LG Multi F MAX LGRED and SAMSUNG FJM Premium, 4 zones, 36,000 BTU

Home / Comparisons / Multi-zone, 4 zones, 36,000 BTU

Comparison · Multi-zone · 4 zones · 36,000 BTU

LG Multi F MAX LGRED and SAMSUNG FJM Premium: distribution box or direct connections

Two R-32 outdoor units of 36,000 BTU/h for four rooms, connected in two different ways. With LG, a main line runs to a branch distribution box, which sends a short branch to each head. With SAMSUNG, four lines leave the outdoor unit directly. This page shows what each layout allows, according to the published limits, then the certified values of both systems.

SEER2 22 and 21.5HSPF2 V 9.8 and 7.7Max. total piping: 475.7 and 230 ft
LG Multi F MAX LGRED, 4 zones (AirGreen image)
LG

Multi F MAX LGRED · 4 zones, 36,000 BTU

KUMXA361A + distribution box + non-ducted indoor units · AHRI 215402345

See the product page
SAMSUNG FJM Premium, 4 zones (AirGreen image)
SAMSUNG

FJM Premium · 4 zones, 36,000 BTU

AJ036DXS4CG/AA + non-ducted indoor units · AHRI 216372792

See the product page
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 36,000 BTU/h zone in Montréal, at Hydro-Québec’s Rate D, taxes included. Both heat pumps are calculated in exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference point. Here, the zone is all four rooms together. In cooling at 35 °C, the certificates state 36,000 BTU/h for the Multi F MAX LGRED and 34,000 BTU/h for the FJM Premium: the calculation uses the common nominal size, 36,000 BTU/h.

How this amount is calculated
  1. Heat to deliver over the winter. A zone whose heat loss reaches 36,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours per day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump as for the baseboards: this simplification does not account for recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 36,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario you can set above, from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a ceiling, since a variable-speed unit slows down once the room is at temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. Network access charges, the same with or without a heat pump, are not counted.

AirGreen method v1.1, November 9, 2026. An estimate is used to compare units under the same conditions. The actual bill depends on the house, the insulation, the settings and the use; this amount is not a promise.

Distribution box or direct connections

Two ways to connect four rooms to a single outdoor unit

Set two distances: from the outdoor unit to the point where the lines split, then from there to each head. With LG, the distribution box goes at that point: one main line comes in, four branches go out. With SAMSUNG, each head has its own line, end to end. Both diagrams and both cards apply the limits published by each manufacturer.

Multi F MAX LGRED Distribution box

Outdoor unit box 30 ft 4 × 25 ft

One main line (Ø 3/8 – 3/4 in) to the box; one branch per head.

diagram

FJM Premium Direct connections

Outdoor unit 4 × 55 ft

Four ports on the outdoor unit; each line runs end to end.

diagram
length covered by the factory charge with refrigerant added, up to the maximum your total beyond a published limit

Published limits

Multi F MAXFJM Premium
Main line16.4 to 180.4 ftNot applicable
Per headBranch: 16.4 to 49.2 ftLine: up to 82 ft
Outdoor unit to one head32.8 to 229.6 ftUp to 82 ft
Maximum total475.7 ft230 ft
Without adding refrigerant180.4 ft230 ft
Height, outdoor unit and head98.4 ft49 ft
Height between two heads49.2 ft25 ft

Limits: LG submittal KUMXA361A (SB_Multi_F_MAX_LGRED_ODU_R32_KUMXA361A_1_26B) and SAMSUNG submittal AJ036DXS4CG/AA (version 02142025A). With LG, the length without added refrigerant splits into 49.2 ft of main line and 131.2 ft of branches; beyond that, 0.54 oz per foot of main line and 0.22 oz per foot of branch. LG also sets a maximum of 32.8 ft of height between the box and a head. This diagram applies published values to your settings; it does not replace the piping calculation done for the house.

Extreme cold

Below −15 °C: what each manufacturer publishes, at its exact temperature

NEEP certifies both systems at −15 °C and at −25 °C: the same temperatures for both. LG also publishes a maximum capacity at −20 °C in its submittal. Nothing is calculated between two points: between two published values, the page shows the range.

What each manufacturer publishes below −15 °C. LG: the heating range of the KUMXA361A runs from −13 to 64 °F wet bulb (about −25 to 18 °C); the submittal gives a maximum capacity of 40,000 BTU/h at −4 °F. SAMSUNG: the heating range of the AJ036DXS4CG/AA runs from −25 to 24 °C (−13 to 75 °F). For both, the coldest certified point is −25 °C, the bottom of the published range.
Documented features

What each manufacturer writes

LG submittal KUMXA361A and SAMSUNG submittal AJ036DXS4CG/AA. These documents describe the outdoor unit: several comfort features depend on the head chosen.

Extreme cold

Multi F MAX LGRED: heating listed from −13 to 64 °F wet bulb; 40,000 BTU/h maximum at −4 °F.

FJM Premium: heating listed from −25 to 24 °C.

Base pan heater

Multi F MAX LGRED: factory-installed base pan heater.

