HSPF2 Region IV and Region V: why two numbers

Home / Comparisons / Guides: reading the records

Guide · Reading the records · Heating

HSPF2 Region IV and Region V: why two numbers

The same heat pump carries two heating ratings. They do not contradict each other: each one assumes a different winter. This guide shows what the standard puts in each region, which one resembles Montréal’s winter, and which one our cost estimates use.

Region IV · design at −15 °CRegion V · design at −23.3 °CMontréal · −23.1 °C
FUJITSU AIRSTAGE ORION XLTH 12,000 BTU (AirGreen image)
ExampleFUJITSU AIRSTAGE

ORION XLTH · 12,000 BTU

ASUH12KZAS / AOUH12KZAH1 · AHRI 214888802

See the product page
The map of regions

Six regions, six reference winters

HSPF2 is calculated for a reference winter. The U.S. Department of Energy (DOE) test procedure defines six, numbered I to VI. Tap a region: its design temperature, its heating hours and, for the two regions the NEEP record publishes, the HSPF2 of the example unit.

A diagram, not a geographic map: the regions are stacked from the coldest, at the top, to the mildest, at the bottom. Region VI is the Pacific Coast region. Montréal is placed by its design temperature.

Two winters

Region V spends more hours in the cold

For each region, the standard splits the heating season into 5 °F bins and gives each bin’s share of hours. The two distributions are overlaid here. Tap a bin to compare.

Region IVRegion VThe region’s design temperature

Why more cold gives a lower rating

A heat pump’s efficiency drops as the outdoor temperature drops. The NEEP record of the example unit shows it at maximum capacity, from 8.3 °C to −26.1 °C. A reference winter with more cold hours therefore gives a lower average, and the calculation adds electric backup when the heat pump is no longer enough.

COP at 8.3 °C3.07
COP at −8.3 °C2.44
COP at −15 °C2.16
COP at −26.1 °C1.81

FUJITSU AIRSTAGE ORION XLTH 12,000 BTU, NEEP record no. 392122, “Max” column, read on November 10, 2026. COP there is calculated by NEEP from capacity and input power. The hour shares come from Table 20 of Appendix M1 as the DOE published it on January 5, 2017; the current version refers to the corresponding table of AHRI Standard 210/240-2024. The shares do not add up to 100%: the table enters zero for the two mildest bins.

And Montréal

Which of the two winters resembles Montréal’s

The six regions describe the climate of the United States: Montréal is not in them. Three reference points still let us place the city, and all three point to Region V.

The design temperature

Montréal’s is −23.1 °C according to Natural Resources Canada’s HOT2000 climate data (Montréal Intl station). Region V’s is −10 °F, or −23.3 °C; Region IV’s is 5 °F, or −15 °C.

Canadian regulations

In Canada, the minimum heating standard for split-system heat pumps is expressed in Region V: an HSPF2 of at least 6.0. In the United States, the same category must reach 7.5 in Region IV. Natural Resources Canada explains that it uses Region V to account for Canadian climate conditions.

The neighbours to the south

In its 2017 rule, the DOE places southern Vermont, for example, in Region V, and New York and New Jersey in Region IV. Vermont borders Québec, and the standard has no region colder than V.

What this does not mean. Region V remains a reference winter, the same for all units. It is not Montréal’s weather record, nor Saguenay’s or Gatineau’s. It is used to compare heat pumps under conditions close to ours, not to predict a bill.

Our calculation

Our cost estimates use Region V

On all our comparison pages, a heat pump’s heating electricity is estimated with its Region V HSPF2, never with its Region IV value. Here is why, and what this choice changes for the example unit.

  1. It is the reference winter closest to ours. Our method uses Montréal’s design temperature, −23.1 °C. Region V’s is −23.3 °C; Region IV’s is −15 °C.
  2. It is the region of Canadian regulations. The federal minimum standard is expressed in Region V HSPF2.
  3. It is the same rule for every unit. Each heat pump, of each brand, is calculated with the same region and the same formula: the amounts can be compared from one page to another.

One heating winter, example unit

How this amount is calculated

AirGreen method v1.1 of November 9, 2026, the same as on our comparison pages. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, heated around the clock: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat (degree-days and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station). Heat pump electricity: heat × 3.412 ÷ HSPF2. Electric baseboards: 1 kWh of electricity for 1 kWh of heat. Price: Hydro-Québec Rate D in effect April 1, 2026, average price of 9.104¢ per kWh, GST and QST included; network access charges are not counted. An estimate is used to compare units under the same conditions. The actual bill depends on the house, the insulation, the settings and the use; this amount is not a promise.

On the record

How the NEEP record names the two numbers

The record shows the two values one under the other: “HSPF2 (Region IV)” and “HSPF2 (Region V)”. A third line, “HSPF (Region IV)”, without the “2”, keeps the place of the former rating: do not confuse it with the other two.

On the record read on November 10, 2026, the + mark accompanies the Region IV value, the one used for U.S. compliance. The Region V value is shown without that mark; the record does not say why. Both lines come from the same record and the same AHRI certificate number.

For the rest of the record, field by field: How to read a NEEP record and an AHRI certificate. For the three seasonal ratings: SEER2, EER2, HSPF2.

Frequently asked questions

What we are asked about the two regions

An HSPF2 with no region stated: which one is it?

You cannot know without checking. AHRI Standard 210/240 states that HSPF2 varies by region and that Region IV is used for compliance in the United States; Canadian regulations are expressed in Region V. The unit’s NEEP record shows both values: compare the advertised number with the two lines.

