Diagnosis · Chomedey (Laval)

Repair of a Goodman wall-mounted heat pump in Chomedey (Laval): complete recommissioning on a wall bracket

Wall-mounted heat pump Goodman 5 min
Réparation d’une thermopompe murale Goodman à Chomedey (Laval) : remise en service complète sur support mural

In the Chomedey sector of Laval , we serviced a Goodman wall-mounted heat pump (mini-split) installed high on a brick facade, directly under a balcony. This type of installation is common in residential buildings (condos, plexes, co-ownerships): the outdoor unit is mounted on wall brackets to free up floor space, protect the unit from snow accumulation, and keep a yard or parking area clear.

This visit was for a repair (not an installation): the client contacted us because the system was no longer delivering the expected comfort, with performance becoming erratic over the weeks.


Context: reported symptoms and initial observations

Upon our arrival, the client described typical signs of a problem that is gradually “taking hold”:

  • Insufficient cooling in air conditioning mode (interior temperature drops very slowly).

  • Short cycles : the unit would start, then stop quickly.

  • Noise is more noticeable outside during start-up attempts.

  • The heat pump feels like it's "working hard", without a proportional result.

Visually, the installation presented several elements useful for diagnosis:

  • Goodman outdoor unit mounted on metal brackets on the wall.

  • Electrical disconnect box installed nearby.

  • Refrigerant lines running inwards (consistent layout, but exposed to temperature variations and vibrations, which can affect the fittings over time).

  • Position under balcony: partial protection, but be careful of clearance and air circulation.


AirGreen diagnosis: method, measurements and validation

At AirGreen, we don't "guess." A drop in performance on a wall-mounted heat pump can stem from several causes: fouling, ventilation, electronics, sensors, drainage, or even the refrigerant circuit. Our diagnosis therefore followed a logical sequence.

1) Verification of operating parameters

We first confirmed:

  • Requested mode (air conditioning/heating) and setpoint.

  • Response of the indoor unit (airflow, louver behavior, stability).

  • Anomalies were present at startup.

2) Mechanical inspection and ventilation (exterior)

On the outdoor unit:

  • General condition check, fixing of supports, vibrations.

  • Fan propeller and motor check (no blockage, correct rotation).

  • Coil inspection (cleanliness, debris, partial obstruction).

A clogged coil can be enough to cause a drop in performance, but in this particular case, dirt alone did not explain the symptoms.

3) Electrical measurements and protections

We then checked:

  • Power supply to the disconnect switch.

  • Voltage stability.

  • Connections and signs of overheating.

Everything was in order, which led us to a more thorough diagnosis of the refrigeration circuit .

4) Most likely hypothesis: pressure drop / slight leak

The symptoms (gradually decreasing performance, unstable cycles, lack of “cooling power”) are often consistent with an insufficient refrigerant charge , usually caused by a micro-leak (often on flare fitting, especially when the unit is high up and subject to more vibration and expansion).

We therefore carried out confirmation tests.


Repair: Steps taken on the Goodman wall-mounted heat pump

Step 1 — Locating the leak (rigorous approach)

We inspected the sensitive areas:

  • Flare fittings and accessible connections.

  • Tracing of connections, friction zones.

  • Signs of oil (a common indicator of a slow leak).

After checks, the analysis converged on a fitting with insufficient sealing (typical: slight play, micro-irregularity, or tightening that has changed over time).

Step 2 — Reconnecting the joint: re-flare and adjustment

We dismantled the relevant section, then:

  • Resumed the preparation of the tube (clean cut, deburring).

  • Created a high-quality flare (uniform geometry).

  • Replace the fitting with controlled tightening to avoid:

    • under-tightening (leak),

    • overtightening (flare crack).

Step 3 — Leak test and pressurization

Before putting the system back into service, we carried out the following:

  • A leak test (pressure testing procedure).

  • Confirmation that there was no further loss at the connection point.

This is an essential step: recharging a system without ensuring it is airtight guarantees the problem will return.

Step 4 — Vacuuming and recharging

Once the seal is confirmed:

  • Complete vacuuming with a stable vacuum objective (proof of absence of moisture and residual leaks).

  • Recharging according to system parameters and link length (methodical and measured approach).

Step 5 — Performance testing under real-world conditions

After restarting, we confirmed:

  • Stability of pressures and temperatures.

  • Heat transfer quality (clear improvement in cooling).

  • Absence of a short cycle.

  • Normalized noise level.

Result: the Goodman heat pump has returned to stable operation, with a noticeable performance recovery almost immediately.


Installation details observed: what this photo tells us (and what we are monitoring)

This installation, typical of condominiums, has a few key points:

  • Outdoor unit on wall brackets : excellent for avoiding snow and clearing space, but it increases the importance of anti-vibration and the quality of the connections.

  • Installation at height : makes access more technical (safety, ladder, handling), and can complicate maintenance if periodic inspections are not planned.

  • Proximity to a balcony : good clearance must be maintained for the unit to breathe. Reduced air circulation can degrade efficiency and put strain on the compressor.

Our recommendation, after repair, therefore included a simple reminder: an annual check (or every two years depending on usage) limits surprises, especially when the unit is exposed to freeze/thaw cycles and vibrations.


Results: restored comfort and peace of mind

After the procedure:

  • The customer has regained efficient and consistent cooling .

  • The system has stopped "straining" unnecessarily, which helps to protect the compressor.

  • The cycles have returned to normal, with better temperature stability.

Beyond repair, the objective is always the same: to restore comfort , reduce the risk of recurrence and extend the lifespan of the equipment.


Why entrust a Goodman repair to AirGreen in Laval?

Because on a wall-mounted heat pump, the quality of a repair depends on:

  • the accuracy of the diagnosis (avoiding unnecessary replacements),

  • the rigor of the leak tests,

  • the recharging procedure,

  • and the final validation under real-world conditions.

In Chomedey as elsewhere in Greater Montreal, we intervene with the same approach: methodical, documented, results-oriented .

You made it to the end.Share it with someone it could help.
Near you

More AirGreen jobs in the area

Other jobs, not the one described above.

Keep reading

Latest published jobs

AirGreen Climatisation & Chauffage

The same service at your place?

Cleaning, repair or maintenance: tell us about your unit and we schedule the visit.

  • RBQ licence 5645-9605-01Subclasses 15.8, 15.10 and 16
  • $5M liability insuranceOn every job
  • 15+ yearsFamily-owned, based in Montréal