KINGHOME CHARMO R32 and KINGHOME CLIVIA R32, figure by figure
Two wall series from the same brand, in the same 12,000 BTU size. Here is what their AHRI certificates and KINGHOME's sheets publish for each one: efficiency, heating in deep cold, sound, piping and estimated electricity cost in Montréal.
KINGHOME
CHARMO R32
KW12HQ19CDI / KW12HQ19CDO · AHRI 217956851Also sold as GREE CHARMO / VITA R32 (AHRI 215402236) and GREE LIVO R32 (AHRI 214779350): same certified AHRI and NEEP values.
See the product page
KINGHOME
CLIVIA R32
KW12XQ25S1DI / KW12XQ25S1DO · AHRI 217933620Same NEEP “Clivia” series as the GREE CLIVIA R32 (AHRI 216032436), with one small difference: rated COP at −8.3 °C of 2.88 here, 2.11 on the GREE certificate.
See the product pageWhat the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec Rate D, taxes included. Both heat pumps are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the point of reference.
Here, the gap comes from two certificate figures: HSPF2 Region V of 7.3 and 8.0 for winter, SEER2 of 19 and 24.5 for summer. The rest of the calculation is identical for both.
How this amount is calculated
- Heat needed over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (18 °C base) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (the “Heating” slider), the heat is reduced in the same proportion, for the heat pump and the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air conditioning calculator, with the seasonal SEER2 efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one offered by Hydro-Québec’s calculators. GST and QST included. The system access charge, the same with or without a heat pump, is not counted.
AirGreen method v1.1, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the insulation, the settings and how it is used; this amount is not a promise.
The two records, brought together line by line
On the left, the CHARMO's record; on the right, the CLIVIA's. Bring them together: the lines where KINGHOME and the AHRI certificate give the same value merge into one; the ones that differ stay apart, with both figures.
Sources: AHRI certificates 217956851 and 217933620 read on NEEP on November 10, 2026; ENERGY STAR directory; KINGHOME spec sheets for the CHARMO R32 and the CLIVIA R32 (undated). When a KINGHOME sheet and the certificate differ, the page follows the certificate.
Below −15 °C: what each series publishes, point by point
Both certificates give a capacity at −15 °C. Further down, they do not stop at the same place: the CLIVIA is certified down to −30 °C, the CHARMO down to −25 °C. For the CHARMO, a GREE table for the same NEEP series adds two points outside the certificate. No figure is calculated between two points.
What KINGHOME writes for each series
Each card covers a function named in the KINGHOME sheet of one series or the other. When a sheet does not name it, that is stated as such: this silence does not mean the function is absent.
Both sheets name Wi-Fi and app control.
Same printed dehumidification rate for both: 1.4 L/h.
The CHARMO sheet describes a cycle using condensation, freezing and defrosting of the coil.
The unit resumes its settings when power returns.
Vertical and horizontal air direction, named in both sheets.
Named by KINGHOME for both series, with no treatment details.
Both NEEP records list 72 W, on below 1 °C (33.8 °F) or during defrost. The KINGHOME sheets do not name it.
The CLIVIA sheet gives an airflow of 212 to 400 CFM, without a number of speeds.
Named in the icon row of the CHARMO sheet.
A mode that keeps the room around 8 °C, for example in an unoccupied cottage.
The CLIVIA sheet mentions a fresh-air module offered as an option, without airflow figures.
Heating operating ranges printed by KINGHOME (outdoor).
What KINGHOME publishes on sound level
For the indoor unit, each sheet gives only the lowest and the highest value, without the detail per speed. For the outdoor unit, both sheets give 52 dB(A).
Indoor unit
Range printed in each series' KINGHOME sheet
How to read these figures. The A-weighted decibel follows the ear's sensitivity; the lower the figure, the quieter the unit. Each dot is a value printed by KINGHOME: the smallest matches the lowest fan speed, the largest the highest.
Why this is not a ranking. The sheets state neither the measuring distance nor the method. Two ranges from the same brand can be read side by side, but they say nothing about the sound in a particular room.
Measurements taken by each manufacturer with its own method, which the sheets do not detail; for indication only.
