FUJITSU AIRSTAGE AQUILA and LG Multi F R32, 3 zones, 24,000 BTU

Home / Comparisons / Multi-zone, 3 zones, 24,000 BTU

Comparison · Multi-zone · 3 zones · 24,000 BTU

FUJITSU AIRSTAGE AQUILA and LG Multi F R32: three rooms, three line sets

Two R-32 outdoor units that serve up to three indoor units. With three rooms, the piping becomes a real question: the length of each line, the total, the height between floors. This page sets out the limits each manufacturer publishes, then the certified values of both systems.

SEER2 23 and 22.5HSPF2 V 8.5 and 7.69Max. total piping: 164 and 230 ft
FUJITSU AIRSTAGE AQUILA, 3 zones (AirGreen image)
FUJITSU AIRSTAGE

AQUILA · 3 zones, 24,000 BTU

AOUH24KWAS3 + non-ducted indoor units · AHRI 215447687

Also sold as GENERAL AIRSTAGE.

See the product page
LG Multi F R32, 3 zones (AirGreen image)
LG

Multi F R32 · 3 zones, 24,000 BTU

KUMXB241A + non-ducted indoor units · AHRI 214848483

See the product page
Estimated operating cost

What the electricity costs, in dollars, winter and summer

AirGreen estimate for the same 24,000 BTU/h zone in Montréal, at Hydro-Québec’s Rate D, taxes included. Both heat pumps are calculated in exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards serve as the reference point. Here, the zone is all three rooms together. In cooling at 35 °C, the certificates state 22,000 BTU/h for the AQUILA and 24,000 BTU/h for the Multi F R32: the calculation uses the common nominal size, 24,000 BTU/h.

How this amount is calculated
  1. Heat to deliver over the winter. A zone whose heat loss reaches 24,000 BTU/h ( kW) at −23.1 °C, Montréal’s design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours per day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump as for the baseboards: this simplification does not account for recovery after a temperature setback.
  2. Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
  3. Electricity for cooling. 24,000 BTU/h ÷ SEER2 × hours per day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario you can set above, from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day long: that is a ceiling, since a variable-speed unit slows down once the room is at temperature.
  4. Price. Hydro-Québec Rate D in effect April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. Network access charges, the same with or without a heat pump, are not counted.

AirGreen method v1.1, November 9, 2026. An estimate is used to compare units under the same conditions. The actual bill depends on the house, the insulation, the settings and the use; this amount is not a promise.

Three rooms, three lines

Set the length of each line and the height between floors

Each indoor unit has its own pair of pipes running to the outdoor unit. Both manufacturers set a length per line, a total for the three lines, a length already charged at the factory and two maximum heights. Set up your house: the diagram and both cards update with each system’s published limits.

2nd floor1st floorGround Outdoor unit 20 ft 30 ft 40 ft 10 ft 8 ft diagram

Total piping: 90 ft

Published limits

AQUILAMulti F R32
Per line16 to 82 ft9.8 to 82 ft
Maximum total164 ft230 ft
Pre-charged98 ft98.4 ft
Outdoor unit and head49 ft49.2 ft
Between two heads33 ft24.6 ft
below the published minimum factory charge refrigerant to add, up to the maximum your total

Limits: FUJITSU AIRSTAGE “Submittal 24KWAS3” (version 20250409A) and brochure FG2057B for heights; LG submittal KUMXB241A (SB_Multi_F_ODU_R32_KUMXB241A_2025_01_07). LG states that its lengths are equivalent lengths, elbows included. This diagram applies published values to your settings; it does not replace the piping calculation done for the house.

Published combinations

Three heads: the sets each table provides for

A 24,000 BTU/h outdoor unit can connect more than its own size, up to a ceiling. Choose three heads, in thousands of BTU/h: the page shows whether the combination is in the manufacturer’s table and what it represents relative to the system.

Heads from 7,000 to 18,000 BTU/h. Tables read from the text of the documents: FUJITSU AIRSTAGE brochure FG2057B and LG “R32 Multi F and Multi F MAX Outdoor Unit Combination Data Manual” (CDM_Multi_F-MAX_ODU_R32_05_25), KUMXB241A section.

