Is it the right size for your home?
It delivers 78 cfm net, enough to ventilate 800 to 1,400 sq ft. Choose your home's living area.
It's the right size.
For a 900 to 1,500 sq ft home, about 63 cfm of air needs to be renewed continuously. This unit delivers 78 cfm net — enough for the house, with extra capacity to boost ventilation for the bathroom and kitchen.
Calculation: 0.35 air changes per hour over the living volume, with 9 ft ceilings. Our estimator sets the exact airflow room by room, following CSA F326.
What it does, in numbers
$40.99
Electricity per year
Less than a 60 W light bulb
Bulbs left on day and night. Same calculation for every line: wattage × 8,760 h × 11.142 ¢/kWh.
Meets the Québec Construction Code for Greater Montréal. The Code requires 54% at −25 °C below 6,000 degree-days (Montréal, Laval, Longueuil and both shores) and 60% above that. This unit is rated at 55% at 53 cfm.
Airflow and efficiency at 0 °C and −25 °C: HVI directory, Section III. Cost: 42 W over 8,760 h at Hydro-Québec's Rate D second tier (11.142 ¢/kWh).
What you should know about this one
Published, verifiable facts, not brochure claims.
-DBuilt-in motorized outdoor air damper
The -D suffix means the FIT 80E-D-HC has a built-in motorized damper. When the unit is tied to a furnace return, it can block the unconditioned outdoor air the blower would otherwise pull in while the unit is off, which Fantech recommends for that type of installation. The damper brings the width to 21 7/8 in, versus 21 5/8 in for the FIT 80E-HC.
-HCHard-connect version shipped without a cord
The -HC (hard connect) suffix means the unit ships with no power cord and is wired directly to the circuit where code requires it. On the FIT 80E-D-HC, the supply wires enter the electrical box through a 3/8 in cable fastener and connect to the unit's leads and ground screw.
55%What it still recovers at −25 °C
The only efficiency figure that matters for a Québec winter, and the one the Code uses. An efficiency quoted without its temperature means nothing; this one is measured at a test airflow of 53 cfm.
ExhaustIt defrosts by pausing the fresh air for a few minutes
In cold weather, the supply fan stops for a few minutes while the exhaust keeps running, so warm indoor air thaws the core. During the cycle the house is briefly under negative pressure; if you have a fireplace or a naturally vented combustion appliance, mention it to our estimator.
ERVIt moves moisture too, not just heat
An ERV transfers some moisture between the two airstreams. Useful in a house that gets too dry in winter or takes on a lot of humidity in summer. The trade-off: it generally recovers less heat than a comparable HRV.
2005306Its HVI certification number
Listed in Section III of the Home Ventilating Institute's certified products directory. Anyone can check it, and it's the first condition for the Rénoclimat grant.
−15 cfmWhat the ducts cost it
Between a nearly unrestricted test bench (0.2 in) and a real duct system (0.4 in), it drops from 93 to 78 cfm. Most spec sheets show only the first number, precisely because it looks better.
42 WMeasured at the airflow it actually runs at
Its 70% at 0 °C is certified at 42 cfm, the continuous airflow of a typical home. At that setting it draws 42 W, or about 368 kWh a year.
5 yearsThe core warranty
The core does the work and is the most expensive part to replace. Motors: 7 years. Parts: 5 years. We register the warranty in your name at commissioning.
4 inWhat it needs on site
4 in ducts, side connection. It weighs 30 lb, and it needs enough clearance to slide the core out once a year.
Rénoclimat: $500 to install or replace an HRV or ERV
First condition met: HVI Section III certified, No. 2005306. Second: your EnerGuide rating must improve between the two evaluations. Québec warns that an air exchanger installed on its own can increase a home's energy use; that's why we balance it to the calculated airflow rather than running it at full speed.
What it needs on site
In a condo with no floor drain, or with little ceiling clearance, we usually look at a side-port model instead. Our estimator checks the location, the drain and the duct route before ordering.
Complete spec sheetData and cited sources
- Net airflow at 0.2 in. w.g.
- 93 cfm
- Net airflow at 0.4 in. w.g.
- 78 cfm
- SRE at 0 °C (42 cfm)
- 70%
- SRE at −25 °C (53 cfm)
- 55%
- ASE at 0 °C
- 75%
- Power draw
- 42 W
- Efficacy
- 1.0 cfm/W
- Type
- ERV
- Connection
- Side ports
- Duct collars
- 4 in
- Defrost cycle
- Exhaust only (supply fan off)
- Filters
- 2 washable electrostatic MERV 3 panel filters (9 1/2 × 8 1/2 in); optional MERV 8 (484397) and MERV 13 (484396)
- Dimensions (L × D × H)
- 20.63 × 18.19 × 10.06 in
- Weight
- 30 lb
- Power supply
- 120 V
- HVI certification (Section III)
- 2005306
- Warranty — core
- 5 years
- Warranty — motors
- 7 years
- Warranty — parts
- 5 years
- Spec sheet (French)
- Spec sheet (English)
Net airflow, efficiency at 0 °C and −25 °C, and power draw: Home Ventilating Institute certified products directory, Section III (HVID 2005306). Annual consumption calculated at 42 W running continuously for 8,760 h, at Hydro-Québec's Rate D second tier (11.142 ¢/kWh), in effect since April 1, 2026.