Same line lengths, not the same gas line
Both series accept 10 to 66 ft of line set, with 25 ft already charged and 40 ft of height difference. The difference is elsewhere: the gas line goes from 3/8 in on the CHARMO to 1/2 in on the CLIVIA, and the CLIVIA's outdoor unit is wider and heavier.
The indoor units, at the same scale


Widths to scale from the dimensions in the KINGHOME sheets (width × height × depth). KINGHOME photos, cut out.
Is your wall wide enough?


The calculation compares the unit width with the wall width. The side clearances required by the installation manual come on top and are not counted here.
CHARMO R32, outdoor unit
CLIVIA R32, outdoor unit
Diagram to scale, front view, from the width × height dimensions in the KINGHOME sheets. Both sheets show the same outdoor unit photo; the diagram avoids suggesting that both cabinets are the same size.
| Line | CHARMO R32 | CLIVIA R32 |
|---|---|---|
| Line set | ||
| Maximum piping length | 66 ftminimum 10 ft · KINGHOME sheet | 66 ftminimum 10 ft · KINGHOME sheet |
| Pre-charged length | 25 ft0.2 oz/ft added beyond | 25 ft0.2 oz/ft added beyond |
| Maximum height difference | 40 ft | 40 ft |
| Liquid – gas diameters | 1/4 – 3/8 in | 1/4 – 1/2 in |
| Factory R-32 refrigerant charge | 17.6 oz | 28.2 oz |
| Dimensions and weight | ||
| Outdoor unit W × H × D, weight | 28 13/16 × 21 7/8 × 12 63/64 in, 56.2 lb | 31 37/64 × 21 27/32 × 13 25/32 in, 67.3 lb |
| Indoor unit, weight | 19.8 lb32 7/8 × 10 53/64 × 7 7/8 in | 20.9 lb32 61/64 × 11 17/32 × 7 7/8 in |
| Clearances around the outdoor unit | Not published by the manufacturer in the spec sheet; see the installation manual. | Not published by the manufacturer in the spec sheet; see the installation manual. |
| Electrical and operation | ||
| Electrical protection | 208-230 V, MCA 12 A, MOCP 15 A | 208-230 V, MCA 10 A, MOCP 15 A |
| Dehumidification | 1.4 L/h | 1.4 L/h |
| Indoor fan airflow | 182 to 424 CFM | 212 to 400 CFM |
| Advertised heating / cooling range | −25 to 24 °C / −18 to 48 °C | −30 to 30 °C / −29 to 50 °C |
Source: KINGHOME spec sheets for the CHARMO R32 (KW12HQ19CDI / KW12HQ19CDO) and the CLIVIA R32 (KW12XQ25S1DI / KW12XQ25S1DO), undated, distributed by AirGreen.
What we are asked about these two series
Where is the clearest difference in the figures?
In seasonal efficiency and in the cold. SEER2 19 for the CHARMO and 24.5 for the CLIVIA; HSPF2 Region V 7.3 and 8.0. At −15 °C, the certified maximum capacity is 9,100 and 11,000 BTU/h. The coldest test point is −25 °C for the CHARMO and −30 °C for the CLIVIA. These are values from each unit's AHRI certificate, read on NEEP.
Are both listed as cold-climate heat pumps?
Yes. The ENERGY STAR directory lists both combinations with the cold-climate mention: the CHARMO since May 28, 2026 (Canadian market), the CLIVIA since August 12, 2026 (United States and Canada). For the CHARMO, NEEP's ENERGY STAR field and the KINGHOME sheet say “no”; the page follows the directory and points this out.
What is published for the CHARMO below −25 °C?
The certificate stops at −25 °C, with 6,500 BTU/h. The KINGHOME sheet advertises a heating range down to −25 °C. A GREE table for the LIVO R32, which has the same certified values, gives 8,030 BTU/h at −26.1 °C as maximum output, outside AHRI conditions. Colder than that, none of the documents consulted gives a figure.
The KINGHOME sheet for the CLIVIA shows 7,700 BTU/h at −8.3 °C. Why does the page show 12,000?
Because AHRI certificate 217933620 gives 12,000 BTU/h (rated and maximum) at 17 °F (−8.3 °C). The same sheet prints 11,000 BTU/h at −15 °C, more than the 7,700 at −8.3 °C; this is probably a printing error. When a sheet and the certificate differ, the page follows the certificate.
