Wall-mounted heat pump and electric baseboards: who heats when
A wall-mounted unit does not replace your baseboards: it goes first. As long as its capacity is enough, it heats the zone; when the cold exceeds what it can supply, the baseboards make up the difference. Here is where that handover happens for two 12,000 BTU FUJITSU AIRSTAGE examples, the settings Hydro-Québec publishes, and what it all represents in dollars.

ORION XLTH · 12,000 BTU
ASUH12KZAS / AOUH12KZAH1 · AHRI 214888802
See the product page
ALTAIR 500 · 12,000 BTU
ASUH12KPAS / AOUH12KPAS1 · AHRI 215212610
See the product pageWhat the electricity costs, in dollars, winter and summer
AirGreen estimate for the same 12,000 BTU/h zone in Montréal, at Hydro-Québec Rate D, taxes included. The two heat pumps of the example are calculated exactly the same way, with the same method as on all our comparison pages; only their certified efficiencies change. Electric baseboards alone serve as a reference point, and the efficiency used for each heat pump already counts the backup in extreme cold.
How this amount is calculated
- Heat needed over the winter. A zone whose heat loss reaches 12,000 BTU/h ( kW) at −23.1 °C, the Montréal design temperature: kW × 24 h × 4,167 degree-days ÷ (18 − (−23.1)) = kWh of heat for round-the-clock heating, all winter. Heating degree-days (base 18 °C) and design temperature: Natural Resources Canada, HOT2000 climate data, Montréal Intl station. With fewer hours a day (“Heating” slider), the heat is reduced in the same proportion, for the heat pump and for the baseboards alike: this is a simplification that ignores the recovery after a temperature setback.
- Electricity for heating. Heat pump: heat × 3.412 ÷ HSPF2 Region V, the AHRI certificate value published by NEEP. Region V is the coldest in the standard, and its calculation includes the electric backup expected when the heat pump is no longer enough. Electric baseboards: 1 kWh of electricity for 1 kWh of heat.
- Electricity for cooling. 12,000 BTU/h ÷ SEER2 × hours a day × 60 days ÷ 1,000: the method of Hydro-Québec’s air-conditioning calculator, with the SEER2 seasonal efficiency from the AHRI certificate. The number of hours is a scenario, adjustable above from 1 to 24 h. At 24 h, the calculation assumes rated capacity all day: that is a maximum, since a variable-speed unit slows down once the room is at the right temperature.
- Price. Hydro-Québec Rate D in effect on April 1, 2026: 7.065¢ per kWh up to 40 kWh a day, 11.142¢ beyond that; the average price, 9.104¢, is the one Hydro-Québec’s calculators use. GST and QST included. Network access charges, the same with or without a heat pump, are not counted.
AirGreen method v1.1, November 9, 2026. An estimate is meant to compare units under the same conditions. The actual bill depends on the house, insulation, settings and use; this amount is not a promise.
At each temperature, the wall-mounted unit’s share and the baseboards’ share
Two identical rooms, a 12,000 BTU wall-mounted unit in each, the baseboards under the window. Move the temperature slider: it stops at the temperatures where a capacity is published. Also set the heat loss of the zone, and watch when the baseboards come into play.


Two thermostats, one gap: what decides which one heats
Hydro-Québec publishes a tip sheet for households that have a heat pump and baseboards. It comes down to one line: the heat pump is set to the desired temperature, the baseboards 2 to 3 °C lower, so that they heat only when needed. Try your own settings.
| Setting | What Hydro-Québec advises | What it changes |
|---|---|---|
| Heat pump thermostat | A comfortable temperature, for example 20 °C. | The heat pump is the one aiming for the room temperature. |
| Baseboard thermostat | Lower, for example 18 °C. | The baseboards start only if the room drops below that setting. |
| Gap between the two | 2 to 3 °C. | The heat pump provides the main heating; the baseboards, the backup. |
| Operating mode | Heating mode, rather than Automatic mode. | In Automatic mode, cooling can start on a mild, sunny winter day. |
| Outdoor unit clearance | Always kept clear: vegetation and snow. | The outdoor unit draws its heat from the air passing through it. |
| Extreme cold | The baseboards run as needed, particularly in very cold weather. | Below a model’s minimum operating temperature, the backup takes over. |
Source: Hydro-Québec, “Conseils d’utilisation d’une thermopompe” (tip sheet, in French), rev. 07/2026 (2025G386F), and its page on central and wall-mounted heat pumps, consulted November 9, 2026. The 20 °C and 18 °C examples are those of the tip sheet.
Below −15 °C: every published figure, at its exact temperature
Extreme cold is where the two examples part ways. The ORION XLTH is certified down to −26.1 °C, with a manufacturer point at −21 °C. For the ALTAIR 500, the last published point is at −15 °C, the bottom of its stated heating range.
What people ask us about baseboards
Should the baseboards be turned off when you have a wall-mounted unit?
