Sizing a heat pump: heat loss, not square feet
Two houses with the same floor area can call for very different heat pumps. What counts is the heat the house loses in cold weather, and that figure is calculated. Here is what the calculation looks at, how it reads against a unit’s certified capacity, and what Natural Resources Canada’s guide asks the professional to decide.

ORION XLTH · 9,000 to 24,000 BTU
KZAH series · five sizes · AHRI certificates in the data section
See the product pageDesign heat loss
Set by a calculation · CSA F280-12 standard
See what the calculation looks atSame floor area, not the same heat loss
House A was left as built. House B has the same floor area: adjust its insulation, its windows and its airtightness, and watch the arrows. The thicker an arrow, the more heat escapes that way.
House A
As built · same floor areaHouse B
Adjustable · same floor areaIllustration not to scale: the thickness of the arrows and the five steps give an order of magnitude, not a measurement. The heat loss of a real house is established by calculation, as the next section explains.
What a heat loss calculation takes into account
In Canada, the reference method is CSA F280-12, “Determining the required capacity of residential space heating and cooling appliances.” It is used to calculate a building’s heat losses and heat gains in order to choose the capacity of the appliances. Floor area is only one input among others.
| What the calculation looks at | What the texts say | What floor area alone does not tell |
|---|---|---|
| Building envelope | Design loads are determined from the characteristics of the building envelope.NRCan, sizing guide, figure 13 | The insulation of the walls, roof and floors, which changes from one house to the next. |
| Windows and glazing | Heat gain through glazed surfaces, adjusted for shading.CSA Group, presentation of standard F280-12 | The glazed area, its orientation and what shades it. |
| Air leakage | Air change heat loss, calculated for each room.CSA Group, presentation of standard F280-12 | Airtightness: two houses of the same size do not let the same air through. |
| Continuous ventilation | Heat loss from continuous ventilation.CSA Group, presentation of standard F280-12 | Whether there is an air exchanger, and its airflow. |
| Foundations | Heat loss models for the common types of foundations.CSA Group, presentation of standard F280-12 | Basement, crawl space or slab: the below-grade part loses heat differently from the walls. |
| Local climate | The calculation starts from the weather data of the location. In Montréal, the design temperature used on our pages is −23.1 °C.CSA Group; NRCan, HOT2000 climate map, Montréal Intl station | The same house, in another region, no longer has the same load. |
| Indoor conditions | The capacity chosen must maintain the specified indoor conditions.CSA Group, presentation of standard F280-12 | The temperature you want to maintain. |
Where the figure can come from
NRCan’s sizing guide describes four starting points for the design heating load.
According to the guide, codes require it for new residential construction; it is also used for an existing house whose envelope has been extensively upgraded.
When the house has had an energy audit, the report contains a load estimate.
A model of the house, in HOT2000 for example, for the whole house or for one zone.
The guide presents it as a last resort.
Source: Natural Resources Canada, Air-Source Heat Pump Sizing and Selection Guide, version 1.0, step 3, options 3A to 3D.
The load line of the house, against the published capacity
The thermal balance point is the outdoor temperature where the load line of the house crosses the capacity of the heat pump. Above it, the heat pump is enough; below it, backup heating may have to make up the difference. Set the design heat loss, choose a size of the example, and read each published point.
What the heat pump has to cover: NRCan’s four approaches
Once the load is known, NRCan’s guide asks the designer to choose an approach. Each one aims at a different share of the heating and leaves more or less work to the backup.
Emphasis on cooling
The unit is selected for cooling and heats in mild weather. Target: a cooling capacity of 80 to 125% of the design cooling load.
Balanced heating and cooling
The unit covers most of the heating in mild weather, up to most of the season. Same cooling target: 80 to 125%.
Emphasis on heating
The unit covers most of the heating, from mild to cold weather. Target: a capacity at −8.3 °C equal to the design load × 43 ÷ (60 − design temperature in °F). With −23.1 °C (−9.6 °F): 0.62 times the design load.
Sized on the design heating load
The unit covers all of the season’s heating, or nearly. Target: the design load at the design temperature; with no backup, the capacity must exceed it.
Source: Natural Resources Canada, Air-Source Heat Pump Sizing and Selection Guide, version 1.0, step 4, options 4A to 4D. Diagrams: the line is the load of the house, the tinted area the share aimed at, the diamond the capacity target. Choosing the approach is part of the designer’s work.
What size changes at both ends of winter
A variable-speed heat pump modulates between a minimum capacity and a maximum capacity. NRCan’s guide calls the quotient of the two the turn-down ratio; it notes that a high ratio reduces cycling, and that cycling degrades performance and comfort.
More capacity than the load
In mild weather, the load of the house falls below the unit’s minimum capacity: it starts and stops instead of modulating.