Total connected: 27,000 BTU/h

Extreme cold

Below −15 °C: what each manufacturer publishes, at its exact temperature

NEEP certifies both systems at −15 °C, the same temperature. The Multi F R32 has one more certified point, at −20 °C. Further down, each card shows its last published value and what the manufacturer says beyond it. Nothing is calculated between two points.

What each manufacturer publishes below −15 °C. FUJITSU AIRSTAGE: the published heating range of the AOUH24KWAS3 runs from −15 to 24 °C; the submittal adds that the system keeps operating below that range, depending on conditions, that it has no low-temperature cut-out, and that its capacity is not tested outside the range. LG: the heating range of the KUMXB241A runs from −4 to 64 °F wet bulb; the submittal gives 15,400 BTU/h of maximum capacity at −4 °F, the same value as the NEEP point at −20 °C. AirGreen also offers, in 3 zones, the AQUILA XLTH (AOUH24KWAH3): its certificate goes down to −26.1 °C, with 14,000 BTU/h of maximum capacity.
Documented features

What each manufacturer writes

FUJITSU AIRSTAGE submittal 24KWAS3 and brochure FG2057B; LG submittal KUMXB241A and LG combination manual. These documents mostly describe the outdoor unit: several comfort features depend on the head chosen.

Extreme cold

AQUILA: heating listed from −15 to 24 °C; no low-temperature cut-out, capacity not tested below the range.

Multi F R32: heating listed from −4 to 64 °F wet bulb; defrost and deicing.

Cooling in cold weather

AQUILA: from 14 to 122 °F (−10 to 50 °C).

Multi F R32: from 14 to 118 °F; down to −4 °F with the ZLABGP03A wind baffle.

Choice of heads

AQUILA: wall-mounted, Slim Duct, compact cassette and mid static ducted.

Multi F R32: standard wall-mounted, ART COOL Mirror, 1-way and 4-way cassettes, low-wall console, ducted units and multi-position air handler.

Connectable capacity

AQUILA: from 14,000 to 31,000 BTU/h, “up to 130%”.

Multi F R32: from 14,000 to 33,000 BTU/h, two to three indoor units.

Compressor

AQUILA: INVERTER compressor; current limit function.

Multi F R32: twin rotary inverter compressor; soft start.

Electrical protection

AQUILA: circuit, fan motor and compressor protection.

Multi F R32: self-diagnosis; three-minute restart delay.

Restart after a power outage

AQUILA: not stated in the 24KWAS3 submittal.

Multi F R32: “Auto restart”.

Maintenance and coil protection

AQUILA: Blue Fin–treated heat exchanger against corrosion.

Multi F R32: Gold Fin–treated heat exchanger.

Base pan heater

AQUILA: not stated in the 24KWAS3 submittal.

Multi F R32: PQSH1203 pan heater available as an option.

Sound

How loud each one is, according to its manufacturer

Outside, a single unit serves all three rooms: this figure matters for the neighbours. Inside, the sound depends on the head chosen; the values below are those of a 9,000 BTU/h wall-mounted head from each brand.

dB(A)

How to read these figures. The dB(A) measures a noise level as the ear perceives it: the lower the figure, the quieter the unit. Each dot is a fan speed or a mode published by the manufacturer.

Why this is not a ranking. Each manufacturer measures under its own conditions. LG cites the ISO 3745 standard; FUJITSU AIRSTAGE states an anechoic chamber without naming a standard. A gap of a few dB(A) can come from the method as much as from the unit.

Outdoor unit, outside

Cooling and heating, published values for the 24,000 BTU/h unit

Indoor unit, in the room

Cooling, published speeds, 9,000 BTU/h wall-mounted head

Measured by each manufacturer using its own method: read them separately, not as a ranking.

Sources: FUJITSU AIRSTAGE submittal 24KWAS3 (outdoor unit sound pressure) and brochure FG2057B (ASUH09KPAS); LG submittal KUMXB241A (± 1 dB(A), ISO 3745) and LG sheet for the KNUAB091A wall unit (± 3 dB(A)).

Installation

Outside, on the wall, in the piping

Outdoor units, at the same height scale

FUJITSU AIRSTAGE AOUH24KWAS3 outdoor unitAOUH24KWAS3
LG KUMXB241A outdoor unitKUMXB241A

Depth 12 3/8 in
101 lb

Depth 13 in
103.4 lb

Top: photos from the AirGreen product cards, taken at three-quarter view and scaled to each unit’s published height. Bottom, diagram: published width and height, at the same scale. The LG unit is slightly wider and lower; the weight is almost the same.

