LIFEBREATH 155 MAX and vänEE V160H75RT, HRV air exchangers

Home / Comparisons / Air exchangers

Comparison · HRV air exchanger · about 150 CFM

LIFEBREATH 155 MAX and vänEE V160H75RT, spec sheet against spec sheet

Two HRVs listed in the HVI directory, tested at the same airflow of 64 CFM at 0 °C. One has a counterflow core and a PSC motor, the other a cross-flow core and ECM motors. Here is what their certified figures say, test point by test point, and what they do not say.

At 0 °C and 64 CFM: 75% and 77% Power at the same point: 72 W and 28 W At −25 °C: 70% and 67%, test airflows of 68 and 66 CFM
LIFEBREATH 155 MAX (AirGreen image)
LIFEBREATH

155 MAX

Horizontal HRV · HVI 2505085

Spec sheet 155 MAX 2019*, code 0726

See the product page
vänEE V160H75RT (AirGreen image)
vänEE

V160H75RT

Vertical HRV, top ports · HVI 2505306

Spec sheet 1109196G · also listed as BROAN-NUTONE V160H75RS (side ports)

See the product page
Estimated operating cost

What the fans cost, in dollars per year

Both units were tested at the same airflow, 64 CFM at 0 °C. At that point, the HVI directory publishes 72 W for the 155 MAX and 28 W for the V160H75RT. Here is what that difference in watts means on a Hydro-Québec bill when the exchanger runs day and night.

Price per kWh (Rate D, April 1, 2026)
How this amount is calculated
  1. Power: the HVI directory watts at the same test point, 64 CFM at 0 °C: 72 W for the LIFEBREATH 155 MAX (listing 2505085), 28 W for the vänEE V160H75RT (listing 2505306).
  2. Energy: watts × hours per day × 365 days ÷ 1,000 = kWh per year.
  3. Price: Hydro-Québec Rate D in effect April 1, 2026 (7.065¢ up to 40 kWh a day, 11.142¢ above, 9.104¢ on average), multiplied by 1.14975 for GST and QST. The system access charge is not counted.

This calculation counts only the electricity used by the fans at this airflow. A unit set higher uses more, and the HVI directory publishes only one test airflow common to both. Heating the incoming fresh air is not counted.

AirGreen method v1.1, ventilation, November 9, 2026. An estimate is for comparing units under the same conditions. The actual bill depends on the house, the settings and how the unit is used; this amount is not a promise.

Two cores

Counterflow or cross-flow: what the air passes through

In the 155 MAX, the outgoing and incoming air run along the same plates in opposite directions (counterflow core, per the Lifebreath spec sheet). In the V160H75RT, they cross at right angles (cross-flow, per spec sheet 1109196G). Pick the temperature: the animation shows each unit’s certified efficiency and what it would mean for the fresh air in a house at 21 °C.

LIFEBREATH 155 MAXdiagram · counterflow core
75%SRE · 64 CFM · 72 WHVI certified

vänEE V160H75RTdiagram · cross-flow core
77%SRE · 64 CFM · 28 WHVI certified

Extreme cold

At 0 °C, same conditions; at −25 °C, almost

The HVI directory publishes two test temperatures for each. At 0 °C, both were measured at the same airflow, 64 CFM: the comparison is direct. At −25 °C, the test airflows differ by 2 CFM (68 and 66) and power jumps; we say so rather than lining the figures up as if they were identical.

0 °C32 °FSame temperature and same airflow
75%LIFEBREATH 155 MAX · 64 CFM · 72 W · adjusted SRE 82%
77%vänEE V160H75RT · 64 CFM · 28 W · adjusted SRE 80%
−25 °C−13 °FSame temperature, different airflows
70%LIFEBREATH 155 MAX · 68 CFM · 92 W · adjusted SRE 73%
67%vänEE V160H75RT · 66 CFM · 43 W · adjusted SRE 69%

Bars run from 0 to 100% sensible recovery. Source: HVI directory, section III, data as of November 4, 2026. The V160H75RT is also tested at 129 CFM at 0 °C (66%, 100 W); the 155 MAX has no test point at that airflow in the directory.

LIFEBREATH 155 MAX defrost

Recirculating damper (“intelligent recirculating damper defrost”), per spec sheet 0726. The MAX series installation guide (69-MAX-INSTALL 10-19) sets the defrost mode with DIP switches; neither the spec sheet nor the guide gives the trigger temperature.

vänEE V160H75RT defrost

Recirculation (Homeshield), from −5 °C, per spec sheet 1109196G. The fresh-air intake closes and house air circulates through the core to clear the frost.