Less capacity than the load
Below the balance point, the maximum capacity is no longer enough: the backup supplies the difference. The seventh step of the guide is to define that backup.
| ORION XLTH, by size | At 8.3 °C: min. / rated / max. | At −15 °C: min. / rated / max. |
|---|
Values of the AHRI certificate published by NEEP, in BTU/h, consulted November 9, 2026. Turn-down ratio: AirGreen calculation, maximum capacity ÷ minimum capacity at 8.3 °C. At −15 °C, the rated capacity and the maximum capacity of the certificate are the same for three of the five sizes.
What the professional does, in seven steps
NRCan’s guide is written for mechanical designers and renovation contractors. Its seven steps show where the load calculation sits, and everything that depends on it.
- Define the configurationCentral with ducts or wall-mounted without ducts, one zone or several.
- Choose the indoor unitFor a ductless system: the type of unit that suits each room.
- Determine the design loadsThe heat loss and heat gain of the house or of the zone: this is where the calculation is done.
- Choose the approach and the target capacityOne of the four approaches described above.
- Select the unitA model whose published capacities meet the target: NEEP’s list, the manufacturer’s tables.
- Define the control strategyHow the heat pump and the backup share the work.
- Define the backupThe heating that completes below the balance point.
Source: Natural Resources Canada, Air-Source Heat Pump Sizing and Selection Guide, version 1.0, December 21, 2020. The step headings follow the guide; the explanations are AirGreen’s.
What people ask us about size
Why not choose the size from the floor area?
Because floor area says nothing about insulation, windows, air leaks or climate. CSA F280-12 calculates heat losses from those inputs: two houses with the same floor area can end up with very different loads.
Who does the heat loss calculation?
A qualified professional. NRCan’s guide is written for mechanical designers and renovation contractors; it also accepts the report of an energy audit or a model of the house as a starting point. Ask the company proposing a unit which load the chosen size is based on.
What is the balance point?
The outdoor temperature where the load line of the house crosses the capacity curve of the heat pump. Above it, the heat pump covers the load; below it, a backup may have to make up the difference. On this page, it is given as an interval between two published points, with no interpolation.
Is a larger heat pump always a cautious choice?
Not necessarily. In mild weather, if the load falls below the unit’s minimum capacity, it cycles; NRCan’s guide notes that cycling degrades performance and comfort. In the example, the certified minimum capacity at 8.3 °C is 3,500 BTU/h for the 12,000 BTU size and 8,200 BTU/h for the 24,000 BTU size.
For a wall-mounted unit, is the whole house calculated?
NRCan’s guide speaks of a target zone: it takes the load of the rooms served from the calculation, the report or the model. Failing that, it prorates the calculated load of the house by the zone’s share of floor area, a method it presents as simplified. This is not a number of BTU per square foot: the starting point remains a calculated load.
What about cooling?
The standard also calculates summer heat gains. In approaches 4A and 4B of NRCan’s guide, the target cooling capacity is between 80 and 125% of the design cooling load.
My house was renovated: has the load changed?
Insulation, windows and airtightness go into the calculation; changing them changes the result. NRCan’s guide mentions the CSA F280 calculation for an existing house whose envelope has been extensively upgraded.
Is the chart on this page enough to choose a size?
No. It is an illustration: the design heat loss there is a figure you set. A sizing starts from the calculated load of your house or of the target zone, and from the manufacturer’s capacity tables.
The AHRI and NEEP values of the five sizes of the example
FUJITSU AIRSTAGE ORION XLTH, ASUH wall-mounted units with AOUH outdoor units of the KZAH series. Each bar runs from the minimum capacity to the maximum capacity of the certificate, on the same scale for all five.
Heating capacities in BTU/h, from minimum to maximum, at each temperature of the certificate. R-32 refrigerant: GWP 675 according to the IPCC (AR4), class A2L according to ASHRAE 34. The five sizes appear in the ENERGY STAR directory and on NEEP’s cold-climate list. Heating range stated by the manufacturer: −26 to 24 °C. Also sold under the GENERAL AIRSTAGE name.
The five sizes of the example are on AirGreen’s site.
Do you have an energy audit report or a heat loss calculation? Bring it, with the list of rooms to heat, and talk it over with our team.
Where each statement comes from
Data verified November 9, 2026. Capacities and efficiencies: AHRI certificates and NEEP database. Operating range and percentages in extreme cold: per the manufacturer. Standard and guide: official texts cited, which can change. This guide explains a method with the help of an example; it does not rank any unit and does not replace a load calculation done by a qualified professional.
Trademarks. FUJITSU AIRSTAGE, ORION XLTH and AIRSTAGE are trademarks of their respective owners. The logos are used only to identify the product shown. AirGreen is a retailer of the brand; this page is not produced, sponsored or approved by the manufacturer. FUJITSU AIRSTAGE systems are also sold under the GENERAL AIRSTAGE name.
Photos: AirGreen and manufacturer, for identification purposes. The houses and the charts are diagrams.
Does a figure look inaccurate? Write to us: every reported figure is checked again.