9,000 BTU/h wall-mounted heads to scale

AQUILA headASUH09KPAS: 32 13/16 × 10 5/8 × 8 3/4 in
FUJITSU AIRSTAGE wall-mounted head from the AirGreen card, to scale
32.81 in
LG headKNUAB091A: 32 15/16 × 12 1/8 × 7 9/16 in
LG wall-mounted head from the AirGreen card, to scale
32.94 in

Published widths: FUJITSU AIRSTAGE (brochure FG2057B) and LG (KNUAB091A sheet). The two heads are almost the same width.

InstallationAQUILAMulti F R32
Maximum piping lengthTotal of the three lines164 ftPublished minimum: 33 ft in total.230 ftEquivalent lengths, per note 3 of the LG submittal.
Piping length per indoor unitFrom 16 to 82 ftFrom 9.8 to 82 ft
Pre-charged lengthTotal of the three lines98 ftThen 0.22 oz per foot (20 g/m).98.4 ftThen 0.22 oz per foot.
Maximum height differenceOutdoor unit and indoor unit49 ft33 ft between two indoor units (brochure FG2057B).49.2 ft24.6 ft between two indoor units.
Liquid – gas diameters1/4 – 3/8 inTwo 1/4 – 3/8 in connections and one 1/4 – 1/2 in connection.1/4 – 3/8 inThree 1/4 – 3/8 in connections.
Factory refrigerant charge3 lb 15 oz (1,800 g) of R-323.08 lb of R-32
Outdoor unit W × H × D, weight32 5/16 × 28 3/16 × 12 3/8 in, 101 lb34 1/4 × 25 13/32 × 13 in, 103.4 lbDimensions read from the dimensioned drawing in the LG submittal.
Indoor unit, weight9,000 BTU/h wall-mounted head21 lbASUH09KPAS.19.73 lbKNUAB091A.
Electrical protectionPer the manufacturer20 A breaker (MCA 18 A)MOP 20 A (MCA 16.5 A)
Number of indoor unitsUp to 3From 2 to 3
Heating / cooling range listed−15 to 24 °C / −10 to 50 °C−20 to 18 °C / −10 to 48 °C−4 to 64 °F wet bulb / 14 to 118 °F dry bulb.

Clearances around the outdoor unit: figures in the installation manuals, not reproduced on this page.

Questions

What people ask us about these two systems

Why the AQUILA rather than the AQUILA XLTH?

AirGreen offers both in 3 zones at 24,000 BTU/h. This page compares the two units that carry neither the XLTH label at FUJITSU AIRSTAGE nor the LGRED label at LG: the AOUH24KWAS3 and the KUMXB241A. The AQUILA XLTH (AOUH24KWAH3, AHRI 215447693) has a published heating range down to −26 °C and a certified point at −26.1 °C.

Are both really 24,000 BTU/h?

In cooling at 35 °C, the AQUILA’s certificate states 22,000 BTU/h and the Multi F R32’s, 24,000 BTU/h. In heating at 8.3 °C, the certified rated capacities are 24,000 and 24,600 BTU/h. The cost calculation on this page uses the common nominal size, 24,000 BTU/h.

What happens below −15 °C with the AQUILA?

Its published heating range stops at −15 °C. The FUJITSU AIRSTAGE submittal states that the system keeps operating below that range, depending on conditions, with no low-temperature cut-out, but that its capacity is not tested outside the range. The last certified value is 19,200 BTU/h at −15 °C.

Will refrigerant need to be added?

Both units are charged at the factory for about 98 ft of piping in total, all three lines together. Beyond that, each manufacturer calls for 0.22 oz per foot. Three 35 ft lines make 105 ft, or about 1.5 oz to add for either one.

Why does the height between two heads matter?

Because each manufacturer sets a maximum difference between indoor units: 33 ft for the AQUILA, 24.6 ft for the Multi F R32. One head in the basement and another on the second floor can come close to those values. The difference between the outdoor unit and the heads is 49 and 49.2 ft.

Does the certificate change with ducted units?

Yes. A multi-zone AHRI certificate covers a set: one outdoor unit and one type of indoor unit. The values on this page are those of the “non-ducted” sets. For the AQUILA, the submittal also gives a SEER2 of 19.5 with ducted units and 21 in a mixed combination.

