A service call in a café in the heart of Côte-des-Neiges
At AirGreen , we were recently contacted by a café owner in Montreal's Côte-des-Neiges neighborhood whose Daikin wall-mounted air conditioner was no longer working properly. In the middle of August, with a packed room and temperatures exceeding 30°C, customer comfort was seriously compromised. Our team quickly scheduled an emergency HVAC intervention to diagnose and repair the problem on-site.
Diagnosis: Blocked airflow and faulty sensor
Upon arrival, our technician noticed that the indoor wall unit—installed near the ceiling, above a curtain separating the kitchen from the dining room—was displaying a flashing light and was no longer producing cold air.
After removing the facade, we carried out several checks:
-
Air filters completely clogged with dust and grease from the surroundings (kitchen environment).
-
Evaporator coil covered with a greasy film reducing heat exchange.
-
Indoor temperature sensor (thermistor) showing inconsistent reading, causing compressor to automatically shut off.
To confirm the diagnosis, we measured the refrigeration pressures and discharge temperature: everything indicated a sensor malfunction rather than a lack of refrigerant.
Intervention: deep cleaning and sensor replacement
The work took place in three stages:
-
Complete cleaning of the indoor unit :
-
Remove and wash the filters in warm soapy water.
-
Application of a biodegradable product to the evaporator coil.
-
Steam rinse to remove greasy residue.
-
-
Replacing the temperature sensor :
-
Installation of an original Daikin sensor compatible with the FTXS series model.
-
Checking the ohmic signal and calibrating via the electronic card.
-
-
Full system test :
-
Restart the compressor and measure the delta T between suction and discharge.
-
Static pressure and air flow control at the outlet grille.
-
Result: a stable blowing temperature at 17°C and silent operation, proof of restored efficiency.
AirGreen Expertise: recommended preventive maintenance
We took advantage of this visit to recommend quarterly preventative maintenance , which is particularly essential in catering businesses where dust and cooking fumes accumulate quickly.
Our recommendations to the owner:
-
Clean the filters every two weeks .
-
Have the coil professionally cleaned twice a year.
-
Avoid blocking the airflow with curtains or hanging objects (as was the case here).
Thanks to this quick repair, the client was able to reopen the air-conditioned room the same day, thus avoiding loss of revenue and customer dissatisfaction.