Airflow

The more the ducts resist, the further the curves part

External static pressure, in inches of water column (in. w.c.), measures duct resistance. At 0.2 in., both deliver 159 CFM of fresh air. Beyond that, the 155 MAX curve drops faster. The HVI directory publishes the 155 MAX up to 0.5 in. and the V160H75RT up to 1.0 in.

LIFEBREATH 155 MAX HVI 2505085vänEE V160H75RT HVI 2505306Hatched area: beyond the last published point of the 155 MAX (123 CFM at 0.5 in.).
Features

Two ways to build an HRV

What each spec sheet names, side by side. The tags show which spec sheet documents it.

Airflow balancing

155 MAX : balancing dampers and measuring ports on the door, adjusted by hand. V160H75RT : automatic balancing and constant airflow (Virtuo Air).

spec sheet 0726spec sheet 1109196G
Motor and fans

155 MAX : one PSC motor shared by both centrifugal blowers, several speeds, high speed set by DIP switches. V160H75RT : PMSM ECM motors.

spec sheet 0726spec sheet 1109196G
Recovery core

155 MAX : hexagonal counterflow core, heat conducting, removable for cleaning. V160H75RT : impact-resistant cross-flow polypropylene.

spec sheet 0726spec sheet 1109196G
Factory filters

155 MAX : washable MERV 6 in both airstreams, MERV 13 available (65-195-6R). V160H75RT : washable MERV 8, MERV 13 and HEPA optional.

spec sheet 0726spec sheet 1109196G
Wall control

155 MAX : DXPL03 digital control included, to be mounted centrally in the house, 3-conductor wire up to 100 ft. V160H75RT : settings on the unit’s screen; wall controls sold separately per the spec sheet.

spec sheet 0726spec sheet 1109196G
Defrost

155 MAX : recirculating damper. V160H75RT : Homeshield recirculation from −5 °C.

spec sheet 0726spec sheet 1109196G
Installation

A long, low cabinet and an almost cubic one

The 155 MAX is 33.63 in. long and 18.68 in. high; the V160H75RT, 21 in. by 21.5 in. The first hangs horizontally from four straps and S-hooks supplied; the second weighs half as much.

LIFEBREATH 155 MAX33.63 × 14.75 × 18.68 in. (W × D × H) · 71 lb
LIFEBREATH 155 MAX
vänEE V160H75RT21 × 16.13 × 21.5 in. (W × D × H) · 35 lb
vänEE V160H75RT

Left, the manufacturer photo, in perspective. Right, the outline of the front, width × height, drawn to the same scale for both (diagram). Dimensions and weight per the spec sheets.

The four ports of the 155 MAX

fresh air to the housestale air from the housefresh air from outdoorsstale air to outdoorsdiagram · 6 in. round collars

6 in. round collars and balancing dampers on the door, per spec sheet 0726. The manufacturer photo shows ports on top and at the ends; their exact assignment is on the installation drawing in guide 69-MAX-INSTALL, which the installer follows.

The four ports of the V160H75RT

four ports on topdiagram · 6 in. round ports

6 in. round ports on top (the V160H75RS has them on the side), per spec sheet 1109196G. Built-in motorized dampers: the spec sheet states no backdraft dampers need to be added.

Installation, per the manufacturerLIFEBREATH 155 MAXvänEE V160H75RT
Duct portsround6 in., round collars6 in., on top
Dimensions W × D × H33.63 × 14.75 × 18.68 in.21 × 16.13 × 21.5 in.
Unit weight71 lb35 lb
Power supply120 V, 60 Hz, 2.2 A15 A max. protection120 V, 60 Hz, 2.4 A, 163 W
DrainYes, 1/2 in. (12 mm) drain fittingsYes, snap-in drain, hose supplied
Factory filterWashable MERV 6MERV 13 availableWashable MERV 8MERV 13 and HEPA optional
CoreCounterflow, hexagonal, removablePolypropylene, cross-flow
Fan motorPSC, one motor for both blowersPMSM ECM
CabinetPre-painted galvanized steel, 22 gauge, insulatedGalvanized steel
Questions

What people ask about these two air exchangers

Which one recovers more heat?

