Réparation d’un climatiseur mural Zephyr à Sainte-Julie
Job photo

Performance diagnosis: air less cold than expected

At AirGreen , we were contacted by a Sainte-Julie customer concerned about the reduced performance of their Zephyr wall-mounted air conditioner . Despite regular maintenance, the unit was no longer producing air cool enough to maintain the desired indoor temperature. One of our certified technicians was dispatched to the site to perform a complete diagnosis of the HVAC system .

Step 1: Measuring the blowing temperature

The first step was to measure the temperature of the blown air using a precision infrared thermometer . The reading was 11.2°C , while the ambient temperature was around 20°C . This discrepancy, although indicating minimal compressor operation, suggested a partially reduced efficiency of the unit.

Our technicians know that for a Zephyr wall-mounted air conditioner in good condition, the difference between the suction and discharge temperatures should normally exceed 10 to 12 °C . In this specific case, the difference was at the acceptable limit - a sign of a weakened refrigerant level or internal fouling .

Step 2: Checking the refrigeration circuit

After turning off the power and securing the workstation, we carried out an inspection of the refrigeration circuit . A slight trace of oil around the flare connection of the external compressor confirmed a micro-leak of refrigerant .

We then have:

  • performed a nitrogen leak test at 350 psi;

  • detected the leak using an electronic detector ;

  • replaced and tightened the flare fitting ;

  • then recharged the system with R410A refrigerant according to the nominal quantity from the manufacturer Zephyr.

Step 3: Cleaning and Recalibration

Before restarting the system, the internal filter and evaporator were cleaned with a biodegradable product to remove accumulated dust. The tangential fan was also balanced to reduce vibration and noise.

Once the circuit was recharged, the technician took another measurement: 6.8°C at the outlet , an efficiency gain of almost 40% . The air conditioner returned to optimal performance , ensuring constant comfort in the main room.

Step 4: Preventive Maintenance Tips

As always, our team took the time to explain to the customer some simple practices to extend the life of their device:

  • clean the air filter every four weeks during the summer season;

  • keep the outdoor condenser clear of any obstacles;

  • schedule an annual professional interview before each summer.

Final result

Thanks to a quick and methodical intervention, the Zephyr wall-mounted heat pump was able to regain its full efficiency. The customer immediately noticed the difference: cool, quiet, and stable air, even in the heat.

At AirGreen , we combine precise diagnosis , careful repair and local expertise to ensure the comfort of our customers in Montreal, Laval, Longueuil, the North Shore and the South Shore .

You made it to the end.Share it with someone it could help.
Near you

More AirGreen jobs in the area

Other jobs, not the one described above.

Keep reading

Latest published jobs

AirGreen Climatisation & Chauffage

The same service at your place?

Cleaning, repair or maintenance: tell us about your unit and we schedule the visit.

  • RBQ licence 5645-9605-01Subclasses 15.8, 15.10 and 16
  • $5M liability insuranceOn every job
  • 15+ yearsFamily-owned, based in Montréal