Lifebreath METRO 120D-ECM HRV Air Exchanger | Montreal, Laval, Longueuil, South Shore and North Shore
Is it the right size for your home?
It delivers 114 cfm net, enough to ventilate 1,300 to 2,100 sq ft. Choose your home's living area.
It's the right size.
For a 1,500 to 2,500 sq ft home, about 105 cfm of air needs to be renewed continuously. This unit delivers 114 cfm net — enough for the house, with extra capacity to boost ventilation for the bathroom and kitchen.
Calculation: 0.35 air changes per hour over the living volume, with 9 ft ceilings. We set the exact airflow during our on-site assessment.
What it does, in numbers
$21.47
Electricity per year
Less than a 60 W light bulb
Bulbs left on day and night. Same calculation for every line: wattage × 8,760 h × 11.142 ¢/kWh.
Meets the Code's 55% threshold; below the 60% it requires where there are 6,000 degree-days or more. At −25 °C and at least 22 L/s, the Code (art. 9.36.3.9, in force since April 17, 2025) requires 55% where there are fewer than 6,000 heating degree-days and 60% elsewhere. This unit is rated at 59% at 55 cfm (HVI).
Airflow and efficiency at 0 °C and −25 °C: HVI directory, Section III. Cost: 22 W over 8,760 h at Hydro-Québec's Rate D second tier (11.142 ¢/kWh).
What you should know about this one
Published, verifiable facts, not brochure claims.
ECMIndependent ECM blower on each airstream
Each airstream has its own high-efficiency ECM centrifugal blower with multiple speeds. That is what the “-ECM” suffix of this METRO 120D version refers to.
50–130 cfmOperating range of 50 to 130 cfm
Lifebreath lists an operating range of 50 to 130 cfm. High speed is selected with DIP switches, under the swing-open e-box cover.
59%What it still recovers at −25 °C
The only efficiency figure that matters for a Québec winter, and the one the Code uses. An efficiency quoted without its temperature means nothing; this one is measured at a test airflow of 55 cfm.
DamperIt defrosts with indoor air
In cold weather, a motorized damper closes the outdoor air intake and recirculates indoor air through the core to thaw it. During the cycle, no outdoor air comes in through the unit.
HRVIt recovers heat, not moisture
Excess moisture leaves the house. In Québec, that's the right choice in most cases: in winter, a house almost always has too much humidity, not too little.
2505108Its HVI certification number
Listed in Section III of the Home Ventilating Institute's certified products directory. Anyone can check it.
−13 cfmWhat the ducts cost it
Between a nearly unrestricted test bench (0.2 in) and a real duct system (0.4 in), it drops from 127 to 114 cfm. Most spec sheets show only the first number, precisely because it looks better.
22 WMeasured at the airflow it actually runs at
Its 68% at 0 °C is certified at 64 cfm, the continuous airflow of a typical home. At that setting it draws 22 W, or about 193 kWh a year.
LifetimeThe core warranty
The core does the work and is the most expensive part to replace. Motors and parts: 5 years.
5 inWhat it needs on site
5 in ducts, side connection and a condensate drain. It weighs 40 lb, and it needs enough clearance to slide the core out for cleaning.
What it needs on site
In a condo with no floor drain, or with little ceiling clearance, we usually look at a side-port model instead. Our estimator checks the location, the drain and the duct route before ordering.
Complete spec sheetData and cited sources
- Net airflow at 0.2 in. w.g.
- 127 cfm
- Net airflow at 0.4 in. w.g.
- 114 cfm
- SRE at 0 °C (64 cfm)
- 68%
- SRE at −25 °C (55 cfm)
- 59%
- ASE at 0 °C
- 71%
- Power draw
- 22 W
- Efficacy
- 2.9 cfm/W
- Type
- HRV
- Connection
- Side ports
- Duct collars
- 5 in
- Condensate drain
- Required
- Defrost cycle
- Recirculation (motorized damper)
- Filters
- 2 washable MERV 6 filters (exhaust and supply); MERV 13 upgrade (65-195-6R)
- Dimensions (L × D × H)
- 25.75 × 20.19 × 9.75 in
- Weight
- 40 lb
- Power supply
- 120 V
- HVI certification (Section III)
- 2505108
- Warranty — core
- Lifetime
- Warranty — motors
- 5 years
- Warranty — parts
- 5 years
- Spec sheet (French)
- Spec sheet (English)
Net airflow, efficiency at 0 °C and −25 °C, and power draw: Home Ventilating Institute certified products directory, Section III (HVID 2505108). Annual consumption calculated at 22 W running continuously for 8,760 h, at Hydro-Québec's Rate D second tier (11.142 ¢/kWh), in effect since April 1, 2026.
The next model down and up
Talk to an HVAC technician before you choose
We assess your needs on site, check the location and the drain, and give you an installed price. Balancing is measured at commissioning, not estimated.
A 9.75 in. high HRV for condos and low ceilings
Only 9.75 in. high (add 1 in. for the drain cup underneath), the Lifebreath METRO 120D-ECM is a heat recovery ventilator (HRV) that mounts under the ceiling with the brackets supplied. Lifebreath designed it for apartments, townhomes and high-rise condos that are short on mechanical space.