The next model down and up
Talk to an HVAC technician before you choose
We calculate the airflow room by room, check the location and the drain, and give you an installed price. Balancing is measured at commissioning, not estimated.
Pour une unité à air pulsé où le code impose un câblage fixe
Le Fantech FIT 80E-D-HC s'adresse aux chantiers qui cumulent deux exigences : un échangeur d'air raccordé au retour de la fournaise, et une alimentation électrique permanente, sans cordon ni prise. Le volet motorisé (-D) protège le réseau contre l'air extérieur non traité; la version -HC arrive sans cordon, prête à être branchée au circuit.
C'est un ventilateur récupérateur d'énergie (VRE) de la série FIT 80 : débit net de 78 pcm à 0,4 po, plage de 20 à 78 pcm, raccords latéraux de 4 po et un poids de 30 lb seulement. Son boîtier de 10,06 po d'épaisseur se loge au plafond d'un placard ou d'une salle mécanique.
Le volet, côté air extérieur
Fantech l'explique dans son manuel : lorsque l'appareil est éteint, aucun air vicié ne le traverse, mais la soufflerie de la fournaise continue d'aspirer de l'air extérieur par son conduit. Cet air froid entre alors dans la maison sans avoir été tempéré, et la charge du système augmente. Le volet du FIT 80E-D-HC se ferme à l'arrêt et coupe ce chemin. Avec lui, la largeur passe de 21 5/8 po à 21 7/8 po.
Le branchement fixe
Les fils d'alimentation entrent dans le boîtier électrique par un serre-câble de 3/8 po et se relient aux fils et à la vis de mise à la terre de l'appareil. Il faut prévoir 2 3/8 po libres au-dessus du boîtier. Côté basse tension, le bornier reçoit la commande murale, les minuteries de salle de bain et le relais d'asservissement de la fournaise (NO, C, NC).
Efficacité mesurée
Les données HVI : 70 % d'efficacité de récupération sensible à 0 °C et 42 pcm, 75 % ajustée, 55 % à −25 °C et 53 pcm. Ce dernier chiffre respecte le seuil de 54 % de la section 9.32 du Code applicable au Grand Montréal. En été, à 35 °C, la récupération totale est de 50 %. Consommation : 42 W au débit d'essai, 52 W en haute vitesse, pour un courant maximal de 0,6 A.
Dimensions et dégagements
- 20,63 × 18,19 × 10,06 po.
- 8 1/2 po devant la porte pour retirer le noyau.
- Pas de drain à raccorder.
- Support de montage inclus, au plafond ou au mur.
Fantech recommande de placer l'appareil dans une salle mécanique, près d'un mur extérieur, dans un espace qui reste au-dessus de 10 °C, et loin des pièces principales de la maison.
Équilibrage avec la fournaise en marche
Un VRE relié au plénum de retour doit être équilibré dans les conditions réelles. Fantech demande de faire la procédure avec la soufflerie en marche et l'appareil en haute vitesse. On mesure d'abord le débit du côté de l'air vicié, puis du côté de l'air neuf, avec une commande murale Fantech programmable à écran tactile et un manomètre. Chaque pression sur la commande modifie la vitesse d'un ventilateur de 1 %. Les vitesses basse et moyenne suivent le réglage de la vitesse maximale. Nous inscrivons ensuite la pression mesurée et les deux débits au rapport de mise en service.
Prise d'air et sortie d'air vicié
L'air neuf est pris à au moins 18 po au-dessus du sol ou de la neige accumulée, à 3 pi ou plus d'un coin de mur, et loin d'une sortie de sécheuse ou de l'évacuation d'une fournaise à haut rendement. La sortie d'air vicié respecte les mêmes distances et doit éviter un compteur ou un trottoir, où le givre pourrait bloquer le passage. Ni l'une ni l'autre ne se place dans un garage.
Filtration
Filtres fournis : deux électrostatiques lavables MERV 3, format 9 1/2 × 8 1/2 po. Filtres optionnels : MERV 8 (484397) ou MERV 13 (484396). Le noyau à membrane se lave à l'eau, lui aussi.
Garantie du fabricant
Fantech : 7 ans sur les moteurs; 5 ans sur le noyau, les composants électriques et le moteur du volet. Les pièces de rechange se trouvent sur le portail Fantech, accessible par le code imprimé sur la plaque signalétique.
AirGreen, de la conception à la mise en service
Pour un projet à Montréal, à Laval, à Longueuil, sur la Rive-Nord ou sur la Rive-Sud, nous établissons les débits requis pièce par pièce selon la norme CSA F326. Nous coordonnons le circuit avec votre électricien, nous raccordons le VRE au plénum de retour et nous équilibrons l'alimentation et l'évacuation au manomètre, jusqu'au débit calculé.
Homologué à la section III du répertoire HVI sous le no 2005306, le FIT 80E-D-HC est admissible à l'aide Rénoclimat de 500 $ si la cote ÉnerGuide s'améliore entre les deux évaluations; l'évaluation doit être faite avant le début des travaux.
Soumission gratuite : 514 316-2973, sales@airgreen.ca.