FJM Premium: base pan heater as standard.

Cooling in cold weather

Multi F MAX LGRED: from 14 °F (−10 °C); down to −4 °F with two ZLABGP04B wind baffles.

FJM Premium: from 14 to 115 °F (−10 to 46 °C).

Connection layout

Multi F MAX LGRED: at least one distribution box; two at most, with the ARBLN03321 Y-branch.

FJM Premium: four ports on the outdoor unit; adapters supplied.

Number of indoor units

Multi F MAX LGRED: two to five.

FJM Premium: two to four.

Compressor

Multi F MAX LGRED: scroll compressor; soft start.

FJM Premium: twin rotary BLDC compressor; soft start.

Restart after a power outage

Multi F MAX LGRED: “Auto restart”.

FJM Premium: automatic restart.

Monitoring

Multi F MAX LGRED: self-diagnosis; three-minute restart delay.

FJM Premium: output for an R-32 leak alarm, with the MIM-B14U module.

Outdoor fans

Multi F MAX LGRED: two fans; defrost and deicing.

FJM Premium: two fans.

Sound

How loud the outdoor unit is, according to its manufacturer

Outside, a single unit serves all four rooms: this is the figure that matters for the neighbours. Inside, the sound depends on each head chosen; its sheet comes with the quote.

dB(A)

How to read these figures. The dB(A) measures a noise level as the ear perceives it: the lower the figure, the quieter the unit. Each dot is a mode published by the manufacturer.

Why this is not a ranking. Each manufacturer measures under its own conditions. LG cites the ISO 3745 standard; the SAMSUNG submittal gives a sound pressure without naming a standard. A gap of a few dB(A) can come from the method as much as from the unit.

Outdoor unit, outside

Cooling and heating, published values for the 36,000 BTU/h unit

Measured by each manufacturer using its own method: read them separately, not as a ranking.

Sources: LG submittal KUMXA361A (sound pressure, ISO 3745) and SAMSUNG submittal AJ036DXS4CG/AA (sound pressure).

Installation

Outside, on the ground, in the piping

Outdoor units, at the same height scale

LG KUMXA361A outdoor unitKUMXA361A
SAMSUNG AJ036DXS4CG/AA outdoor unitAJ036DXS4CG

Depth 13 in
218.3 lb

Depth 13 in
194 lb

Top: photos from the AirGreen product cards, scaled to each unit’s published height. Bottom, diagram: published width and height, at the same scale. The two units are almost the same width; the LG unit is about 6 1/2 in taller.

What goes between the outdoor unit and the heads

  • Multi F MAX LGRED
    One LG distribution box (PMBD3620ZR, PMBD3630ZR, PMBD3640ZR or PMBD3641ZR): it goes between the main line and the branches. Two boxes at most, joined by the ARBLN03321 Y-branch, with at most 49.2 ft of height between them. A head can be up to 32.8 ft higher or lower than its box.
  • FJM Premium
    Nothing in between: each line runs from the outdoor unit’s port to its head. The port adapters are supplied with the unit. The factory charge, 109.3 oz of R-32, covers up to 230 ft of piping in total.

Per each manufacturer’s submittal. The location of the box, service access and the line routing are decided during the assessment visit.

InstallationMulti F MAX LGREDFJM Premium
Connection layoutMain line, distribution box, then one branch per headOne direct line per head, four ports on the outdoor unit
Maximum piping lengthTotal of all lines475.7 ftMain line and branches together.230 ft
Main pipingUp to the distribution boxFrom 16.4 to 180.4 ftNot applicable: one line per head
Piping per indoor unitFrom the outdoor unit to one headFrom 32.8 to 229.6 ftIncluding a branch of 16.4 to 49.2 ft after the box; at most 295.3 ft for all branches together.Up to 82 ft per line
Pre-charged lengthWithout adding refrigerant180.4 ft49.2 ft of main line and 131.2 ft of branches.230 ftFactory charge of 109.3 oz.
Refrigerant to add, beyond that0.54 oz per foot of main line; 0.22 oz per foot of branchNo addition published up to 230 ft, the maximum
Maximum height differenceOutdoor unit and indoor unit98.4 ft49 ft
Maximum height differenceBetween two indoor units49.2 ft32.8 ft between the box and a head.25 ft
Liquid – gas diameters3/8 – 3/4 inMain line, up to the box.1/4 – 3/8 in and 1/4 – 1/2 inTwo ports of each size.
Factory refrigerant charge9.262 lb of R-32109.3 oz (6.83 lb) of R-32
Outdoor unit W × H × D, weight37 13/32 × 54 1/4 × 13 in, 218.3 lb37 × 47 5/8 × 13 in, 194 lb
Electrical protectionPer the manufacturerMOP 40 A (MCA 32.1 A)MOP 40 A (MCA 35.9 A)
Number of indoor unitsFrom 2 to 5From 2 to 4
Heating range listed−25 to 18 °C−13 to 64 °F wet bulb.−25 to 24 °C−13 to 75 °F.