Hydro-Québec does not advise turning them off, but setting them lower than the heat pump, by 2 to 3 °C: for example 18 °C when the heat pump is at 20 °C. They then heat only when needed.
Why keep the baseboards?
Because they serve as backup. According to NRCan’s sizing guide, when a ductless heat pump is added to an existing heating system, that system left in place can meet the whole load in the coldest weather. A wall-mounted unit also heats the zone where it is located; closed rooms keep their own heating.
At what temperature is the wall-mounted unit no longer enough?
There is no single temperature: it depends on the heat loss of the zone and on the capacity of the model. In the illustration, for a zone with a design heat loss of 12,000 BTU/h, the ORION XLTH still covers the load at −21 °C (14,880 BTU/h published for a load of 11,300); the ALTAIR 500 covers it at −8.3 °C (11,000 for 7,400) and the baseboards make up the difference at −15 °C (8,500 for 9,500).
Should I switch to Automatic mode in winter?
Hydro-Québec advises Heating mode: in Automatic mode, cooling can start on a mild, sunny winter day.
Do the amounts in the Cost section count the baseboards?
Yes, for the backup share. The seasonal efficiency used, HSPF2 Region V, includes the electric backup expected when the heat pump is no longer enough. The “electric baseboards” amount corresponds to a zone heated by baseboards alone.
Do the two examples heat down to the same temperature?
No. FUJITSU AIRSTAGE states heating down to −26 °C for the ORION XLTH and down to −15 °C for the ALTAIR 500. Below −15 °C, the ALTAIR 500 sheet no longer publishes a capacity: the Extreme cold section shows every published point.
All the AHRI and NEEP values of the two examples
| Certified value | ORION XLTH | ALTAIR 500 |
|---|---|---|
| Cooling | ||
| Rated capacity at 35 °C | 12,000 BTU/h | 12,000 BTU/h |
| SEER2 | 30.5 | 24 |
| EER2 | 16 | 11.7 |
| Heating, same conditions | ||
| HSPF2 Region IV / V | 12.7 / 10.1 | 10.5 / 7.9 |
| 8.3 °C: min. / rated / max.BTU/h | 3,500 / 16,000 / 23,600 | 2,700 / 14,000 / 17,000 |
| 8.3 °C: COP at min., rated, max. | 5.13 / 4.64 / 3.07 | 6.09 / 3.80 / 3.69 |
| −8.3 °C: min. / rated / max.BTU/h | 2,200 / 10,000 / 18,700 | 2,900 / 8,700 / 11,000 |
| −8.3 °C: COP at min., rated, max. | 3.39 / 3.45 / 2.44 | 4.05 / 2.86 / 2.69 |
| −15 °C: min. / rated / max.BTU/h | 1,950 / 16,600 / 16,600 | 2,100 / 8,500 / 8,500 |
| −15 °C: COP at min., rated, max. | 3.36 / 2.16 / 2.16 | 2.56 / 2.29 / 2.29 |
| Coldest point — different temperatures, not highlighted | ||
| Test temperature | −26.1 °C (−15 °F) | −15 °C (5 °F) |
| Capacity min. / max. | 1,400 / 12,200 BTU/h | 2,100 / 8,500 BTU/h |
| COP min. / max. | 2.74 / 1.81 | 2.56 / 2.29 |
| Certifications and refrigerant | ||
| ENERGY STAR / cold climate (NEEP) | Yes / Yes | Yes / No |
| AHRI certificate · NEEP record | 214888802 · 392122 | 215212610 · 392096 |
| RefrigerantGWP per the IPCC (AR4); ASHRAE 34 class | R-32 · GWP 675 · A2L | R-32 · GWP 675 · A2L |
higher marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Capacities and COPs by test point are not highlighted: the order changes with the point you read. The two examples are also sold under the GENERAL AIRSTAGE name.
The two examples are on AirGreen’s site.
Tell us which zone you want to heat and which baseboards are already there: our team looks with you at what each model would cover.
Where each figure comes from
Data verified November 9, 2026. Performance: AHRI certificates and NEEP database. Operating ranges and percentages in extreme cold: per the manufacturer. Settings: Hydro-Québec texts cited, which can change. When a source contradicts the AHRI certificate, the certificate prevails. This guide explains how the two work together with the help of two examples; it does not rank any unit. Other models have other values.
Trademarks. FUJITSU AIRSTAGE, ORION XLTH, ALTAIR 500 and AIRSTAGE are trademarks of their respective owners. The logos are used only to identify the products shown. AirGreen is a retailer of the brand; this page is not produced, sponsored or approved by the manufacturer or by Hydro-Québec. FUJITSU AIRSTAGE systems are also sold under the GENERAL AIRSTAGE name.
Photos: AirGreen and manufacturer, for identification purposes. The rooms are diagrams.
Does a figure look inaccurate? Write to us: every reported figure is checked again.