Réparation d’une thermopompe murale Friedrich à Blainville
Reading time: 3'

Repair of a Friedrich wall-mounted heat pump in Blainville

A winter breakdown quickly brought under control

Quebec winters put HVAC systems to the test, and a simple drop in performance can quickly become a major inconvenience. This is exactly what one of our customers in Blainville experienced when their Friedrich wall-mounted heat pump stopped defrosting properly at the height of the cold season. At AirGreen , we quickly responded to diagnose and resolve the problem, restoring indoor comfort within hours.

The context of intervention

Installed on a north-facing brick wall, the Friedrich outdoor unit was exposed to wind and snow accumulation. The customer contacted us after noticing:

  • a lack of heat in the house ,

  • a more frequent defrost cycle than usual ,

  • and an irregular whistling noise when starting.

These signs often indicate restricted airflow or an imbalance in the refrigeration circuit , two common problems on units subjected to extreme winter conditions.

On-site diagnosis

Upon our arrival, our technicians conducted a complete inspection of the Friedrich unit. The main observations were as follows:

  • Ice buildup on the lower part of the outdoor coil, indicating partial defrosting.

  • Spool slightly clogged with dust and frozen particles.

  • Slightly low refrigerant level , confirming a small leak on a flare fitting.

  • Defrost sensor showing resistance outside normal values.

Using our digital measuring instruments and a portable charging station, we were quickly able to confirm that the system was suffering from both a micro-leak of R-410A refrigerant and a faulty thermal sensor , preventing optimal defrosting.

Steps of repair

1. Defrosting and preparing the unit

We first defrosted the outdoor coil thoroughly using a defroster safe for aluminum surfaces. Once the ice was removed, we cleaned the heat exchanger grille to maximize airflow.

2. Leak detection and repair

Using an electronic leak detector , we located the problem point on a slightly loose flare fitting . After cleaning, we resealed the joint and applied a tightening torque according to Friedrich specifications.

3. Vacuum drawing and recharging the circuit

A 20-minute vacuum was applied to remove any moisture. The system was then recharged with R-410A at the manufacturer's recommended pressures.

4. Replacing the defrost probe

We replaced the faulty thermal sensor with an original Friedrich sensor , guaranteeing an accurate and efficient defrost cycle even in very cold weather.

Checks and results

After restarting, the Friedrich heat pump displayed optimal performance values :

  • Indoor blowing temperature: 32°C ,

  • Balanced and stable pressure in the circuit,

  • 6 minute defrost cycle, in accordance with manufacturer standards.

The client immediately felt an improvement in comfort and a reduction in perceived noise. The heat pump now operated smoothly and energy-efficiently, despite the -15°C outside temperature.

AirGreen Tips for Winter Maintenance of a Wall-Mounted Heat Pump

  1. Clear snow regularly around the outdoor unit to prevent ice buildup on the coil.

  2. Avoid covering the unit completely , even in winter — a rigid protective cap is sufficient.

  3. Schedule annual preventative maintenance before the cold weather sets in to check pressures and sensors.

  4. Monitor defrost cycles : if they become more frequent or longer, it's time to call a professional.

AirGreen: expertise, rigor and proximity

Our team of HVAC experts operates throughout Montreal , Laval , Longueuil , the North Shore and the South Shore , with repair, maintenance and installation services tailored to all brands — including Friedrich, Fujitsu, Midea, Sharp, Gree, and more.

Each intervention is an opportunity for us to demonstrate our know-how: diagnose precisely, intervene effectively and guarantee the long-term reliability of your HVAC system .