It depends on the test temperature. At 0 °C and 64 CFM, same conditions for both, the HVI directory publishes 77% for the V160H75RT and 75% for the 155 MAX. At −25 °C, it publishes 70% for the 155 MAX at 68 CFM and 67% for the V160H75RT at 66 CFM. The test airflows are not identical at that temperature.

Why is the 155 MAX’s adjusted SRE higher than the V160H75RT’s at 0 °C, when its SRE is lower?

SRE and adjusted SRE are two ways of calculating recovery, defined by CSA C439. The HVI directory publishes 75% and 82% for the 155 MAX, 77% and 80% for the V160H75RT. We show them as published; neither one sums up the unit on its own.

72 W versus 28 W: is that a big difference on the bill?

At 64 CFM, around the clock, at the average Rate D price with taxes, the estimate comes to about $66 a year for the 155 MAX and $26 for the V160H75RT. The calculation is detailed in the cost section; it counts only the fans.

What does “2019*” mean in the 155 MAX name?

According to the Lifebreath spec sheet, the asterisk and “2019” refer to the year of ENERGY STAR certification, not the year of manufacture. The spec sheet states the unit is ENERGY STAR certified for use in Canada only.

Which one takes less space?

It depends on the shape of the space. The 155 MAX is long and low (33.63 in. × 18.68 in. front); it hangs horizontally. The V160H75RT is narrower (21 in.) but taller (21.5 in.), with its ports on top. The 155 MAX weighs 71 lb, the V160H75RT 35 lb.

What about noise and warranty?

The spec sheets consulted publish no sound level for these two models, and this page does not compare warranties. The warranty documents for the unit chosen come with the quote.

All values

Every HVI certified value, side by side

Both columns come from the HVI directory, section III, data as of November 4, 2026. Dimensions and weight come from the spec sheets.

MeasurementLIFEBREATH 155 MAXvänEE V160H75RT
Recovery at 0 °C, same test airflow
Test airflownet fresh air64 CFM (30 L/s)64 CFM (30 L/s)
Sensible recovery efficiency (SRE)75%77%
Adjusted sensible recovery efficiency (ASRE)82%80%
Power draw72 W28 W
Recovery at −25 °C, different test airflows
Test airflownet fresh air68 CFM (32 L/s)66 CFM (31 L/s)
Sensible recovery efficiency (SRE)70%67%
Adjusted sensible recovery efficiency (ASRE)73%69%
Power draw92 W43 W
Net airflow delivered, same static pressure
Airflow at 0.1 in. w.c. (25 Pa)170 CFM163 CFM
Airflow at 0.2 in. w.c. (50 Pa)159 CFM159 CFM
Airflow at 0.3 in. w.c. (75 Pa)148 CFM155 CFM
Airflow at 0.4 in. w.c. (100 Pa)138 CFM150 CFM
Airflow at 0.5 in. w.c. (125 Pa)123 CFM144 CFM
Airflow from 0.6 to 1.0 in. w.c.Last published point: 123 CFM at 0.5 in.140, 133, 127, 121 and 114 CFM
Certification
HVI directory, section IIIYes, listing 2505085Yes, listing 2505306
ENERGY STARSpec sheet: yes, Canada onlySpec sheet: yes, Canada onlybroan-nutone.com page: no

“Higher” marks the higher value of the same measurement, under the same conditions. It is not a recommendation. Rows at −25 °C are not marked: the test airflows differ.

Both are on the AirGreen website.

To choose for your house, talk to our team: the space available, the duct lengths and the number of rooms matter as much as the figures.

Sources and documents

Where every figure comes from

HVI, Certified Products Directory, section IIIPublication 911, data as of November 4, 2026 · listings 2505085 and 2505306 · consulted November 9, 2026
LIFEBREATH 155 MAX 2019* spec sheetCode 0726, lifebreath.com (100-155-MAX-Spec, 2025) · consulted November 9, 2026
LIFEBREATH, MAX series installation guide69-MAX-INSTALL 10-19 · defrost DIP switches, drain, suspension · consulted November 9, 2026
vänEE V160H75RT / V160H75RS spec sheetBroan-NuTone LLC / Venmar Ventilation ULC, performance sheet 1109196G, undated · consulted November 5, 2026
V160H75RT product page, broan-nutone.comENERGY STAR: no · consulted November 9, 2026
Hydro-Québec, Electricity RatesIn effect April 1, 2026 · Rate D, section 2.5 · fan cost