vänEE V160H75RT and V160E75RT, HRV or ERV

Home / Comparisons / Air exchangers

Comparison · HRV or ERV · vänEE, 160 CFM

HRV or ERV: the vänEE V160H75RT and the V160E75RT, one core apart

Same brand, same 21 × 21.5 in. cabinet, same power supply. The V160H75RT is an HRV: its core recovers heat. The V160E75RT is an ERV: its membrane core recovers heat and part of the moisture. Here is what that core changes in the HVI directory and spec sheet figures, winter and summer.

At −25 °C and 66 CFM: 67% and 63% (HVI) Moisture recovered at 0 °C: ERV 0.68, per its spec sheet Airflow at 0.4 in. w.c.: 150 and 133 CFM
vänEE V160H75RT, HRV (AirGreen image)
vänEE · HRV

V160H75RT

Heat recovery ventilator · HVI 2505306

Spec sheet 1109196G

See the product page
vänEE V160E75RT, ERV (AirGreen image)
vänEE · ERV

V160E75RT

Energy recovery ventilator · HVI 2005455

Spec sheet 1109194J

See the product page
Estimated operating cost

What the fans cost, in dollars per year

Same cabinet, same motors: both use almost the same power. At the closest HVI test point, 64 CFM for the HRV and 66 CFM for the ERV at 0 °C, the directory publishes 28 W and 33 W.

Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the HVI directory watts at 0 °C: 28 W at 64 CFM for the V160H75RT (listing 2505306), 33 W at 66 CFM for the V160E75RT (listing 2005455). The test airflows differ by 2 CFM.
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

This calculation counts only the electricity used by the fans. It does not count heating the fresh air, nor the effect of the moisture the ERV keeps or rejects, which the documents do not express in dollars.

AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.

The core in cross-section

Heat only, or heat and moisture

In the core, two airstreams pass on either side of thin walls without mixing. In the HRV, the wall lets heat through. In the ERV, a polymer membrane also lets part of the water vapour through. Pick the season to see which way it travels.

V160H75RT · HRVdiagram · polypropylene wall
V160E75RT · ERVdiagram · polymer membrane

Winter in Québec

Cold outdoor air holds little water. The ERV sends part of it back into the house, per its spec sheet (ratio of 0.68 at 0 °C and 66 CFM). The HRV renews the air without keeping its moisture.

An airtight house

The less air a house leaks, the more the mechanical ventilation does the work. The HRV or ERV choice is made based on the humidity measured in the house, which the estimator checks on site.

Summer

The HVI directory publishes the ERV’s total efficiency in cooling, at 35 °C. The HRV is not tested under these conditions; its summer figures are not published.

Extreme cold

At −25 °C, the same test airflow for both

The HVI directory tests both at 66 CFM at −25 °C. Under these identical conditions, the HRV recovers 67% of the sensible heat with 43 W; the ERV, 63% with 72 W. At 0 °C, their test airflows differ by 2 CFM.

−25 °C−13 °FSame temperature and same airflow
67%V160H75RT · 66 CFM · 43 W · adjusted SRE 69%
63%V160E75RT · 66 CFM · 72 W · adjusted SRE 66% · moisture recovered 0.63 (spec sheet)
0 °C32 °FSame temperature, different airflows
77%V160H75RT · 64 CFM · 28 W · adjusted SRE 80%
78%V160E75RT · 66 CFM · 33 W · adjusted SRE 81% · moisture recovered 0.68 (spec sheet)

V160H75RT defrost

Recirculation (Homeshield), from −5 °C, per spec sheet 1109196G.

V160E75RT defrost

Recirculation (Homeshield), from −5 °C, plus 10 minutes every 5 cycles, per spec sheet 1109194J.

Bars from 0 to 100% sensible recovery. Source: HVI directory, section III, data as of November 4, 2026. The moisture recovery ratio comes from V160E75RT spec sheet 1109194J; it is not presented on this page as an HVI value.

Summer

In cooling, only the ERV has published figures

In summer, outdoor air is hot and humid. The HVI directory publishes the total recovery efficiency (TRE) of the V160E75RT at 35 °C: heat and moisture together. The V160H75RT has no cooling test in the directory; we do not assign it any figure.

V160E75RT at 36 CFM · 21 W
69%
TRE · adjusted 72% · moisture 0.77 (spec sheet)
V160E75RT at 66 CFM · 36 W
64%
TRE · adjusted 66% · moisture 0.69 (spec sheet)
V160E75RT at 125 CFM · 112 W
52%
TRE · adjusted 56% · moisture 0.60 (spec sheet)
total efficiency, HVI directory moisture recovery ratio, spec sheet 1109194JV160H75RT: no published cooling test
Airflow

The membrane core slows the air a little more

With the same cabinet and the same motors, the ERV delivers less air at every static pressure per the HVI directory: 133 CFM at 0.4 in. w.c. versus 150 for the HRV. The ERV spec sheet gives an adjustable range of 35 to 140 CFM; the HRV’s, 35 to 160.

V160H75RT · HRV HVI 2505306V160E75RT · ERV HVI 2005455The gap between the curves is shown at each point.
Installation

Same cabinet; the drain makes the difference

Both measure 21 × 16.13 × 21.5 in., with 6 in. ports on top. Per the spec sheets, the HRV has a snap-in drain with hose supplied; the ERV needs no drain. The ERV weighs 2 lb more.

