit W × H × D, weight 32 3/8 × 21 11/16 × 13 7/8 in, 78.3 lbThe GREE Canada submittal sheet shows 75 lb. 37 × 47 5/8 × 13 in, 191.8 lb
Indoor unit, weight9,000 BTU/h wall-mounted head 19.8 lbCHARMO GWH09ATCXB-D6DNA1C. 19.6 lbAJ009DNADCG.
Electrical protectionPer the manufacturer MOCP 20 A (MCA 14.5 A)Brochure X610068B. The GREE Canada submittal sheet shows an MCA of 18.5 A: to be confirmed at the quote. MOP 40 A (MCA 35.9 A)
Outdoor unit base pan heater Included, 72 W Included“Base pan heater: standard”, submittal.
Clearances around the outdoor unit 6 in from the wall; 6 to 24 in from obstacles depending on the sideFigure in the GREE Canada submittal sheet. Figure in the FJM R32 installation manual, p. 14The SAMSUNG submittal does not reproduce them.
Stated heating / cooling range −30 to 24 °C / −30 to 48 °C −25 to 24 °C / −10 to 46 °C
Questions

What we are asked about these two systems

Why compare an 18,000 and a 20,000 BTU system?

Because these are the two 2-zone systems we are asked to put side by side. They are not the same size, and the page says so from the title. The efficiencies (SEER2, HSPF2) compare directly; the capacities are read knowing that one is certified at 18,000 BTU/h and the other at 21,000 BTU/h.

The SAMSUNG is called “20,000”: why 21,000 on the certificate?

The AHRI certificate of the AJ020DXS3CG, published by NEEP, shows a rated cooling capacity of 21,000 BTU/h at 35 °C. SAMSUNG’s combination table gives 18,000 BTU/h with two 9,000 heads and 21,000 BTU/h with 9 + 12 or 12 + 12.

Why is the cost calculated for 18,000 BTU/h in both cases?

To compare the two systems against the same need. The 18,000 BTU/h zone is the certified capacity of the FREEMATCH R32, which the FJM Premium also covers. Each is calculated with its own certified efficiencies.

What happens below −25 °C or below −30 °C?

SAMSUNG publishes a heating range down to −25 °C for the FJM Premium, GREE down to −30 °C for the FREEMATCH R32. Neither gives a capacity figure beyond its last certified point: 18,000 BTU/h at −25 °C for the former, 10,200 BTU/h at −30 °C for the latter.

Does refrigerant need to be added for long lines?

For the FREEMATCH R32, GREE specifies 0.2 oz per foot beyond 33 ft of piping, up to 131 ft in total. For the FJM Premium, SAMSUNG’s installation manual says not to add any, whatever the installation, up to the maximum of 230 ft.

Does the SAMSUNG outdoor unit need more space?

According to the submittals: 47 5/8 in high and 191.8 lb for the AJ020DXS3CG, against 21 11/16 in and 78.3 lb for the GWHD(18)ND6MO. The published electrical protection is 40 A for the former and 20 A for the latter. The location and the electrical panel are checked during the visit.

Which one is right for me?

This page does not rank the units. It shows the certified values and what each manufacturer publishes, with the sources. The right choice depends on the real need of your two rooms, the outdoor location, your electrical panel and your current heating.

Are these systems eligible for financial assistance?

Eligibility is checked on the official list of Hydro-Québec’s LogisVert program at the time of the quote, for the exact combination installed. This page gives no amounts, and programs can change.

Certified record

All AHRI and NEEP values

Certified value FREEMATCH R32 FJM Premium
Cooling
Rated capacity at 35 °C 18,000 BTU/h 21,000 BTU/h
35 °C: min. / rated / max.BTU/h 7,000 / 18,000 / 19,600 9,500 / 21,000 / 30,000
SEER2 21.0 23.0
EER2 12.0Brochure X610068B shows 12.5; the certificate prevails. 15.0
Heating, same conditions
HSPF2 Region IV 10.0 10.5
HSPF2 Region V 8.0 7.1
8.3 °C: min. / rated / max.BTU/h 7,000 / 18,000 / 18,100 7,600 / 22,000 / 32,000
8.3 °C: COP min. / rated / max. 3.95 / 3.91 / 3.21 4.95 / 4.64 / 3.91
−8.3 °C: min. / rated / max.BTU/h 7,200 / 17,600 / 17,600 10,500 / 13,200 / 22,000
−8.3 °C: COP min. / rated / max. 3.25 / 2.36 / 2.36 2.96 / 2.95 / 2.22
−15 °C: min. / rated / max.BTU/h 7,200 / 13,800 / 13,800 10,500 / 22,000 / 22,000
−15 °C: COP min. / rated / max. 2.45 / 2.00 / 2.00 2.05 / 1.95 / 1.95
Coldest point of each certificate (different temperatures)
Test temperature −30 °C (−22 °F) −25 °C (−13 °F)
Capacity min. / max.BTU/h 7,000 / 10,200 10,000 / 18,000
COP min. / max. 1.55 / 1.51 1.65 / 1.61
Certification
ENERGY STAR / cold climate (NEEP) Yes / Yes Yes / Yes
ENERGY STAR directory, markets listed United States, Canada United States, Canada
AHRI certificate · NEEP record 214931586 · 392112 216372795 · 417116
RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class R-32 · GWP 675 · A2L R-32 · GWP 675 · A2L

higher marks the higher value of the same measure, under the same conditions. It is not a recommendation. Capacities are not highlighted: the two systems are not the same size, and the order of the COPs changes depending on the point read.

Both are on the AirGreen website.

To choose the right size, talk to our team: bring the dimensions of both rooms, the planned outdoor location, the capacity of your electrical panel and your current heating.

Sources and documents

Where each figure comes from

NEEP, record 392112 (GREE, GWHD(18)ND6MO)AHRI 214931586, non-ducted units · consulted November 9, 2026 NEEP, record 417116 (SAMSUNG, AJ020DXS3CG)AHRI 216372795, non-ducted units · consulted November 9, 2026
ENERGY STAR directory (data.energystar.gov, dataset 83eb-xbyy)Cold climate: yes for both; markets United States and Canada · consulted November 9, 2026
GREE, FREEMATCH R32 brochure (EN)Document X610068B · capacities, piping, electrical, ranges, features GREE Canada, GWHD(18)ND6MO submittal sheetUndated · combinations, clearances, base pan heater · consulted November 9, 2026 GREE, Multi R32 service manual, outdoor unitsPages 2 and 3: GWHD(18)ND6MO data, ranges, sound, piping · consulted November 9, 2026 GREE, CHARMO Inverter R32 service manualPage 9: GWH09ATCXB-D6DNA1C, sound pressure, dimensions, weight · consulted November 9, 2026
SAMSUNG, AJ020DXS3CG submittalVersion 02142025A · dimensions, weight, electrical, piping, ranges, base pan heater
SAMSUNG, FJM R32 installation manualDB68-13175A-00 · p. 23 (lengths), p. 25 (start-up below −5 °C), p. 29 (no added refrigerant)
SAMSUNG, Free Joint Multi Premium (R32) technical data bookVersion 1.1 · p. 29 (combination table), p. 76 (outdoor unit sound); capacity table, version 1.1, p. 10 (9 + 9 combination, trend data)
SAMSUNG, AJ009DNADCG submittal and technical data bookFJM Standard, version 1.2, p. 17 and 95 · sound, dimensions, weight, features
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · estimated operating cost Natural Resources Canada, HOT2000 climate mapMontréal Intl station: 4,167 degree-days (18 °C), −23.1 °C design · consulted November 9, 2026