Can one region be converted into the other?

It is not necessary: the record gives both. For the example unit, 12.7 ÷ 10.1 gives a ratio of 1.26. The two minimum standards, 7.5 in Region IV in the United States and 6.0 in Region V in Canada, give 1.25. These are observations, not a rule: each unit is calculated separately for each region.

Is Montréal officially in Region V?

The regions of the test procedure describe the climate of the United States; they do not classify Canadian cities. What is official is that Canadian federal regulations express their minimum standard in Region V HSPF2, and that Montréal’s design temperature published by Natural Resources Canada, −23.1 °C, is 0.2 °C from Region V’s.

Does Region V HSPF2 say what the unit delivers at −25 °C?

No. It is an average over the whole season, where very cold hours are rare: in Region V, the bins below −17.8 °C account for 3.6% of the hours. For a specific temperature, read the capacity points on the NEEP record. For the example unit, the coldest published point is at −26.1 °C: 12,200 BTU/h at maximum, with a COP of 1.81.

Do both regions count electric backup?

Yes. In both cases, when the heat pump does not cover a bin’s heating need, the calculation adds electric resistance heat to fill the gap, and that electricity goes into the rating. Region V has more cold hours, hence more occasions to use it.

And Regions I, II, III and VI?

These are milder winters: their design temperatures range from 2.8 °C to −8.3 °C. The NEEP record publishes HSPF2 only for Regions IV and V, and our pages use only those two values.

Table

Region IV and Region V, value by value

The region values come from Table 20 of DOE Appendix M1 (rule of January 5, 2017). The example’s values come from NEEP record no. 392122, read on November 10, 2026.

ValueRegion IVRegion V
The reference winter
Outdoor design temperature−15 °C (5 °F)−23.3 °C (−10 °F)
Heating load hours1,701 h2,202 h
Coldest bin countedRepresentative temperature−22.2 °C (−8 °F)−30.6 °C (−23 °F)
Share of hours below −6.7 °C8.4%20.5%
The calculation
Threshold where the heating need starts12.8 °C (55 °F)12.8 °C (55 °F)
Slope factor, variable speed1.071.08
Who uses it
Minimum standard, split-system heat pumpsRequired HSPF2United States: 7.5Canada: 6.0
AirGreen cost estimatesNot usedYes
The example: FUJITSU AIRSTAGE ORION XLTH 12,000 BTU
HSPF2 on the NEEP record12.710.1
Estimated heating winterAirGreen method v1.1, 12,000 BTU/h zone

The minimum standards are those Natural Resources Canada gives for split-system heat pumps (technical bulletin of May 2021 and Regulations page modified October 28, 2025). They can change: only the official texts are authoritative.

The example unit is on AirGreen’s site.

Its product page gives the model numbers; its AHRI number leads to its NEEP record. For a project, talk it over with our team: bring the area to heat, your current heating and the planned outdoor location.

Sources and documents

Where each number comes from

U.S. Department of Energy, “Test Procedures for Central Air Conditioners and Heat Pumps”, final rule, 82 FR 1426, January 5, 2017Appendix M1, section 4.2 and Table 20 (six regions: heating load hours, outdoor design temperature, slope factors, fractional bin hours); definition of “design heating requirement” (“six generalized U.S. climatic regions”); preamble, section III, footnote 18 (southern Vermont in Region V, New York and New Jersey in Region IV) · consulted November 9, 2026 U.S. Code of Federal Regulations, 10 CFR Part 430, Subpart B, Appendix M1 (current version)Reference to AHRI Standard 210/240-2024 for the HSPF2 calculation · consulted November 10, 2026 AHRI Standard 210/240-2024 (I-P), “Performance Rating of Unitary Air-conditioning and Air-source Heat Pump Equipment”Definition 3.2.23: HSPF2 varies by region; Region IV is used for U.S. compliance · consulted November 9, 2026 Natural Resources Canada, Energy Efficiency Regulations, page “Thermopompes centraux bibloc” (in French)Test standard: 10 C.F.R. Appendix M1; split-system heat pumps other than space-constrained or small-duct high-velocity: HSPF2 (Region V) of at least 6.0 · page modified October 28, 2025 · consulted November 10, 2026 Natural Resources Canada, “Les climatiseurs centraux et les thermopompes”, technical bulletin on amending the standards, May 2021 (in French)Table 1: split-system heat pumps, HSPF2 of 7.5 (Region 4) in the United States and 6.0 (Region 5) in Canada; Canadian compliance based on Region 5, to account for Canadian climate conditions · page modified January 13, 2025 · consulted November 10, 2026 NEEP, record no. 392122: FUJITSU AIRSTAGE ORION XLTH 12,000 BTUAOUH12KZAH1 / ASUH12KZAS, AHRI certificate 214888802: HSPF2 (Region IV) 12.7; HSPF2 (Region V) 10.1; COP at maximum capacity: 3.07 at 47 °F, 2.44 at 17 °F, 2.16 at 5 °F and 1.81 at −15 °F (12,200 BTU/h) · consulted November 10, 2026
Cost estimate: AirGreen method v1.1Natural Resources Canada, HOT2000 climate data, Montréal Intl station (4,167 degree-days, −23.1 °C); Hydro-Québec, Electricity Rates, Rate D in effect April 1, 2026 · method of November 9, 2026, the same on all our pages