The outdoor unit: snow, wall bracket, base pan heater

A heat pump draws its heat from outside. So its outdoor unit has to breathe all winter: stay above the snow, keep free air around it and let the defrost water drain away. Installation manuals put figures on nearly all of it. This guide goes through them point by point, for two units sold by AirGreen.

Level with the expected snow, or higher Free air behind, in front and on the sides Defrost water freezes at 0 °C
FUJITSU AIRSTAGE ORION XLTH 12,000 BTU (AirGreen image)
ExampleFUJITSU AIRSTAGE

ORION XLTH · 12,000 BTU

Outdoor unit AOUH12KZAH1 · AHRI 214888802

See the product page
GREE EXTRÊME R32 12,000 BTU (AirGreen image)
ExampleGREE

EXTRÊME R32 · 12,000 BTU

Outdoor unit GWH12AVDXE-D6DNA1B/O · AHRI 215386290

See the product page
Cost per season

A unit that breathes poorly heats less well

FUJITSU AIRSTAGE writes that air inlets and outlets blocked by snow make heating difficult, and that insufficient clearance lowers performance. The base pan heater, for its part, uses electricity when it runs: each manufacturer declares its power to NEEP. This guide shows no dollar amount: the cost of a season is worked out unit by unit, from the certified HSPF2 Region V, and it appears on our comparison pages.

ORION XLTH FUJITSU AIRSTAGE150 WBase pan heater power declared to NEEP, record 392122
EXTRÊME R32 GREE72 WBase pan heater power declared to NEEP, record 389444

NEEP records read on November 10, 2026. These figures are for the heating element alone, when it is on; they do not say how many hours it runs in a winter.

Snow

How high the snow gets, and where the unit sits

Set the snow depth on the ground and the height of the support. Both units are drawn to scale, from their published dimensions. The three markers come from Environment and Climate Change Canada's climate normals for Montréal-Trudeau.

Outdoor unit AOUH12KZAH1 (photo) Outdoor unit GWH12AVDXE-D6DNA1B/O (photo)

Photo of the unit to scale; wall, support and snow drawn as a diagram. Dots on the ruler: Montréal-Trudeau markers.

Example shown
Type of support

Markers: average snow depth on the ground in February, 14 cm; greatest depth of the 1991-2020 period, 51 cm (March 24, 2001); station record, 102 cm (March 12, 1971). Canadian Climate Normals 1991-2020, Montréal-Trudeau station, climate ID 7025251. These measurements are taken on open ground: they do not account for snow that drifts, slides off a roof or is pushed by snow clearing. Unit dimensions: 632 mm high for the AOUH12KZAH1 (FUJITSU AIRSTAGE technical manual), 21 27/32 in for the GREE unit (EXTRÊME R32 brochure).

Clearances

Free air around the unit, with the manufacturer's figures

Each manual gives the distances to keep clear around the outdoor unit; here they are seen from above. FUJITSU AIRSTAGE warns that insufficient space can lower the unit's performance. Snow counts too: the same manual writes that air inlets and outlets blocked by snow hamper heating.

ORION XLTH FUJITSU AIRSTAGE

Obstacles behind and on the sides, open above

Outdoor unit installation manual, Part No. 9300793025-01, p. 7: 100 mm (4 in) behind, 100 mm (4 in) on one side, 250 mm (10 in) on the other, 600 mm (24 in) in front. Diagram.

EXTRÊME R32 GREE

Installation dimension diagram

Service manual “AIRY INVERTER SERIES_R32”, p. 53: 30 cm from the wall, 30 cm on one side, 50 cm on the other, 200 cm in front, 50 cm above; rounded to inches on the diagram.

The two manuals do not measure the same situations and are not a ranking: each applies to its own unit. The installer follows the manual of the unit being installed and local rules.

Water and the base pan heater

Defrost water leaves through the base of the unit

In heating mode, the outdoor unit releases water each time it defrosts. At 0 °C and below, that water can freeze where it falls. Both manufacturers declare a heating element in the base of the unit, the base pan heater. GREE publishes the temperatures that turn it on and off: move the slider to see them.

ORION XLTH FUJITSU AIRSTAGE

150 W base pan heater

Threshold not publishedControl declared to NEEP: by temperature and system mode
Power
150 W, declared to NEEP
Documents
NEEP record 392122; service manual parts list
EXTRÊME R32 GREE

72 W base pan heater

−10 °C0 °C2 °C6 °C
Power
72 W, declared to NEEP
Documents
Service manual, p. 41; NEEP record 389444

GREE, service manual, p. 41: the element heats at 0 °C and below, stops above 2 °C and keeps its state in between. GREE also declares to NEEP that it runs below 1 °C (33.8 °F) or during a defrost. Diagram.

Water runs under the unit

FUJITSU AIRSTAGE in heating mode, water drains from the outdoor unit; the manual asks for a spot where nothing gets in the way of that flow. GREE the water leaves through a hole in the base, where a drain joint fits.

Below 0 °C, that water freezes

FUJITSU AIRSTAGE the water can freeze and block the drain; measures must be taken to prevent it. GREE the drain joint would frost up in a severe cold area.

No drain hose in cold weather

FUJITSU AIRSTAGE at 0 °C and below, no drain pipe and no drain cap: the water would freeze in the pipe. GREE the manual rules out the drain joint in severe cold areas.

Room under the base

FUJITSU AIRSTAGE unit set high, and no support frame under the drain hole, where ice would build up. GREE at least 3 cm above the floor, for the joint.

No two units one above the other

FUJITSU AIRSTAGE where the water can freeze, ice from the upper unit can affect the lower one. GREE the manuals consulted do not describe it.