In terms of airflow, it delivers 127 cfm net when static pressure is 0.2 in., and 114 cfm at 0.4 in. Compared with the METRO 120F-ECM, it defrosts differently: a recirculating damper here, the supply fan shutting off periodically on the F model. The "-ECM" suffix refers to its motors.
Two ECM Blowers, from 50 to 130 cfm
Two independent centrifugal blowers, one per airstream, run on high-efficiency, multi-speed ECM motors. Their operating range runs from 50 to 130 cfm, according to Lifebreath, and high speed is set with DIP switches. This lets the unit be matched to the airflow your home actually needs, without running it harder than necessary.
The difference shows on the bill. At the 64 cfm HVI test point, the METRO 120D-ECM draws 22 W, or 2.9 cfm per watt; at the same airflow, the METRO 120D needs 66 (HVI directory). Running continuously all year at that rate, that comes to about 193 kWh, around $21 at Hydro-Québec Rate D (second tier, 11.142 ¢/kWh).
Efficiency in the Dead of Winter
In the counter-flow aluminum HEX core, the stale air and the fresh air pass each other in opposite directions, separated by the core's walls, without ever mixing. At 0°C and 64 cfm, the sensible recovery efficiency is 68%. At −25°C and 55 cfm (26 L/s), its sensible recovery efficiency is 59% (HVI directory, November 4, 2026 edition). The Québec Construction Code (art. 9.36.3.9) requires at least 55% where there are fewer than 6,000 heating degree-days and 60% elsewhere, at no less than 22 L/s. The METRO 120D-ECM therefore clears the first threshold, not the second.
When it is colder than −3°C outside, a motorized damper periodically closes off the outdoor air inlet and the home's air recirculates through the core to defrost it. Lifebreath calls this an "intelligent" defrost with an ice-breaker feature, and no remote control can interrupt a cycle once it has started. The colder it gets, the more often defrost comes around: Lifebreath counts 3 minutes of defrost every 25 minutes of ventilation at −3°C, and 7 minutes every 15 at −35°C. During those minutes, no frigid air is pushed into the home.
Installation and Connections
The cabinet weighs 40 lb. Besides its 9.75 in. height, it measures 25.75 in. by 20.19 in. (20 3/16 in.). Lifebreath's METRO manual reserves wall mounting for the XTR models. Its four collars, all round, take 5 in. (125 mm) ducts.
A drain is required; Lifebreath provides a multi-position drain. Servicing calls for 25 in. (635 mm) of clearance at the front of the unit. Lifebreath also thought about access: the hinged door uses no screws, the swing-open e-box cover reveals the circuit board and its DIP switches, and the motor and electronics assembly comes out in one piece. The main control goes on a wall in a central room; Lifebreath calls for three-wire cable of 20 gauge or heavier, no more than 100 ft long. Its manual specifies that the 99-BC04 basic control cannot operate the METRO 120D-ECM, while the 99-DXPL03 works with every METRO.
Filter Care
Two washable MERV 6 filters keep the core clean, one in the stale airstream and the other in the fresh airstream. The METRO manual calls for cleaning or replacing them 4 times a year, and for cleaning the core and the inside of the cabinet twice a year. A MERV 13 kit (Lifebreath part 65-195-6R), ordered separately, filters the fresh air more finely, the only side it fits on; after its first installation, the unit's airflows must be rebalanced.
Warranty
Lifebreath warrants the core for life. Motors and parts are warranted for 5 years.
Installation by AirGreen in Greater Montreal
Before recommending the METRO 120D-ECM, we assess the home's ventilation needs on site (bedrooms, bathrooms, kitchen, basement). When those needs exceed its 114 cfm net at 0.4 in., the METRO 120D, which delivers 125 at the same point, takes over within the same series. In a condo, we also check that the door stays accessible with its 25 in. of clearance and that the ducts can reach the exterior wall.
Lifebreath wants the unit in a heated space: it names a closet, the top of a water heater or of a stacked washer and dryer, and advises against the attic. Above an area sensitive to water, its manual recommends an auxiliary drain pan. A clothes dryer, a range hood or a central vacuum must not be connected to the unit.
For the drain, we fasten the four-position spout with its four screws, preferably pointed toward the door hinges, and seal it with silicone. A 1/2 in. hose then runs down to a trap that must sit lower than the unit's door, then keeps a slope of 1/4 in. per foot to a nearby drain or a condensate pump, in a space that does not freeze. Outside, the fresh-air intake goes away from dryer vents, furnace exhausts and driveways, and the stale-air outlet clear of meters and of walkways where ice would be a hazard, as Lifebreath requires.
Power comes from a dedicated 120 V outlet, with no extension cord, ideally on its own 15 A circuit; Lifebreath also offers a permanently wired version. On start-up day, we measure the static pressure of the supply and exhaust ducts: Lifebreath considers the METRO 120D-ECM factory balanced as long as the gap between the two stays under 0.3 in., which keeps its two airflows within 10% of each other.
Our team, under AirGreen's RBQ licence 5645-9605-01, installs the METRO 120D-ECM in Montreal, Laval, Longueuil, the North Shore and the South Shore.
Since October 1, 2026, Rénoclimat no longer funds HRV or ERV installations, except for a home already evaluated before the change whose post-work evaluation is done by March 31, 2027.
For a free quote, call us at 514 316-2973 or write to sales@airgreen.ca: we will call you back.