Heat pump failure on a flat roof in Montreal
In the heart of the Rosemont–La Petite-Patrie neighborhood, a client who owns a duplex called us after noticing that his Fujitsu wall-mounted heat pump installed on the roof was no longer producing cooling. The outdoor compressor seemed active, but the air inside remained lukewarm, making summer days uncomfortable.
At AirGreen , we understand that a heat pump installed on a flat roof is exposed to demanding conditions: intense heat in the summer, extreme cold in the winter, and debris buildup. These elements can quickly affect the system's performance if rigorous maintenance is not performed.
Initial diagnosis: loss of efficiency and pressure fluctuation
Upon our arrival, our technician secured access to the roof using his safety equipment, before carrying out a complete check of the Fujitsu AIRSTAGE system .
Initial pressure measurements revealed low pressure on the evaporator side and rapid fluctuations on the pressure gauge , a classic sign of a lack of R-410A refrigerant or a partial obstruction in the circuit .
After a careful visual inspection, we spotted traces of oil at the base of the compressor , indicating a slow leak. This situation explains why the customer had been observing increasingly low performance over the past few weeks.
Technical intervention: rigor and precision
Once the diagnosis was confirmed, we took the following steps:
-
Complete cleaning of the outdoor condenser , clogged with dust and accumulated particles from the roof.
-
Leak detection using an electronic detector and nitrogen test. The leak came from the flare fitting of the liquid line , which was slightly cracked.
-
Replaced the fitting and completely tightened to Fujitsu torque standards.
-
Complete vacuuming of the circuit for 45 minutes to eliminate all traces of humidity.
-
Recharge the system to the exact pressure recommended by the manufacturer for this model.
-
Operation test in cooling and heating mode to ensure inverter stability and correct defrost cycle.
The results were excellent:
-
Pressure stabilized at 120 PSI (low) and 400 PSI (high);
-
Indoor outlet air temperature at 8°C after 10 minutes of operation;
-
No abnormal noise or vibration detected.
Roof installation: specific features and precautions
HVAC systems installed on flat roofs , as is often the case in Montreal, present certain challenges:
-
direct exposure to sunlight, which increases the operating temperature;
-
increased risk of condensation and thermal expansion;
-
restricted access requiring specialized tools.
That's why our AirGreen technicians undergo advanced roof safety training and use reinforced anti-vibration mats to extend the life of the unit.
During this intervention, we also replaced the anti-vibration shims under the heat pump and checked that the condensates were draining properly.
Result: comfort restored and efficiency regained
As soon as the repair was completed, the customer immediately noticed the difference:
-
rapid cooling of the main room;
-
quieter operation of the outdoor unit;
-
significant reduction in temperature variations.
We concluded the visit with personalized maintenance recommendations :
-
cleaning the internal filter every month during the summer,
-
visual inspection of the condenser twice a year,
-
and annual refrigerant charge verification by an AirGreen certified technician.
AirGreen: your HVAC partner in Montreal and throughout the region
At AirGreen , we put our expertise in Fujitsu wall-mounted heat pumps at the service of residents of Montreal, Laval, Longueuil, the North Shore and the South Shore .
Our teams stand out for their meticulous approach and attention to detail, whether for a one-off repair , preventive maintenance or a complete installation .
Each intervention is documented with photos, performance measurements and advice tailored to the client's environment.
Our goal: to guarantee the lasting comfort and energy performance of each HVAC system installed or maintained by us.
In conclusion
This Fujitsu heat pump repair in Rosemont–La Petite-Patrie perfectly illustrates the rigor and precision of our work. Thanks to a rapid diagnosis and comprehensive intervention, we not only restored the customer's comfort, but also optimized the system's durability for many years to come.