Is the line set the same for both?
The lengths, yes: 10 to 66 ft, 25 ft pre-charged, 40 ft of height difference. The diameters, no: 1/4 – 3/8 in for the CHARMO, 1/4 – 1/2 in for the CLIVIA. The factory charge also goes from 17.6 to 28.2 oz of R-32. If an existing line set is to be reused, its diameter matters.
Are these series sold under other names?
The CHARMO has the same certified AHRI and NEEP values as the GREE CHARMO / VITA R32 and the GREE LIVO R32. The CLIVIA belongs to the same NEEP series as the GREE CLIVIA R32, with one small difference in rated COP at −8.3 °C. Our “platform” pages detail these names.
Where does the gap in the cost calculation come from?
Only from the two seasonal efficiencies on the certificate: HSPF2 Region V for winter, SEER2 for summer. The zone, the climate, the hours and the price per kWh are the same for both. Move the sliders: the gap follows the number of hours and the price tier.
The AHRI certificate values, side by side
| Measure | CHARMO R32 | CLIVIA R32 |
|---|---|---|
| Seasonal efficiency | ||
| SEER2 | 19 | 24.5 |
| EER2 | 9.75 | 13 |
| HSPF2 Region IV | 8.5 | 9.5 |
| HSPF2 Region V | 7.3 | 8.0 |
| Rated capacity at 35 °C (95 °F), cooling | 12,000 BTU/h | 12,000 BTU/h |
| Certified heating | ||
| Capacity at 8.3 °C (47 °F): min. / rated / max. | 3,070 / 12,000 / 12,000 BTU/h | 3,070 / 12,000 / 14,600 BTU/h |
| COP at 8.3 °C: at min., rated, max. | 5.29 / 3.52 / 3.52 | 5.62 / 3.78 / 3.72 |
| Capacity at −8.3 °C (17 °F): min. / rated / max. | 2,700 / 9,700 / 11,500 BTU/h | 2,700 / 12,000 / 12,000 BTU/h |
| COP at −8.3 °C: at min., rated, max. | 3.04 / 2.71 / 2.20 | 3.04 / 2.88 / 2.06 |
| Capacity at −15 °C (5 °F): min. / rated / max. | 2,600 / 9,100 / 9,100 BTU/h | 2,600 / 11,000 / 11,000 BTU/h |
| COP at −15 °C: at min., rated, max. | 2.54 / 1.80 / 1.80 | 3.17 / 1.95 / 1.95 |
| Coldest point on the certificate (different temperatures) | ||
| Test temperature | −25 °C (−13 °F) | −30 °C (−22 °F) |
| Capacity min. / max. | 1,800 / 6,500 BTU/h | 2,000 / 7,300 BTU/h |
| COP at min. / max. capacity | 2.03 / 1.42 | 2.79 / 1.51 |
| Certification | ||
| AHRI certificate · NEEP record | 217956851 · record 369973 | 217933620 · record 369980 |
| ENERGY STAR, directory (cold climate) | Yes, listed cold climate, Canada, May 28, 2026NEEP ENERGY STAR field: no | Yes, listed cold climate, United States and Canada, August 12, 2026 |
| Refrigerant | R-32, GWP 675 (IPCC AR4), class A2L (ASHRAE 34) | R-32, GWP 675 (IPCC AR4), class A2L (ASHRAE 34) |
“higher” marks the higher value of the same measure, under the same conditions. It is not a recommendation.
Both are on the AirGreen site.
AirGreen offers KINGHOME's CHARMO R32 and CLIVIA R32. For a quote or a question about your room, call or write to us.
Documents consulted
Data verified on November 10, 2026. Certified values: AHRI certificates read on NEEP. Declared values: KINGHOME sheets and GREE table cited above. Cost: AirGreen estimate, method v1.1.
KINGHOME, CHARMO, CLIVIA, GREE, LIVO, VITA and ENERGY STAR are trademarks of their respective owners. Logos and images are used only to identify the products. AirGreen is a dealer; this page is not produced, sponsored or approved by the manufacturers.
Photos: AirGreen and manufacturers, for identification.
Does a figure look wrong to you? Write to us at sales@airgreen.ca.