Clearances around the outdoor unit: figures in the installation manuals, not reproduced on this page.

Questions

What people ask us about these two systems

What does LG’s distribution box do?

It receives the main line coming from the outdoor unit and splits it into branches, one per head. The main line can run up to 180.4 ft, and each branch is 16.4 to 49.2 ft long. The box therefore goes near the rooms it serves, and it is what allows long distances to the outdoor unit.

Why does the length per line matter so much with the FJM Premium?

Because each head has its own line to the outdoor unit: at most 82 ft per line, and at most 230 ft for all four together. Four 55 ft lines already make 220 ft. On the other hand, there is no box to install, and the factory charge covers the full allowed length.

Are both really 36,000 BTU/h?

In cooling at 35 °C, the Multi F MAX LGRED’s certificate states 36,000 BTU/h and the FJM Premium’s, 34,000 BTU/h. In heating at 8.3 °C, the certified rated capacities are 45,000 and 36,600 BTU/h. The cost calculation on this page uses the common nominal size, 36,000 BTU/h.

Will refrigerant need to be added?

With the FJM Premium, the factory charge covers up to 230 ft, the published maximum. With the Multi F MAX LGRED, the factory charge covers 49.2 ft of main line and 131.2 ft of branches; beyond that, LG calls for 0.54 oz per foot of main line and 0.22 oz per foot of branch. The diagram above does this calculation for your distances.

Can a fifth head be connected?

The LG submittal allows two to five indoor units on the KUMXA361A; the SAMSUNG submittal, two to four on the AJ036DXS4CG/AA, which has four ports. This page compares both in four zones, the configuration AirGreen sells for each.

Does the certificate change with ducted units?

Yes. A multi-zone AHRI certificate covers a set: one outdoor unit and one type of indoor unit. The values on this page are those of the “non-ducted” sets. For the FJM Premium, SAMSUNG also has a ducted certificate (216372800) and a mixed-combination certificate (216411176).

Certified data

All AHRI and NEEP values

Certified valueMulti F MAX LGREDFJM Premium
Cooling
Rated capacity at 35 °C36,000 BTU/h34,000 BTU/h
35 °C: min. / rated / max.BTU/h10,800 / 36,000 / 47,0009,500 / 34,000 / 42,000
SEER222.021.5
EER214.512.5
Heating, same conditions
HSPF2 Region IV / V11.0 / 9.89.5 / 7.7
8.3 °C: min. / rated / max.BTU/h12,420 / 45,000 / 50,0007,600 / 36,600 / 54,500
8.3 °C: COP min. / rated / max.5.13 / 4.00 / 3.404.95 / 4.21 / 3.47
−8.3 °C: min. / rated / max.BTU/h14,880 / 29,600 / 49,60013,500 / 23,000 / 36,600
−8.3 °C: COP min. / rated / max.3.16 / 2.38 / 2.632.83 / 2.45 / 1.83
−15 °C: min. / rated / max.BTU/h13,392 / 41,500 / 45,00013,500 / 36,600 / 36,600
−15 °C: COP min. / rated / max.2.93 / 1.89 / 2.272.20 / 2.04 / 2.04
Coldest point of both certificates (same temperature)
Test temperature−25 °C (−13 °F)−25 °C (−13 °F)
Capacity min. / max.BTU/h11,212 / 35,90011,000 / 20,000
COP min. / max.2.61 / 1.871.90 / 1.87
Certification
ENERGY STAR / cold climate (NEEP)Yes / YesYes / Yes
AHRI certificate · NEEP record215402345 · 389367216372792 · 417119
RefrigerantR-32 (GWP 675, IPCC AR4; class A2L)R-32 (GWP 675, IPCC AR4; class A2L)

“higher” marks the higher value of the same measure under the same conditions. It is not a recommendation. AHRI certificate values published by NEEP (non-ducted indoor units), retrieved November 10, 2026; capacities in BTU/h at 21.1 °C indoors in heating and 26.7 °C in cooling.

Both are on AirGreen’s website.

To choose for your four rooms, talk it over with our team: bring the room dimensions, the floor of each one, the planned outdoor location, the distance to the rooms and your current heating.

Sources and documents

Where each figure comes from

NEEP, record 389367 (LG, KUMXA361A)AHRI 215402345, non-ducted units · retrieved November 10, 2026 NEEP, record 417119 (SAMSUNG, AJ036DXS4CG)AHRI 216372792, non-ducted units · retrieved November 10, 2026
LG, submittal KUMXA361ASB_Multi_F_MAX_LGRED_ODU_R32_KUMXA361A_1_26B (media.us.lg.com) · capacities, range, piping, boxes, charge, electrical, sound, features · retrieved November 10, 2026
SAMSUNG, submittal AJ036DXS4CG/AAVersion 02142025A · ranges, ports and piping, charge, electrical, sound, features · retrieved November 10, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · estimated operating cost Natural Resources Canada, HOT2000 climate mapMontréal Intl station: 4,167 degree-days (18 °C), −23.1 °C design temperature · retrieved November 10, 2026