V160H75RT · HRV21 × 16.13 × 21.5 in. · 35 lb
vänEE V160H75RT
V160E75RT · ERV21 × 16.13 × 21.5 in. · 37 lb
vänEE V160E75RT

Manufacturer photos and front outlines to the same scale (diagram). The two outlines are identical.

Installation, per the manufacturerV160H75RT · HRVV160E75RT · ERV
Duct portsround6 in., on top6 in., on top
Dimensions W × D × H21 × 16.13 × 21.5 in.21 × 16.13 × 21.5 in.
Unit weight35 lb37 lb
Power supply120 V, 60 Hz, 2.4 A, 163 W120 V, 60 Hz, 2.4 A, 163 W
DrainYes, snap-in drain, hose suppliedNo drain required, per the spec sheet
CorePolypropylene, cross-flowCross-flow polypropylene with polymer membrane and aluminum covers; not washable
Adjustable airflow range35 to 160 CFM35 to 140 CFM, at 0.2 in. w.c.
Factory filterWashable MERV 8MERV 13 and HEPA optionalWashable MERV 8MERV 13 optional
Fan motorPMSM ECMPMSM ECM
Motorized dampersYes, no backdraft dampers to addYes, no backdraft dampers to add
Questions

What people ask about the HRV and the ERV

What is the difference between an HRV and an ERV?

Both renew the air and recover heat. The ERV (V160E75RT) has a membrane core that also transfers part of the moisture, per its spec sheet. The HRV core (V160H75RT) is built for heat; its spec sheet publishes no moisture transfer.

Which one recovers more heat in extreme cold?

At −25 °C and 66 CFM, same conditions for both, the HVI directory publishes 67% for the HRV and 63% for the ERV. The ERV draws 72 W at that point, the HRV 43 W.

Is the ERV better suited to a house where the air is dry in winter?

The ERV returns part of the outgoing air’s moisture to the fresh air, per its spec sheet (ratio of 0.68 at 0 °C). Whether that helps in your house depends on its actual humidity, its airtightness and the number of occupants; the estimator measures these conditions on site.

Why does the ERV not need a drain?

Its spec sheet states that no drain is required. The HRV’s calls for a snap-in drain with hose supplied. The technical reason is not explained in the spec sheets.

Can both cores be washed the same way?

The ERV spec sheet specifies that its core is not washable. Follow the maintenance guide for the model installed; it comes with the unit.

What about noise and warranty?

The spec sheets consulted publish no sound level, and this page does not compare warranties. The warranty documents for the unit chosen come with the quote.

All values

Every HVI directory test point

HVI directory, section III, data as of November 4, 2026, except the moisture ratios, taken from spec sheet 1109194J.

MeasurementV160H75RT · HRVV160E75RT · ERV
Recovery at −25 °C, same test airflow
Test airflownet fresh air66 CFM (31 L/s)66 CFM (31 L/s)
Sensible recovery efficiency (SRE)67%63%
Adjusted sensible recovery efficiency (ASRE)69%66%
Power draw43 W72 W
Recovery at 0 °C, close airflows
Low test airflownet fresh air64 CFM, 28 W66 CFM, 33 Walso 36 CFM, 18 W
Sensible recovery efficiency (SRE)77%adjusted 80%78%adjusted 81%; 81% at 36 CFM
High test airflownet fresh air129 CFM, 100 W125 CFM, 108 W
Sensible recovery efficiency (SRE) at high airflow66%adjusted 71%72%adjusted 78%
Cooling, 35 °C
Total recovery efficiency (TRE) at 66 CFMNo cooling test in the HVI directory64%adjusted 66%, 36 W
Net airflow delivered, same static pressure
Airflow at 0.1 in. w.c. (25 Pa)163 CFM144 CFM
Airflow at 0.4 in. w.c. (100 Pa)150 CFM133 CFM
Airflow at 1.0 in. w.c. (250 Pa)114 CFM104 CFM
Moisture, per the manufacturer spec sheet
Moisture transfer, heating 0 °CNot published by the manufacturer0.74 at 36 · 0.68 at 66 · 0.59 at 125 CFM
Moisture transfer, cooling 35 °CNot published by the manufacturer0.77 at 36 · 0.69 at 66 · 0.60 at 125 CFM
Certification
HVI directory, section IIIYes, listing 2505306Yes, listing 2005455
ENERGY STARSpec sheet: yes, Canada onlybroan-nutone.com page: noSpec sheet: yes, Canada onlybroan-nutone.com page: no

“Higher” marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Rows at 0 °C are not marked: the test airflows differ.

Both are on the AirGreen website.

HRV or ERV is decided by the actual humidity in your house. Talk to our team.

Sources and documents

Where every figure comes from

HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2505306 and 2005455 · consulted November 9, 2026
vänEE V160H75RT / V160H75RS spec sheetBroan-NuTone LLC / Venmar Ventilation ULC, performance sheet 1109196G, undated · consulted November 5, 2026
vänEE V160E75RT spec sheet“Energy Recovery Ventilator – 140 CFM”, document 1109194J, undated · moisture ratios, drain, core · consulted November 5, 2026
broan-nutone.com product pagesV160H75RT and V160E75RT · ENERGY STAR: no · consulted November 5 and 9, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan cost