Certified data

All AHRI and NEEP values

Certified valueAQUILAMulti F R32
Cooling
Rated capacity at 35 °C22,000 BTU/h24,000 BTU/h
35 °C: min. / rated / max.BTU/h6,100 / 22,000 / 27,0008,400 / 24,000 / 25,000
SEER223.022.5
EER213.012.5
Heating, same conditions
HSPF2 Region IV / V10.5 / 8.59.8 / 7.69
8.3 °C: min. / rated / max.BTU/h6,800 / 24,000 / 31,00010,080 / 24,600 / 29,000
8.3 °C: COP min. / rated / max.5.69 / 4.60 / 4.175.01 / 4.19 / 3.02
−8.3 °C: min. / rated / max.BTU/h4,700 / 15,600 / 22,6006,781 / 15,300 / 21,400
−8.3 °C: COP min. / rated / max.4.05 / 3.34 / 2.563.82 / 2.93 / 2.81
−15 °C: min. / rated / max.BTU/h3,900 / 19,200 / 19,2005,759 / 17,300 / 18,400
−15 °C: COP min. / rated / max.3.36 / 2.04 / 2.043.59 / 2.30 / 2.51
Coldest point of each certificate (different temperatures)
Test temperature−15 °C (5 °F)−20 °C (−4 °F)
Capacity min. / max.BTU/h3,900 / 19,2005,200 / 15,400
COP min. / max.3.36 / 2.043.46 / 2.23
Certification
ENERGY STAR / cold climate (NEEP)Yes / YesYes / No
ENERGY STAR directory, markets listedUnited States, CanadaUnited States, Canada
AHRI certificate · NEEP record215447687 · 455170214848483 · 392649
RefrigerantR-32 (GWP 675, IPCC AR4; class A2L)R-32 (GWP 675, IPCC AR4; class A2L)

“higher” marks the higher value of the same measure under the same conditions. It is not a recommendation. AHRI certificate values published by NEEP (non-ducted indoor units), retrieved November 10, 2026; capacities in BTU/h at 21.1 °C indoors in heating and 26.7 °C in cooling.

Both are on AirGreen’s website.

To choose for your three rooms, talk it over with our team: bring the room dimensions, the floor of each one, the planned outdoor location and your current heating.

Sources and documents

Where each figure comes from

NEEP, record 455170 (FUJITSU AIRSTAGE, AOUH24KWAS3)AHRI 215447687, non-ducted units · retrieved November 10, 2026 NEEP, record 392649 (LG, KUMXB241A)AHRI 214848483, non-ducted units · retrieved November 10, 2026 NEEP, record 455167 (FUJITSU AIRSTAGE, AOUH24KWAH3)AHRI 215447693, AQUILA XLTH, cited in the questions · retrieved November 10, 2026
ENERGY STAR directory (data.energystar.gov, dataset 83eb-xbyy)AOUH24KWAS3: cold climate yes; KUMXB241A: cold climate no; markets United States and Canada · retrieved November 10, 2026
FUJITSU AIRSTAGE, “Submittal 24KWAS3”Version 20250409A, pp. 1 to 3 · efficiencies, ranges, piping, charge, electrical, sound · copy hosted by a retailer · retrieved November 10, 2026 FUJITSU AIRSTAGE, brochure H Series / AQUILA / AQUILA XLTH (FR)Part FG2057B, rev. 8/2025 · 3-head combinations, height differences, ASUH09KPAS head LG, submittal KUMXB241ASB_Multi_F_ODU_R32_KUMXB241A_2025_01_07 · capacities, ranges, piping, electrical, sound, dimensioned drawing · copy hosted by a retailer · retrieved November 10, 2026 LG, Multi F and Multi F MAX R32 combination manualCDM_Multi_F-MAX_ODU_R32_05_25, KUMXB241A section · compatible heads and combinations · retrieved November 10, 2026
LG, sheet for the KNUAB091A wall unitSB_MultiF_HiEff_WallMounted_IDU_R32_KNUAB091A, January 10, 2025 · sound and weight of the 9,000 BTU/h head
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · estimated operating cost Natural Resources Canada, HOT2000 climate mapMontréal Intl station: 4,167 degree-days (18 °C), −23.1 °C design temperature · retrieved November 10, 2026