A support that holds

FUJITSU AIRSTAGE four M10 anchor bolts, on a solid base rather than on bare ground. GREE a support able to carry at least four times the unit's weight.

Sources: FUJITSU AIRSTAGE, installation manual 9300793025-01, pp. 7 and 8; GREE, service manual “AIRY INVERTER SERIES_R32”, p. 58.

The manuals, line by line

What each manufacturer asks for the outdoor unit

The requirements are summarized in our own words, with the manual page. When a manual says nothing, the cell says so: that does not mean the point is unimportant.

What the manual asksORION XLTHEXTRÊME R32
Snow
Height above the snowOn a raised support or a shelf, level with the snow depth expected for the region, or higherInstallation manual, p. 8Not described in the manuals consulted
Blowing snow and heavy snowfallA canopy or baffle where snow can block the air inlets and outlets; snow hoods and a wind fence where blowing snow is commonInstallation manual, p. 8Not described in the manuals consulted
The support
Support: what carries the unitA solid base, concrete blocks for example, rather than bare ground; 4 M10 anchor boltsInstallation manual, p. 8A support fixed with expansion screws, able to carry at least four times the unit's weightService manual, p. 58
Tilt of the unit3 degrees at mostInstallation manual, p. 7Not described in the manuals consulted
Strong windBolt the unit to its shelf or bracket, and reinforce the fastening where neededInstallation manual, p. 7A spot where the unit is not directly exposed to strong windService manual, p. 55
VibrationsDamping materials between the unit and its support, depending on installation conditionsInstallation manual, p. 8Not described in the manuals consulted
Clearances
Clearance behind100 mm (4 in)Installation manual, p. 730 cmService manual, p. 53
Clearance on the sides100 mm (4 in) on one side, 250 mm (10 in) on the otherInstallation manual, p. 730 cm on one side, 50 cm on the otherService manual, p. 53
Clearance in front600 mm (24 in)Installation manual, p. 7200 cmService manual, p. 53
Clearance aboveSeparate figures when an obstacle overhangs the unitInstallation manual, p. 750 cmService manual, p. 53
Defrost water
Defrost water: where it goesUnder the unit; choose a spot where the flow is not obstructedInstallation manual, p. 7Through a hole in the base, with a drain joint outside severe cold areasService manual, p. 58
Drain hose in cold weatherNo drain pipe and no drain cap at 0 °C and belowInstallation manual, p. 8No drain joint in severe cold areasService manual, p. 58
Space under the baseUnit installed high; no support frame under the drain holeInstallation manual, p. 7At least 3 cm above the floorService manual, p. 58
Outdoor unit base pan heaterYes; 150 W declared to NEEPNEEP record 392122; service manual parts listYes; 72 W declared to NEEP, on at 0 °C and belowService manual, p. 41; NEEP record 389444
The neighbourhood
NeighboursA spot where the discharged air, noise and vibrations do not bother the neighboursInstallation manual, p. 7A spot where the noise and discharged air do not disturb the neighbourhoodService manual, p. 55

FUJITSU AIRSTAGE: outdoor unit installation manual, Part No. 9300793025-01. GREE: service manual “AIRY INVERTER SERIES_R32”. Only the manufacturer's text is authoritative.

Frequently asked questions

The questions we get about the outdoor unit in winter

How high should the outdoor unit be installed?

FUJITSU AIRSTAGE asks for a raised support or a shelf, level with the snow depth expected for the region, or higher. At Montréal-Trudeau, the average snow depth on the ground in February is 14 cm; the greatest of the 1991-2020 period is 51 cm, and the station record is 102 cm. These measurements come from open ground: snow that drifts, slides off a roof or is pushed by snow clearing is not counted.

On the wall or on the ground?

The manuals accept both. FUJITSU AIRSTAGE mentions shelves, mounting brackets or a solid base such as concrete blocks, and asks for the unit to be bolted down. GREE asks for a support able to carry at least four times the unit's weight. FUJITSU AIRSTAGE adds that the unit can transmit vibrations depending on the installation, and suggests damping materials.

Should you clear the snow around the unit?

The FUJITSU AIRSTAGE manual treats snow as an obstacle: it writes that air inlets and outlets blocked by snow make heating difficult and may cause a failure. The distances to keep clear are in the section on clearances.

Why does ice form under the unit?

Defrost water leaves through the base. At 0 °C or below, it can freeze where it falls. FUJITSU AIRSTAGE asks for the unit to be installed high and for nothing to be placed under the drain hole, so that ice does not end up blocking it.

What is the base pan heater?

It is a heating element placed in the base of the outdoor unit, where the defrost water falls. Both manufacturers declare one to NEEP: 150 W for the ORION XLTH, 72 W for the EXTRÊME R32. GREE turns it on at 0 °C and below and during defrosts.

Can you connect a hose to send the water somewhere else?

Not in cold weather, according to both manuals. FUJITSU AIRSTAGE rules out the drain pipe and drain cap at 0 °C and below, because the water would freeze in the pipe. GREE rules out its drain joint in severe cold areas.

Is a canopy above the unit useful?

FUJITSU AIRSTAGE advises a canopy or a baffle where heavy snowfall can block the air inlets and outlets. An obstacle above the unit changes the clearances, though: the FUJITSU AIRSTAGE manual gives specific figures for that case, and GREE asks for 50 cm above.

Both examples are on the AirGreen site.

The location of the outdoor unit is chosen with the installer. To talk it over with our team, bring photos of the wall or the yard, and tell us how high the snow gets at your place.